PROTECTIVE FUNCTION TURBINE TRIPs VIBRATION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION
ACTION SETPOINT (Nominal Setpoints)
GT Vibration Sensor Fault
L39VT
PROTECTIVE STATUS 2
Initiate a trip to avoid machine damage
39V1A,1B,2A,2B,4A,4B & 5A.
Trip when any detector measures vibration above trip level AND other detector in that pair is disabled or measures above alarm level for LK39TTD
See Control Spec: Trip Level LK39VTx = 1.0 inch/sec Alarm Level LK39VAx = 0.5 inch/sec LK39TTD= 0.5 sec
GT EXHAUST TEMPERATURE AND PRESSURE Trip when 96EP-1 pressure transmitter exceeds limit AND at 63ET-1,63ET-2 least one of the two 96EP-1 exhaust pressure trip switches 63ET-1 or 63ET-2 is picked up. Trip when exhaust temperature exceeds Exhaust Temperature TTKOT1 limit or when it TC's exceeds exhaust temp TT-XD-1 through 31 reference by TTKOT2 deg F. See Control Spec and Device Summary: 63ET-1:INCREASING: 24.0+-0.5 INH2O 63ET-2:INCREASING: 24.0+-0.5 INH2O KAFPEPHH=24 INH2O See Control Spec: TTKOT1 = 1240F TTKOT2 = 40F
Exhaust Duct Pressure High Trip
L63ETH
PROTECTIVE STATUS
Possible damage to exhaust system due to high pressure
Exhaust Overtemperature Trip
L86TXT
PROTECTIVE STATUS
Overtemperature of hot gas path components
Exhaust Overtemperature Trip
L86TXT
POST IGNITION TRIP
Overtemperature of hot gas path components
Exhaust Temperature TC's TT-XD-1 through 31
Trips when exhaust temperature exceeds TTKOT1,6,5 (TTRXB+TTKOT2)
See Control Spec: Over.temp trip isothermal settingTTKOT1 = 1240F Over.temp trip incremental setting.TTKOT2 = 40F diff Low range exhaust temp limit TTKOT5= 1215 F High range ex
Exhaust Thermocouples Open Trip
L86TFB
PROTECTIVE STATUS
Potential loss of temperature control and protection
Exhaust Temperature TC's TT-XD-1 through 31
Trip when exhaust temperature signal drops below TTKXM4 deg F while in operation.
SIZE CAGE CODE
See Control Spec: TTKXM4 = 250F Failed TC alarm constant
DWG NO
g
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE CONT ON SHEET
0476
DISTR TO
DRAWN ISSUED
2 of 13
SIZE
B
DWG. NO.
401B3661
SH.
3
REV.
-
PROTECTIVE FUNCTION Compressor Discharge Pressure Low EXHAUST FRAME AND #2 BEARING High Load Tunnel Temperature Trip LUBE OIL AND HYDRAULIC OIL PROTECTION LOW LUBE OIL PRESSURE TRIP
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION Potential loss of temperature control and protection
DETECTION METHOD
LOGIC DESCRIPTION Trip when compressor discharge pressure drops below CAKCPD psig when Gen breaker is closed.
ACTION SETPOINT (Nominal Setpoints) See Control Spec: CAKCPD = 35 psig
L3TFLT
PROTECTIVE STATUS
96CD-1, 1B, 1C
L30LTT
PROTECTIVE STATUS
Protect vibration monitor components
TT-IB-1,TT-IB-2,TT-IB3
Trip when Load Tunnel Inner Barrel Temp exceeds LTKTRIP deg F.
See Control Spec: LTKTRIP=500.0 degF
L63QTX
PROTECTIVE STATUS
Loss of bearing lubrication
96QT-1, 2, 3
2oo3 sensors reading low lube oil header pressure
15 psig QHTPK = customer specified DECREASING: 20.0+-2.0 PSIG OR 1.4061+-0.1406 KG/Cm2G (INCREASING: 22.0+-2.0 PSIG OR 1.5468+-0.1406 KG/Cm2G) NORM=(1) NO-CEC;
Trip Oil Pressure Low
L63HGL
PROTECTIVE STATUS
Loss of trip oil pressure to maintain stop/control valve position
63HG-1,2,3
2oo3 sensors reading low trip oil header pressure
COMBUSTION MONITOR AND GT FLAME DETECTION Trip occur (1) Spread See Control Spec: #1 > Allowable spread K30SPT= 2sec Allowable Spread limit Exhaust Temperature or (TTXSPL) = Calculated TC's Spread #1 (varies between TTKSPL7 TT-XD-1 through 31 >TTXSPL_Z1 and TTKSPL6 (30-125 AND Spread#2 is 0.8 degF) Compressor times greater rhan Steady state allowable Discharge TC's allowable spread when spread = function CT-DA-1, 2, 3 2nd and 3rd coldest (exhaust temperature, TC's are adjacent after compressor discharge K30SPT seconds temperature)
High Exhaust Temp Spread Trip
L30SPT
PROTECTIVE STATUS
Possible partial combustor flameout
g
SIZE
CAGE CODE
DWG NO
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
3 of 13
SIZE
B
DWG. NO.
401B3661
SH.
4
REV.
-
PROTECTIVE FUNCTION Loss of Flame Trip STARTING MEANS
SIGNAL NAME L28FDT
TYPE PROTECTIVE STATUS
DESIGN JUSTIFICATION Unburned fuel in hot gas path
DETECTION METHOD 28FD-1, 2, 3, 4
LOGIC DESCRIPTION Trip when two of the four combustor flame detectors indicate loss of flame. Trip when 1) Turbine Speed falls below highest attained speed by more than the allowable limit (LK60BOG1) for LK60BOG2 seconds, OR (2) Static starter fails to start after getting start up permissiv e After run and Torque command is giv en to startic
ACTION SETPOINT (Nominal Se tpoints) See Control Spec
GT COMPRESSOR PROTECTION Trip when difference between IGV position feedback (CSGV) and IGV refrence angle (CSRGV) is greater than LK86GVT1 DGA for more than LK86GVT2 sec below L14HS (95% speed), or when IGV position feedback (CSGV) is less than LK4IGVTX DGA abov L14HS e (95% sp Trip when any bleed v alv is not full open e after a time delay of K20CBY sec while the gen circuit breaker is open or the turbine drops below L14HS (94% speed) Trip when compressor pressure ratio, offset by CPKERRO, exceeds the compressor operating limit line by CPKERRMX for CPKERRTD sec.
SIZE CAGE CODE
IGV CONTROL TROUBLE TRIP
L4IGVT
PROTECTIVE STATUS
Impending loss compressor operating margin
96TV-1, -2 90TV-1
See Control Spec: LK86GVT1 = 7.5 DGA LK86GVT2 = 5 sec LK4IGVTX = 38 DGA
Compressor bleed v alv position fault e
L86CBT
PROTECTIVE STATUS
Impending loss compressor operating margin
33CB-1, 2, 3, 4
See Control Spec: K20CBY = 11 sec
Compressor Operating Limit Protection Trip
LCPRERR
PROTECTIVE STATUS
Compressor operation exceeds design limits
96CD-1, 1B, 1C
See Control Spec: CPKERRTD=3 sec CPKERRMX = -0.45 CPKERRO = 0.25
g
DWG NO
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
4 of 13
SIZE
B
DWG. NO.
401B3661
SH.
5
REV.
-
PROTECTIVE FUNCTION FUEL CONTROL Gas Aux Stop Position Fault PreIgnition Trip
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip if the aux stop valve is commanded open and does not open or open fully before flame is detected. Trip when SRV position feedback, fsgr, exceeds startup fuel stroke reference high setpoint, LK60FSGH, and the warmup is not complete and also leak test master should be enabled. If you are on Liquid fuel and if flow divider speed FQL1 is higher than constant LK60FFLH FOR K2SFTL time In liquid fuel , turbine trip is intiated whenever fuel flow is high after completion of warmup,accelerating stage and no liquid fuel recirculation Trips when the firing timer, K2F, expires and when flame is not detected from 2 of 4 flame detectors after giving startcommand K6TT2 times and on total gas.
ACTION SETPOINT (Nominal Setpoints)
L4VS4_PI
PRE IGNITION
Prevent failed start caused by loss of gas flow
33VS4-1, 2
NA
Startup Fuel Flow High
L2SFT
PROTECTIVE STATUS TRIP 2
Prevent excessive fuel caused by valve control failure at ignition
Gas: 96SR-1,2 Liquid: 77FD-1,2,3
See Control Spec: LK60FSGH = 20%,LK60FFLH=14%
Failure to Ignite on Gas
L94FIG L4FIGFLT
PRE IGNITION TRIP L4PRET
Prevent excessive fuel caused by ignition failure
28FD-1, 2, 3, 4
See Control Spec: K2F = 30 sec K6TT2= times
Successive Failure to Ignite on Gas
L86FIGFLT
PRE IGNITION
Prevent excessive fuel caused by ignition failure
28FD-1, 2, 3, 4
Successive Failures to K62TT2 = 2 unsuccessfull light off on gas fuel. start attempts
SIZE CAGE CODE DWG NO
g
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
5 of 13
SIZE
B
DWG. NO.
401B3661
SH.
6
REV.
-
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip when a gas speed ratio valve fault occurs: the error between position command and psoition feedback exceeds K3GRVTX %. Trips (1) When GCV feedback is less than K3GCVFB after time delay of K3GFTD (2) When GCV is failed to open in comparison (greater)with LK3GCVxO when valve is not enabled after time delay of K3GVFTD (3) or if the servo current is lesser than K3GCVSC after time delay of K3GVFTD Trip when difference between GCV position and reference is greater than LK3GCVx for for 10 seconds. Trip when P2 pressure exceeds KFPG2IH for K86FPG2IH seconds before firing permissive is reached. Trip when P2 Pressure exceeds FPG2WUH (post ignition high pressure trip set point) for K86FPG2HT seconds between firing permissive and warmup complete.
SIZE CAGE CODE
ACTION SETPOINT (Nominal Setpoints)
Gas Speed/Ratio Valve Error
L3GRVT
PROTECTIVE STATUS
Inability to control fuel
96SR-1, 2
See Control Spec: K3GRVTX = 5%
Gas Control Valve Servos Check
L3ACS
PRE IGNITION TRIP L4PRET
Inability to control fuel
96GC-x, 77FD
See Control Spec: LK3GCVxFB = -5% LK3GCVxO = 5% LK3GCVxSC = 37.5% K3GVFTD=3 sec (where x = GCV number: 1, 2, 3, Q)
Gas Control Valve Not Following Reference Trip
L86GCVxT
PROTECTIVE STATUS TRIP 3
Inability to control fuel
96GC-n
TO See Control Spec: k836gv = % LK3GCV = 10 sec
Gas Fuel Intervalve P2 Pressure High Before Ignition
L86FPG2IH
PRE IGNITION TRIP L4PRET
Potential high temperature ignition.
96FG-2A, 2B, 2C
See Control Spec: KFPG2IH = 6 psig K86FPG2IH = 5 sec
Gas Fuel Intervalve P2 Pressure High During Ignition and Warm Up
L86FPG2H T
PROTECTIVE STATUS TRIP 2
Potentially High Temperature Ignition
96FG-1, 2A, 2B
See Control Spec: K86FPG2HT = 5 sec
g
DWG NO
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
6 of 13
SIZE
B
DWG. NO.
401B3661
SH.
7
REV.
-
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip when P2 pressure falls below FPG2WUL (post ignition P2 low pressure trip setpoint) for K86FPG2LT seconds between firing permissive and warmup completeon fuel gas operation Trip when the leakage across the SRV is excessive and the P2 cavity pressure rises above K86GLTA psig in K86GLT1 seconds, or if the P2 pressure drops below K86GLTB psig in K86GLT3 sec during a bottle test both during startup and shutdown. Trip when any of the following conditions match: (1) when Aux gas purge trip OR (2) When Pilot premix mode or premix mode and K20PG3ONY sec. to G3 purge command off and purge G3 command close category 4 fault OR (3) Purge G1 Command Close Category Fault and TD G1 Purge command off in Prmix mode (4) TD G2 purge cmd off and purge command category fault
SIZE CAGE CODE
ACTION SETPOINT (Nominal Setpoints)
Gas Fuel Intervalve P2 Pressure Low PROTECTIVE L86FPG2LT During Ignition and STATUS TRIP 2 Warm Up
Potentially High Temperature Ignition
96FG-2A, 2B, 2C
See Control Spec: K86FPG2LT = 15 sec
Excessive P2 Cavity Leak
L94GLTSU L94GLTSD
PRE IGNITION
Prevent excessive fuel during ignition causing fuel to ignite
96FG-2A, 2B, 2C
See Control Spec: K86GLTA = 100 psig K86GLT1 = 30 sec K86GLTB = 150 psig K86GLT3 = 30 sec
Gas Purge for DLN 2+
L4GPFT
TRIP
Non Functioning Gas Fuel Purge System
33PG-xx,63PGxx,20PG-x
K20PG3ONY = 8 Sec.
g
DWG NO
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
7 of 13
SIZE
B
DWG. NO.
401B3661
SH.
8
REV.
-
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip when either of following condition match (1) Purge G3 command open no faults and K20PG30NZ1 sec. TD G3 Purge commandm On Flame not Detected Minimum speed signal come (2)Purge G2 command open no faults and K20PG20NZ1 sec. TD G2 Purge commandm On Flame not Detected Minimum speed signal come (3) Purge G1 command open no faults and K20PG10NZ1 sec. TD G1 Purge commandm On Flame not Detected Minimum speed signal come
ACTION SETPOINT (Nominal Setpoints)
Gas Purge Fault Preignition
L4GPF_PI
PRE IGNITION TRIP
Non Functioning Gas Fuel Purge System
33PG-xx,63PGxx,20PG-x
K20PG30NZ1 = 50 sec.K20PG20NZ1 = 50 sec.K20PG10NZ1 = 50 sec.
SPEED PROTECTION Turbine Primary Electrical Overspeed Trip L12H PROTECTIVE STATUS Overstress of rotating components 77NH-1, 2, 3 Trip when median selected speed is above Primary OS trip level
SIZE CAGE CODE
See Control Spec: TNKHOSTrip Level = 110%
DWG NO
g
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
8 of 13
SIZE
B
DWG. NO.
401B3661
SH.
9
REV.
-
PROTECTIVE FUNCTION Turbine Emergency Electrical Overspeed Trip
SIGNAL NAME L12H_P
TYPE PROTECTIVE STATUS
DESIGN JUSTIFICATION Overstress of rotating components
DETECTION METHOD 77HT-1, 2, 3
LOGIC DESCRIPTION
ACTION SETPOINT (Nominal Setpoints)
Loss of Primary Control Speed L12HF Signal Loss of Emergency Control Speed L12H_FLT Signal
PROTECTIVE Loss of speed control and STATUS TRIP 3 Primary OS protection PROTECTIVE Loss of speed control and STATUS TRIP 2 Emergency OS protection
77NH-1, 2, 3
77HT-1, 2, 3
Speed Signal Deviation Fault
L12HFD_C L12HFD_P
PROTECTIVE STATUS
Potential loss of speed control and protection
77NH-1, 2, 3 77HT-1, 2, 3
Loss of Emergency L12H_ACC Speed Signals TURBINE CONTROL PANEL Control System Fault Trip L3SFLT
PROTECTIVE STATUS
Potential loss of overspeed protection
77HT-1, 2, 3
Trip when median See Control Spec: selected speed is Emergency Trip Level = above Emergency OS 110% trip level Trip when primary See Control Spec: speed signal is low Speed signal < 5% while in operation Trip when emergency See Control Spec and speed signal is low GEH 6421 Chapter 7: while in operation Speed signal < 2.16RPM Trip when difference between Emergency See Control Spec: speed signal and Trip Level = 5% of rated Primary speed signal is speed greater than the trip level. Trip when 2oo3 Emergency speed NA signals indicate sudden deceleration.
PROTECTIVE STATUS TRIP
Controller Fault <P> Core Trip
Loss of TMR Voting Various
Protective Module L5CMPST_ <P> Trip TRP
Trip when 2 of 3 controllers are not voting. Trip when 2 of 3 <P:> controllers are Trip
SIZE CAGE CODE DWG NO
NA NA
0476
DISTR TO
g
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
DRAWN ISSUED
9 of 13
SIZE
B
DWG. NO.
401B3661
SH.
10
REV.
-
PROTECTIVE FUNCTION CUSTOMER Customer Trip
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION
ACTION SETPOINT (Nominal Setpoints) Trip when Customer Trip hardwired digital input drops out. NA
L4CT
PROTECTIVE STATUS PROTECTIVE STATUS
Customer Crosstrip
Customer Crosstrip Contact inputs from Customer and Local Panel
Contact inputs from Customer controller Trip when Remote or Local E-Stop pushbutton is depressed.
Emergency Pushbutton Trip STEP TO MIN LOAD
L5E, R5E
Emergency Trip
Compressor Bleed L83CB_L_S Valves TEP
PROTECTIVE STATUS
Initiate a Step to Spinning Reserve to avoid machine damage
33CB-1, 2, 3, 4
2oo3 Compressor Bleed Valve Open Limit Switches indicate open when commanded closed AND IGVs have 2oo3 open limit switches op ened past the for each of 4 Bleed Valves minimum operating positionL33CSGV_CB. IGV is opened during operation
STEP TO FSNL Remote Breaker Open Detect L83RBO PROTECTIVE STATUS Initiate a Step to Full Speed No Load to avoid machine damage due to overspeed Initiate a Step to Full Speed No Load to avoid machine damage due to overspeed TNH, TNHA 77NH Overspeed and Acceleration Detected Load Rejection due to Generator Breaker opening
SIZE CAGE CODE DWG NO
101.5 % speed, 3 %/sec acceleration
External52G Trip
L52GX
PROTECTIVE STATUS
52GX
NA
g
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
10 of 13
SIZE
B
DWG. NO.
401B3661
SH.
11
REV.
-
PROTECTIVE FUNCTION DCS Breaker Open Command
SIGNAL NAME lca4_fsnl
TYPE PROTECTIVE STATUS
DESIGN JUSTIFICATION STEP TO FSNL
DETECTION METHOD HRSG temperatures
LOGIC DESCRIPTION Load Rejection due to DCS detecting highhigh HRSG temperatures Open Breaker when Maximum of dwatt1 and dwatt2 is less then LK32DWRP When DWATT is lesser than DWTLLIM and Gen Watt transducer is sensing fault after time delay of V32DWTDC Gen Bkr opens on reverse power Open Breaker when operator Issue Manual breaker open Trips before ignition if DC emergencey lube oil pump is determined to be in under voltage condition Trips before ignition if DC emergencey seal oil pump is determined to be in under voltage condition Trip Signal is generated by logic L45LEL_PRET. This protection generates TRIP command in either og the following operating condition (1) If Turbine compartment Haz Gas Level Hi (2) If Gas Compt Has gas Level Hi (3) If Turbine compt Local Haz Gas Level Hi (4) If either of this Haz Gas monotor Rack #1, Rack # 2, Rack#3 (5) If Haz Gas syatem analog signal trbl
SIZE CAGE CODE
ACTION SETPOINT (Nominal Se tpoints) Customer
Reverse Power Detected
L32DW
STEP TO FSNL
Open Breaker to Avoid Generator Motoring
Maximum of MW sensors
Generator Power < LK32DWRP (-4.8MW)
Manual Breaker open Emegency Lube Oil Pump Undervoltage Relay SEAL OIL Emegency Seal Oil Pump Undervoltage Relay
L52GT_TRI P
STEP TO FSNL
Operator initiated manual breaker trip
Operator Action
Operator Initiated
L27QEL
PRE IGNITION TRIP L4PRET
Loss of Bearing Lubrication
27QE-1
NA
L27ESL
PRE IGNITION TRIP L4PRET
Loss of Seal Lubrication
27ES-1
NA
Haz gas Level High High start inhibit
l45LEL_PR ET
PROTECTIVE STATUS
To prevent dangerous atm
45HA,HT,HG
NA
g
DWG NO
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
11 of 13
SIZE
B
DWG. NO.
401B3661
SH.
12
REV.
-
PROTECTIVE FUNCTION Fire ignition trip
SIGNAL NAME L45FTX
TYPE PROTECTIVE STATUS TRIP 1
DESIGN JUSTIFICATION Emergency due to fire
DETECTION METHOD 94F1-B
LOGIC DESCRIPTION Trip signal generates If either fire found in Turbine/Acc compt or other any of 4 zones Gen trip lock out [l86g1a],Breaker failure lock out [l86bft], Gen& GSU Transformer lock out trip[l86v] ,GSU Transformer lock out trip [l86t] Unit trip Via 86G1B[l86g_1b], Trip command will triggered if Emergency push button pressed Turbine trips after time delay of BY K4BTFLT When low ventillation pressure still both oh of the ventillation fans running Trips when level gets high when compared with predetermined level Trips when level gets high when compared with predetermined level
ACTION SET POINT (Nomina l Set points)
Generator protective trip
L86GT
PROTECTIVE STATUS TRIP 1
To avoid generator damage
Electrical inputs L86 signals
Emergecny stop
L5ESTOP1 _FBZ
PROTECTIVE STATUS TRIP 1
To trip the machine giving manual command
[5E-1/PB] [R5E/PB]
Turbine compartment loss of ventillation trip
L4BTFLT
PROTECTIVE STATUS TRIP 2
Over heating of turbine compartment
63AT-1.2.3,4
See control specification K4BTFLT = 60sEC
Scrubber dp/Level very high trip
L4PSTX 4_A
PROTECTIVE STATUS TRIP 4
To prevent uncleaned/moistured fuel entering into the machine To prevent uncleaned/moistured fuel entering into the machine
71GS-1 ,2A,2B
Coalescing filter level high trip
L4PSTX 4_B
PROTECTIVE STATUS TRIP 4
71GCF1A,1B,2A,2B,3A,3B
Load compartment loss of ventillation trip
L63AG_TR P
PROTECTIVE STATUS TRIP 4
Prevent overheating in Load gear compartment
63AG-1,2
Trip signal will generate 1)If load compt vent pressure comes low sensed by both Control spec Pressure pr.switches after a switch setting time delay of 30 sec GEAR/LOAD COMPT AIR K63AG_TRP2 still two PRESSURE SWITCH fans are running DECREASING: 0.4 2)Load compt vent fan INH2O OR 10.1600 control signal is mmH2O enabled , still pressure NORM=NO-CEC; from sensed by 63AG 1,2 is GR1072 low after time delay of 7 min K63AG_TRP2 trip signal will be generated
SIZE CAGE CODE DWG NO
g
GENERAL ELECTRIC COMPANY
08-11-12 08-11-12
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
12 of 13
SIZE
B
DWG. NO.
401B3661
SH.
13
REV.
-
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trips when (1)IF After the firing timer delay of L2F ,no flame is detected in total liquid fuel mode (2) Any protective trip command triggers when Startup firing fuel command is enabled or under operation (3) If total mass flow of liquid fule is gr Trips When fuel feedback exceeds limit while L20FLXX _X timer is denergized ,when there is no recirculation and total liquid fuel