iRed
Thermographic Consultants

No Name Ltd. 1. Some Road. Near A Town. Hidden Dangers.

Priority 2

Quality Audit Trail Information
Image Date/Time Camera Serial No Image Number 14/10/2006 15110274 E1014-07.img 09:27:20

38.0°C 38 36 34 32

Thermographers Collated Data
Emissivity Setting Distance from object Background Tamb Room Temperature 0.85 1.0 m 17.6°C 21
Spot 1 AR01

30 28 26 24 22 20

Electrical Load Recorded Data
Load reading taken at survey Total load as per circuit chart Not Required For This Survey
Label

Reference Spot

19.0°C

Predicted Load correction Results
Value 29.4°C 20.8°C 23.2°C

Actual Spot 1 measured temp Reference Spot temperature Actual Delta T Rise Predicted Full Load Delta T Rise Predicted max temp at full load

28.9°C 27.6°C 1.25 °C * *

AR01 : max AR01 : min AR01 : avg

Engineers specific comment : There are issues with some of the breakers on this board. However, a trained thermographer would be particularly interested in the small heat flare running down the cable on the red phase. (Spot1 to Ref spot). Without the use of a thermal camera this anomaly would proably gone unnoticed. SEE NEXT PAGE.

General Comments The overall condition of the unit was good. No visible damage was evident. Access to unit was also acceptable.

iRed limited R

Colt House New Lane Havant Hampshire PO9 2LY Tel 02392 484400

Fax 02392 484411 e-mail [email protected] web www.ired.ltd.uk

OP/04/B/FE/05

4404/04

iRed
Thermographic Consultants

No Name Ltd. 1. Some Road. Near A Town. Hidden Dangers Revealed.

Priority 1

Quality Audit Trail Information
Image Date/Time Camera Serial No Image Number 14/10/2006 15110274 E1014-09.img 09:34:44
AR01

140.0°C 140

120

Thermographers Collated Data
Emissivity Setting Distance from object Background Tamb Room Temperature 0.85 1.0 m 17.6°C 21
Spot 1

100

80

60

40

Electrical Load Recorded Data
Load reading taken at survey Total load as per circuit chart Not Required For This Survey
Label

Reference Spot

20 18.0°C

Predicted Load correction Results
Value 167.1°C 19.9°C 30.3°C

Actual Spot 1 measured temp Reference Spot temperature Actual Delta T Rise Predicted Full Load Delta T Rise Predicted max temp at full load

167.0°C 57.5°C 109.49 °C * *

AR01 : max AR01 : min AR01 : avg

Engineers specific comment : Once the safety cover had been removed by the Electrician the true danger was revealed. Spot 1 is measuring the temperature on the terminal screw head, the area to the left of this is a small burning hole. This can be seen in the digital image.

General Comments The overall condition of the unit was good. No visible damage was evident. Access to unit was also acceptable.

iRed limited R

Colt House New Lane Havant Hampshire PO9 2LY Tel 02392 484400

Fax 02392 484411 e-mail [email protected] web www.ired.ltd.uk

OP/04/B/FE/05

4404/04

iRed
Thermographic Consultants

No Name Ltd. 1. Some Road. Near A Town. Predictive Loading.

Priority 2

Quality Audit Trail Information
Image Date/Time Camera Serial No Image Number 12/05/2007 15110274 E7012-97.img 11:13:36

AR01

45.0°C 45

40

Thermographers Collated Data
Emissivity Setting Distance from object Background Tamb Room Temperature 0.85
Spot 1

35

1.5 m 20.1°C 21

30

25

Electrical Load Recorded Data
Load reading taken at survey Total load as per circuit chart 33 63
Label

Reference Spot

20 20.0°C

Predicted Load correction Results
Value 45.2°C 22.5°C 26.5°C

Actual Spot 1 measured temp Reference Spot temperature Actual Delta T Rise Predicted Full Load Delta T Rise Predicted max temp at full load

39.7°C 29.7°C 9.98 °C 36.36 °C 66.05 °C

AR01 : max AR01 : min AR01 : avg

Engineers specific comment : This image clearly shows a hotspot (anomally) with a flare dissipating along the cable.However, with the aid of a clamp meter we are now able to predict what would happen to that circuit under full load conditions.

General Comments The overall condition of the unit was good. No visible damage was evident. Access to unit was also acceptable.

iRed limited R

Colt House New Lane Havant Hampshire PO9 2LY Tel 02392 484400

Fax 02392 484411 e-mail [email protected] web www.ired.ltd.uk

OP/04/B/FE/05