Kukdong LSHF - NEK 606 2004

 Application Power circuit below 1kV, Motor Power circuit for PWM AC Drives. Fixed installation power in both explosion risk and safe areas, general purpose. Maximum operating conductor temperature 90 Standard Applied Design guideline : Material properties : Flame retardant : Halogen free properties : Low smoke properties : Cold properties(option) : Sunlight resistance(option) : Mud resistance(option) :

  e   e   m   a    l     l     b    F   a   e   C   g   t   a   n    t     l   a   o    d    V   r   a     h   t   e   g   R    i    H

IEC 60092-353 IEC 60092-351 (Insulation, HF-EPR) IEC 60092-359 (Sheath, SHF2) IEC 60332-3-22, Cate. ‘A’ IEC 60754-1 IEC 61034-1/2 CSA C22.2 No. 03 UL 1581 NEK 606 (2004)

0.6/1kV THREE CORE+THREE EARTH, ARMORED POWER CABLE (Code : 0.6/1kV RFOU-EMC, RFOU-EMC ‘MR’) No. of core

EA 

3+3E

Nominal sectional area

Conductor Min. Max. No. of overall wires dia.

Thickness Thickness of of inner insulation covering

mm2

EA

mm

mm

25 6 35 10

7 7 7 7

6.6 3.3 7.9 4.2

1.2 1.0 1.2 1.0

50 10 70 16 95 25 120 25 150 35 185 35 240 50

19 7 19 7 19 7 37 7 37 7 37 7 61 19

9.1 4.2 11.0 5.3 12.9 6.6 14.5 6.6 16.2 7.9 18.0 7.9 20.6 9.1

1.4 1.0 1.4 1.0 1.6 1.2 1.6 1.2 1.8 1.2 2.0 1.2 2.2 1.4

300 50

61 19

23.1 9.1

2.4 1.4

Nominal dia. over inner covering

Dia. of metal  wire for braid

Nominal dia. over braid

Thickness of outer sheath

Nominal overall dia.

Cable  weight  approx 

mm

mm

mm

mm

mm

mm

kg/km

1.0

23.2

0.3

24.8

1.8

28.6 1.1

1775

1.2

27.1

0.3

28.7

1.9

32.7 1.3

2375

1.2

28.1

0.3

29.7

2.0

33.9 1.4

2860

1.2

32.2

0.4

34.2

2.2

38.8 1.6

3950

1.4

37.3

0.4

39.3

2.4

44.3 1.8

5390

1.4

40.8

0.4

42.8

2.5

48.0 1.9

6330

1.4

45.1

0.4

47.1

2.7

52.7 2.1

7780

1.6

50.2

0.4

52.2

2.9

58.2 2.3

9315

1.6

56.9

0.4

58.9

3.2

65.5 2.6

12005

1.8

63.1

0.4

65.1

3.4

72.1 2.9

14395

Construction Conductor : Circular tinned stranded copper as per IEC 60228 & 60228A, Class 2 Insulation : Halogen Free Ethylene Propylene Rubber (HF-EPR) as per IEC 60092-351 Cabling (with filler) Inner covering : Halogen-free thermosetting compound Amour(screen) : Cu/PS tape & Copper wire braid combination 100% shield screen. Outer sheath : Flame retardant, oil, abrasion, chemical and sunlight resistant. - Halogen-free thermosetting compound as per IEC 60092-359, SHF2 - ’MR’ : Halogen-free & Mud resistance thermosetting compound as per IEC 60092-359, SHF Mud

Identification of color Insulation 3 : Grey, Black, Red Earth : Green or Green/Yellow stripe Outer sheath : Black Note) Any other colors purchaser required

Conductor resistance (20 )

Cable rating at 45

/km

 Amp.

0.734 3.11 0.529 1.84 0.391 1.84 0.270 1.16 0.195 0.734 0.154 0.734 0.126 0.529 0.1000 0.529 0.0762 0.391 0.0607 0.391

  e   e    l     b   m  a   a   C     l    F   t   e   n   a   g   t   a   s    t     l    i   s   o   e    V   R     h   e   r   g   i    i    F    H    &

89 110 137 169 205 237

  e   e   m   l   a   b    l    F   a   e   C   g   t   a   n    t   a    l    d   o   r    V   t   a   e   w   R   o    L

272 311 365 421

IEC 60332-3-22 : Flame retardant, Cate ‘A’ IEC 60754-1 : Halogen free, 0.5% IEC 61034-1/2 : Smoke density CSA C22.2 No.03 : Cold bend, 40

Cold impact, 35

  e     l   e    b   m  a   a   C     l    F   t   e   n   a   g   t   s   a   i    t   s     l   e   o   R    V   e   r   w   i   o    L    F    &

UL 1581 : Sunlight resistance NEK 606 : Mud resistance EMC : Electromagnetic Compatibility

Technical specification Voltages Rated AC and DC voltage Uo/U(Um) ; 0.6/1(1.2)kV Max. permissible periodic peak voltage : 2kV AC test voltage : 5kVeff (Standard test voltage 3.5kV/5min) Min. bending radius : 6 cable outside diameter Max. permissible tensile load : 50N/mm 2(sum of cross-section of all conductors in mm 2) Permissible operation with conductor earth fault in non-earthed n etworks ; max. eight hours, but not more than 125hours within a period of one year.

Marketing Office Tel:82-2-2140-3055 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2144 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297

89

  n   o    i    t   a   m   r   o     f   n    i     l   a   c    i   n     h   c   e    T

Sponsor Documents

Or use your account on DocShare.tips

Hide

Forgot your password?

Or register your new account on DocShare.tips

Hide

Lost your password? Please enter your email address. You will receive a link to create a new password.

Back to log-in

Close