THE SOLUTION PROVIDERS
Design and manufacture manufacture of
STORAGE TANKS FOR ALL PURPOSES
Contents Aboveground Enclosed Bunded Storage Tanks Tanks Envirotank Rectangular T64 Range - Envirotank Cylindrical T34 Range - Envirotank Rectangular With Removable Pitched Roof Bio Envirotank Belowground Double Skin Storage Tanks Tanks Envirotank Cylindrical
Underground Vertical Ve rtical LubeOil Rectangular Bio Fuel Storage Enviro Horizontal Aboveground Abovegr ound Specialist Open Top Chemical
tanks tanks tanks tanks tanks tanks tanks tanks tanks tanks tanks
4 5 6 7 8-9
10-11
Other Enclosed Bunded Storage Tanks Tanks Gravity Feed Envirotank Rectangular Autolube Envirotank Envirotank Rectangular
12 13
Open Bunded Storage Tanks Cylindrical Rectangular
14 15
Vertical Storage Tanks Tanks Open Bunded Cylindrical Tanks Cylindrical Single Skinned Tanks (Type D on legs/skirt) Cylindrical Single Skinned Tanks (Type G flat bottom) V2 Range - Cylindrical Enclosed Bunded Storage
16 17 18 19
Horizontal Tanks Cylindrical Single Skin Storage Tanks Rectangular Single Skin Storage Tanks
20 21
Other Tanks Specialist Tanks Galvanised Open Top Galvanised Bolted Top
22 23 24
Accessories Ladders (Galvanised) Holding Down Straps Typical Connections Support Cradles Mild Steel Fuel Tank Components Pumps & Controls
25 25 25 26 27 28
Other Information Volumes, Volum es, Surface Areas & Conversion Tables Tables C.A.D & Manufacturing Suitable Storage Products
29 30 31
Complete Liquid Storage Solutions
Joseph Ash was born in 1824, the son of a Birmingham Chemist. He founded his company in 1857 which took an active part in the expansion of the Midlands. In 1864 he joined John Pierce Lacy to form Ash & Lacy. At the start of the new millennium Ash & Lacy were taken over by Hill & Smith Holdings Plc, now the Parent Company. JA Envirotanks is a trading name within Joseph Ash Ltd specialising in the mass production of aboveground enclosed bunded steel tanks and buried double skinned steel tanks. The company has occupied its current site for over 150 years, always specialising in tank production with high capacity cranes and specialist welding equipment technology.
More bespoke tanks and fabrications are produced on site from carbon steels and stainless steels which include conical hoppers, chemical and process tanks with specialised linings and ladders, platforms, stairways and frames. All steelwork is galvanised by the sister company Joseph Ash Galvanising. Joseph Ash is also one of the l argest galvanising operations in Europe which includes many galvanising plants within the UK. The patented “ENVIROTANK” product range is manufactured in Birmingham which includes enclosed bunded rectangular and cylindrical tanks which comply with The Control of Pollution Regulations and are licensed to OFTEC standard OFS T200. JA Envirotanks products are suitable for all fuels including specially engineered tanks for the storage of the latest formulated bio fuels with heaters and specialist coatings. JA Envirotanks produce tanks with a designed life of 20 years to meet the needs of aggressive commercial and industrial environments. Located at the hub of the UK motorway network JA Envirotanks can despatch, deliver and offload at any mainland location or port.
s k n a T e g a r o t S d e d n u B d e s o l c n E d n u o r g e v o b A
Aboveground Enclosed Bunded Storage Tanks The ENVIROTANK is a primary storage tank, externally encased within an outer weatherproof bund to ensure any leakage or nominal overfill situation is safely contained. The ENVIROTANK is easily transportable as a one-piece unit and reduces costly and time consuming site work. The ENVIROTANK is delivered by JA Envirotanks transport to the customers premises. If at a later date a new site for the ENVIROTANK is required it only has to be emptied of contents, cleaned internally, uplifted and transported to its new location. Outer bund designed to contain 110% of the inner tank volume. Inner tank manufactured to BS799 Part 5 from Steel plate to BS EN 10 025:2004:S275. Compliance with the control of pollution regulations. Inner tank and outer bund pressure tested.
Envirotank Rectangular Ref
Capacity Litres
(Excl cabinet) mm
Length
Width mm
Height mm
Weight
E61A
2273
1753
1190
1220
1118
E62A
2727
2104
1190
1220
1270
E63
2841
2192
1190
1220
1296
E64
2954
2274
1190
1220
1348
E65
3409
2631
1190
1220
1500
(Approx) Kg
E66
3636
2806
1190
1220
1576
E67A
4546
3080
1470
1220
1800
E70
5682
3845
1470
1220
2102
E71A
6819
3745
1470
1500
2408
E72
7955
2704
1800
1830
2510
E74A
9091
3035
2408
1500
2816
E75A
11364
3790
2408
1500
3278
E76A
13637
4540
2408
1500
3854
E78
18183
3696
3008
1830
4486
E79
22729
4610
3008
1830
5506
E80
27275
5532
3008
1830
6102
E81
31821
6454
3008
1830
6694
E82
36367
7376
3008
1830
7550
E83
40913
8298
3008
1830
8282
E84
45459
9220
3008
1830
9524
E85
54550
11064
3008
1830
10150
E60
80000
10261
3008
3048
14000
E99
90000
11545
3008
3048
15479
E86
100000
12830
3008
3048
16918
E99
110000
11780
3008
3650
17905
E87
120000
12870
3008
3650
19295
E88
140000
12500
3618
3650
22445
E89
180000
14850
3960
3600
27000
Advantages The ENVIROTANK SAFE is an inner storage tank, externally encased within an outer weatherproof bund to ensure any leakage or nominal overfill situation is safely contained. The top connections, pipework and manway are enclosed by a secondary roof section for total security. The ENVIROTANK SAFE is easily transportable as a one-piece unit and reduces costly and time consuming site work. The ENVIROTANK SAFE is delivered by JA Envirotanks transport to the customers premises. If at a later date a new site for the ENVIROTANK SAFE is required it has only to be emptied of contents, cleaned internally, uplifted and transported to its new location. Outer bund designed to contain 110% of the inner tank volume, manufactured to BS799 Part 5 from Steel plate to BS EN 10 025:2004:S275. Compliance with the control of pollution regulations. Inner tank and outer bund pressure tested.
• • • • • • • • • • •
Enclosed bunded tank Space saving (smaller footprint) Reduced maintenance costs Weatherproof (Tank & Bund Enclosed) Cuts costly site work Needs only suitable level hard standing Overfilled product can be re-used Easily transportable Sizes/capacity to suit most situations Finished in green or black oil resistant paint Clients own in-house colours can be accommodated on request • Offloading and positioning facilities available if required • The optional security cabinet will extend the overall length of the unit by 750mm.
Additional Fittings Padlockable access hatch
• 50, 65 or 80mm fill pipe c/w valves, tanker coupling and cap • Venting assembly sized to suit • Sludge drain pipe • 40mm outlet pipe with valve
450mm
• Electric bund monitoring with alarm • Contents guage in litres • Overfill alarm and/or overfill prevention valve • Dipstick, dip pipe, cap and chain
1,830mm
• Dispensing pumps with safety break couplings and automatic nozzle (3m hose supplied) • Fuel monitoring systems • Optional galvanised ladder and platform • Optional distribution board and lighting • Optional security cabinet with aluminium roller shutter door and steel doors.
Padlockable steel doors
Envirotank Safe Ref
Benefits Enclosed Bunded Storage Tank with Secondary Removable Pitched Roof for Total security
Capacity Litres
Length mm
Width mm
Height mm
Weight
S30
2000
1180
1100
1830
1136
S31
3000
1660
1180
1830
1344
S32
5000
2170
1485
1830
1954
S33
7000
2520
1790
1830
2448
S34
10000
3590
1790
1830
3171
S35
15000
4020
2398
1830
4195
S36
20000
5360
2398
1830
5267
S37
25000
6700
2398
1830
6326
S38
30000
6410
3008
1830
7102
S39
40000
8550
3008
1830
9075
S40
50000
10690
3008
1830
10876
S41
60000
10660
3618
1830
11825
S42
70000
12440
3618
1830
14201
S43
80000
14220
3618
1830
16023
(Approx) Kg
UK Patent No: 2 251 021
s k n a T e g a r o t S d e d n u B d e s o l c n E d n u o r g e v o b A
k n a t o r i v n E o i B d n u o r g e v o b A
Bio-Envirotank Rectangular Aboveground Enclosed Bunded Storage Tanks (Inner tank externally stiffened and with a sloping hopper style bottom) A unique design (“Pat App 2 477 266”) comprising a primary storage tank without internal structure to enable ease of internal inspection and cleaning. The base of the tank has a sloping hopper style bottom to a sump, the sump being serviced by a 25mm sludge drain pipe accessible from the tank top.
Design for the Future With developing Bio-fuels water content and bacterial growth is becoming more of an issue in tanks; regular tank cleaning and inspections are now necessary. Entering tanks presents health and safety concerns and by constructing a tank with free internal space (no cross stays) makes entry and egress easier and safer. Access and retrieval of remotely controlled cleaning technologies (non man entry systems) is also more practical with Bio-Envirotanks. The incorporation of sloping bases and sumps helps reduce the frequency of cleaning as water and contaminants will easily drain into the sump. Residues are extracted via the sludge drain pipe which runs from the tank top to the sump.
The concept with correctly positioned manway inspection points allows tank cleaning without man entry reducing the need for confined space entry health and safety procedures. The primary tank is enclosed by an outer steel bund that fully complies with the control of pollution regulations, the bund holding the inner tank capacity plus 10% (110% containment). The tank can be split into compartments for gas oil/diesel/oils/Adblu and process liquids. Internal tank linings can easily be applied due to the unrestrictive internal tank construction. External manways and connections are enclosed within a steel secure hatch which is padlockable to prevent tampering. End or side mounted security cabinets can be fitted including steel or roller shutter doors and integral spillage trays, to house pipework, pumps, gauging, alarms and controls. Designed life 20 years. Inner tank and outer bund pressure tested.
Bio-Envirotank Ref
Capacity Litres
Length mm
Width mm
Height mm
Weight
(Approx) Kg
BE1
2500
1410
1460
2000
1372
BE2
5000
2610
1460
2000
2202
BE3
7500
3760
1460
2000
2937
BE4
10000
3310
2010
2000
3306
BE5
15000
5080
2010
2000
4680
BE6
20000
5560
2410
2000
5557
BE7
30000
6740
2410
2400
7372
BE8
40000
7164
3030
2400
9025
BE9
50000
8864
3030
2400
10839
BE10
70000
9626
3008
3048
15702
BE11
90000
12276
3008
3048
19438
BE12
120000
15476
3160
3048
24249
BE13
140000
16076
3160
3400
26484
BE14
180000
17905
3600
3400
30700
Features Heating Low pressure hot water and steam coils can be built into the tank bottom if needed or electrically powered submersion heaters. All heating can be provided with temperature sensors and control thermostats. Lagging and cladding can be added to the outside of the unit for heating efficiency.
Gauging • • • •
Hydrostatic gauges in litres Electronic gauges in litres Differential and level measurement systems for closed vent tanks Water monitor indicators are available with electronic gauges
• • • • • • • • • • • •
Electrical Lighting, wiring and distribution boards with isolators to suit equipment fitted.
Heating Options • • • •
• • • •
Low pressure hot water coils Steam coils Immersion/submersion heaters Lagging and cladding to minimise heat losses
•
Enclosed bunded tank design Reduced maintenance costs Needs only suitable level hardstanding for siting Easily transportable Lifting eyes for offloading Overfilled product can be reused Fill pipe sizes 50mm/65mm/80mm complete with isolation valve Tanker coupling and cap and chain Venting systems to suit fill size 25mm desludge pipe to sump 50mm outlet pipe for gravity feed or top suction 50mm and 80mm overfill prevention valves available to shut off the tanker fill when the primary tank reaches capacity Electronic low level and overfill alarm units Electronic bund warning alarm units Transfer pump sets available to feed boilers and generators Dispensing pumps available with automatic nozzles Fuel monitoring systems fitted to suit customer needs.
Cabinets • Side cabinets and end cabinets • Roller shutter doors or steel hinged doors
Access • • • •
Vertical caged ladders and walkways Ships ladder and walkways Stairway to walkway All galvanised finish with open mesh or chequer plate flooring
Lockable security hatch over manway and critical connections
Ladder & walkway (optional)
Overflow prevention device
Internal desludge pipe to sump
Cabinet with aluminium roller shutter door (optional)
Outer Bund
Specialist Features
(optional)
Gauge
Fill Pipe Inner tank with hopper base to sump
Alarm Panel 450mm diameter sump Internal suction pipe Universal beam bearers
Pumping options
• 50mm/65mm/80mm vent dryers to minimise moisture and condensation • Internal linings to keep fuel sterile and prevent corrosion • Stainless steel pipework and fittings. • Specialist filters including magnetic filter technology in order to reduce bacteria in the tank bottom. Optional Bolt on Pitched Roof to secure all Top Pipework & Tank Entries
k n a t o r i v n E o i B d n u o r g e v o b A
s k n a T e g a r o t S d e d n u B l a c i r d n i l y C l a c i t r e V
Vertical Bunded Cylindrical Tanks • One coat of zinc phosphate primer, one coat of green oil resistant paint • Inner tank manufactured generally to BS 799 Part 5 Type G • Side manway available on inner tank only • Screwed or Flanged connections available • Pipe work fitted to suit application • Compliance with CoP regulations • Outer bund to contain the capacity of the inner tank plus 10% • Access ladders, platforms, steelwork & periphery hand railing available
Non return valve fitted
• Inner tank pressure tested • Bund tested sound.
Lift lugs
Ref
Inner Tank (DiaxH)mm
No of Tanks
Capacity Litres
B61
1500 x 1545
1
2270
1981 x 1981 x 686
B62
1500 x 2895
1
4545
1981 x 1981 x 1390
B64
1900 x 3590
1
9120
2438 x 2438 x 1775
B65
2486 x 2905
1
11364
2935 x 2935 x 1524
B66
2486 x 3400
1
13638
2935 x 2935 x 1828
B67
2743 x 3352
1
18183
3200 x 3200 x 1981
B68
3000 x 3505
1
22730
3657 x 3505 x 1981
Bund Size (LxWxH)mm
All the above tanks are transported as one piece units (B61-B68)
Additional Fittings • 50mm/65mm/80mm diameter fill pipe with valve and brass cap • Vent complete with bird guard • 25mm diameter sludge complete with valve and plug • 40mm diameter draw off complete with valve • Hydrostatic contents gauge complete with capillary tube and bracketed to the
B69
2743 x 5029
1
27275
4114 x 3656 x 1981
B70
2743 x 6477
1
36368
3810 x 3656 x 2896
B71
2743 x 8051
1
45450
4724 x 3656 x 2896
B72
2743 x 9753
1
54551
5638 x 3656 x 2896
B73
3000 x 10261
1
68189
5638 x 3656 x 3656
B74
2743 x 6477
2
72735
7010 x 3656 x 1981
B75
2743 x 8051
2
90919
8382 x 3656 x 1981
B76
2743 x 9753
2
109103
9753 x 3656 x 1981
B77
3000 x 10261
2
136379
12115 x 3656 x 1981
B78
3000 x 11227
2
150000
12115 x 3656 x 2200
All the above tanks are transported as seperate units to be bolted together at site (B69-B77)
Tank and Bund from 6mm thick mild steel plate
Vertical Single Skin Cylindrical Storage Tanks
s k n a T e g a r o t S n i k S e l g n i S l a c i r d n i l y C l a c i t r e V
• Manufactured in accordance with BS 799: Part 5: Type D • All welded seams • Certified tested • Fitted with 600mm dia. Manhole with set pinned cover and gasket • Standard connections include two 65mm, one 40mm and one 25mm screwed sockets (flanged connections optional) • Finished one coat of primer/gloss finish, or to customer’s requirements • Steel plate to BS EN 10 025: 2004: S275 • Access ladders, platforms, steelwork & periphery hand railing available.
Type D Ref
Mounted on Steel Skirt
Mounted on Legs
Capacity Litres
Height metres
Internal Dia metres
Shell Thk mm
Weight
V01
2273
1.528
1.494
6
460
V02
2841
1.867
1.494
6
530
V03
3409
2.207
1.494
6
630
V04
4546
2.889
1.494
6
790
V05
5682
3.569
1.494
6
960
V08
9092
3.547
1.900
6
1230
V10
11365
4.389
1.900
6
1480
V13
13638
5.230
1.900
6
1750
V15
18184
4.320
2.486
6
1970
V17
22730
5.303
2.486
6
2370
V20
27275
6.286
2.486
6
2780
V21
31821
7.270
2.486
6
2860
V22
36367
8.253
2.486
6
3350
V23
40913
6.600
2.986
6
3690
V24
45459
7.281
2.986
6
3950
V25
54551
8.390
2.986
6
4720
V26
68189
10.262
2.986
6
5430
V27
90918
13.654
2.986
6
6850
V28
100010
14.935
2.986
6
7044
V29
113647
16.926
2.986
6
7924
V30
136377
11.735
4.000
8
11500
(Approx) Kg
s k n a T e g a r o t S d e m o t t o B t a l F l a c i r d n i l y C l a c i t r e V
Vertical Single Skin Flat Bottomed Cylindrical Storage Tanks • Manufactured in accordance with BS 799: Part 5: Type G or BS EN 14015
Dished Top BS 799 Pt5 Type G
• All welded seams • Certified tested
Lifting lugs
• Fitted with 600mm dia. Manhole with set pinned cover and gasket • Standard connections include two 65mm, one 40mm and one 25mm screwed sockets • Finished one coat of primer/gloss finish, or to customer’s requirements • Steel plate to BS EN 10 025: 2004: S275.
High load DPC membrane recommended between tank base & concrete foundation
Conical Top BS EN 14015
Flat Bottom
Type G Ref
Capacity Litres
Height metres
Internal Dia metres
Shell Thk mm
Base Thk mm
Weight
V01
2273
1.528
1.494
6
6
460
V02
2841
1.867
1.494
6
6
530
V03
3409
2.207
1.494
6
6
630
V04
4546
2.889
1.494
6
6
790
V05
5682
3.569
1.494
6
6
960
V08
9092
3.547
1.900
6
6
1230
V10
11365
4.389
1.900
6
6
1480
V13
13638
5.230
1.900
6
6
1750
V15
18184
4.320
2.486
6
8
1970
V17
22730
5.303
2.486
6
8
2370
V20
27275
6.286
2.486
6
8
2780
V21
31821
7.270
2.486
6
8
2860
V22
36367
8.253
2.486
6
8
3350
V23
40913
6.600
2.986
6
10
3690
V24
45459
7.281
2.986
6
10
3950
V25
54551
8.390
2.986
6
10
4720
V26
68189
10.262
2.986
6
10
5430
V27
90918
13.654
2.986
6
10
6850
(Approx) Kg
C.A.D and Manufacturing • J A Envirotanks have several CAD workstations & all drawings are produced in electronic format (PDF, DWG & DXF). • All our storage tanks designs are carried out using Autocad software.
g n i r u t c a f u n a M & D . A . C
• 3D solid modelling utilises our Autocad Inventor workstation. • JA technicians are able to create bespoke tank designs to suit specific applications.
Certain liquids may also be stored adequately in unlined carbon steel tanks – please consult our Sales Office.
Liquids
for storage in carbon steel internally coated Tanks A Aliphatic Hydrocarbons Alkanes Ammonia Aqueous Solution 5% Ammonia Aqueous Solution 10% Ammonia Aqueous Solution 20% Ammonia Aqueous Solution 40% Ammonium Carbonate Aqueous Sol. 5% Ammonium Carbonate Aqueous Sol. 10% Ammonium Carbonate Aqueous Sol. 25% Ammonium Nitrate (all strengths) N-Amyl Acetate Animal Oils and Fats Aromasol H Aromatic Hydrocarbons (not Benzene) Aromatic Solvents (Petroleum) Aviation Fuel B Benzine Bio Fuels Butanol-iso Butanol-normal Butyl Methacrylate C Calcium Chloride 10% Calcium Chloride 25% Calcium Chloride Saturated Calcium Hydroxide Carbon Tetachloride Cashew Nut Oil (20oC) Castor oil (up to 20oC) Caustic Soda sol. 5%, 10%, 25%, 50% China Wood Oil (up to 40oC) Citric Acid 10% Cod Liver Oil (up to 20oC) Cotton Seed Oil (up to 20oC) Crude Oil (high and low sulphur) Cumeme Cyclohexane Cyclohexanol P-Cymene D Decanol Diacetone Alcohol Dibutyl Phthalate Dicyclopentadiene Diesel Oil Diethanolamine Diethylene Glycol Di-2-(ethyl Hexyl) Phthalate Di-Isobutylene Di-iso Butyl Ketone Di-iso-octyl Phthalate Di-n-butyl Phthalate Dipentene Dodencane Dutrex E Engine Oils Ess Aviation o12 12o Esso (base) Light A Special Esso Medium Base Esso Base Light A Ethyl Benzene Ethylene Glycol 2-Ethyl Hexanol F Fats Animal Ferric Chloride (all strengths) Fuel Oil G Gamlen Tank Cleaning Oils
Gasoline Premium (Europe) Gasoline Regular (Europe) Gasoline Premium (Canada) Gasoline Regular (Canada) Gas Oil (2) (Europe) Glycerine Glycerol Grain Groundnut Oil A.V.10 H Heating Oil No.2 (Canada) Heavy Aromatic Naphtha Heptane-normal Hexane-normal Hexylene Glycol High Aromatic White Spirit Hydraulic Oil Hydrocarbon Aliphatic I Isobutanol Iso Dodecane Iso Octanol Iso Octyl Alcohol Isopentane Isoprene J Jet Fuel JP4 Jet Fuel A-1 K Kaydol Heavy Duty White Kerosene Kontol A.162 L Lanoline Lard Linseed Oil Lube Oil Lube Oil Additive Lubricating Oil M Magnesium Chloride Magnesium Chloride Magnesium Chloride Magnesium Chloride Mineral Oils Mineral Spirit
5% 10% 25% Saturated
N Naphtha Naphtha Coal Tar Naphtha Heavy Naphtha Petroleum Naphthenic Acid Nonanol Nonylphenol Nonyl Heptane Nonyl Hexane Nonyl Butanol Nonyl Butyl Alcohol Nonyl Pentane Nuoplaz O Octane-iso Octanol-iso Octyl Phenol Ethylene Oxide Oils Animal Oils Mineral Oils Vegetable Oiticia Oil (up to 20oC) A.V.5 Oleum Olive Oil A.V.10
P Palm Oil (up to 40oC) A.V.10 Palm Kernel Oil A.V.5 Paraffin Paraffin Wax Para Xylene Peanut Oil A.V.10 Pentane-n Pentane-iso Perilla Oil (up to 20oC) A.V.10 Petrol Petroleum Solvents Aliphatic Petroluem Solvents Aromatic Phthalate Plasticisers Pine Oil Polypropylene Glycol Poppy Seed Oil (up to 20oC) A.V.10 Potassium Hydroxide (up to 50%) Propylene Glycol S Sea Water Shell Oil 1984 Shellsol A Shellsol E Shellsol T Shellsol AB Shellsol N Shellsol R Soap Solution Sodium Carbonate (all strengths) Sodium Chloride Solution (all strengths) Sodium Dichromate Solution (up to 25%) Sodium Hydroxide (up to 50%) Sodium Hypochlorite (up to 25%) Sodium Nitrate Solutions (all strengths) Solvent Naphtha Solvesso 100 Solvesso 150 Soya Bean Oil A.V.10 Sperm Oil Sunflower Seed Oil (up to 20oC) A.V.5 T Tallow (acid number not greater than 5) Teepol Tetrahydronaphthalene Titanium Tetrachloride Toluene Trichlorethane Triethylene Glycol Triton X100 Triphenyl Phosphate 2.2.4 Trimethyl Pentane Tung Oil Turpentine Turpentine Substitute W Water Ballast Water Sea Whale Oil (up to 20%) White Spirit White Spirit Aromatic White Spirit Low Aromatic White Spirit High Flash X Xylol Xylene Industrial (mixed isomers) Z Z.D.D.P (Zinc Dialykl Dithiophosphate)
s d i u q i L e g a r o t S l a c i p y T
Main Switchboarrd
0121 622 4661
Generall Sales
0121 666 4778 0121 666 4774 0121 666 4787
Drawing Office
0121 666 4779
Sales Office Hours Monday to Thursday
Friday
8:45am - 1:00pm 2:00pm - 5:00pm 8:45am - 1:00pm 1:30pm - 4:1 15pm
E
[email protected]
W
www.jaenvirotanks.com
PO Box x 16,, Charles s Henry Str treet,, Birmingham, B12 2 0SP