L6

Published on June 2016 | Categories: Documents | Downloads: 60 | Comments: 0 | Views: 298
of 9
Download PDF   Embed   Report

Comments

Content

How do blackouts start? Faults and protection
Joint of disconnector

Outline
• • • • • • • Faults in power systems Power system protection Zones of protection Time-delay overcurrent relay Coordination Directional relays Reclosers and sectionalizers
Electric Power Systems - Olof Samuelsson 2

Disconnector initiates Swedish blackout 23 september
Electric Power Systems - Olof Samuelsson 1

Open-circuit faults
• One phase of circuit breaker stuck open • Conductor falling down Short-circuit faults more common • • • • • • •

Short-circuit faults
Lightning Dirt/salt on insulators Flashover line-line (wind) Flashover to tree Tower/pole or conductor falls Objects fall on conductors Cable insulation failure
Electric Power Systems - Olof Samuelsson 4

Electric Power Systems - Olof Samuelsson

3

Lightning most common

Power lines and trees
400 kV 50 kV

Statistically 80 % of faults on overhead lines are due to lightning

10 kV

www.dmi.dk
Electric Power Systems - Olof Samuelsson 5

Distribution lines most affected

Electric Power Systems - Olof Samuelsson

6

Galopping spectacular

Effects of short-circuit current
• Arc
– Compare with welding – http://205.243.100.155/frames/longarc.htm

• Heating
– Fire and explosion

• Vibration due to magnetic forces
– Parallel conductors are attracted (F=B·i·l)

Electric Power Systems - Olof Samuelsson

7

Electric Power Systems - Olof Samuelsson

8

Heating
• Resistive losses RI2 • Temperature rise with stored heat energy I2t (no cooling assumed) • Same I2t gives equal heating (see graph)
Time Overload

Interrupting large currents
• Fuses
– Use the melting effect of the arc

• Circuit breakers interrupt kA in ms
– Extinguish arc

Short-circuit fault Current
Electric Power Systems - Olof Samuelsson 9

• Breaker operation – Automatic by relay protection
Electric Power Systems - Olof Samuelsson 10

Protection including fuses
Need
– Detect fault – Isolate faulted component – Restore faulted component

When lights go out…
1. An upstream fuse/relay has detected a fault 2. Downstream system isolated by fuse or breaker 3. Automatic reclosing after delay successful if fault not permanent
Electric Power Systems - Olof Samuelsson 12

Aims
– Continued supply for rest of system – Protect faulted part from damage

Electric Power Systems - Olof Samuelsson

11

Protection system performance
High reliability
– Always isolate targeted fault – High sensitivity good

Protection system tasks
Is there a fault?
– Short-circuit or only high load? – All situations must be known!

High selectivity
– Only react to targeted faults – High sensitivity bad
Compromise

Coordination
– Which protection unit should react? – Isolate as small area as possible – Must work also if component fails
Electric Power Systems - Olof Samuelsson 14

Fast
– Good for (transient) stability – Safety
Electric Power Systems - Olof Samuelsson 13

Zones of protection
• Defined for protected objects
– Dedicated protection for each zone

Protection types
• Overcurrent protection
– Lines (distribution)

• Zones overlap • CB in overlap zones • Isolated at fault anywhere inside
G M

• Directional overcurrent relay
– Lines (transmission), generators

• Differential protection
– Lines – Transformers – Busbars – Generators
Ex
Electric Power Systems - Olof Samuelsson 16

Electric Power Systems - Olof Samuelsson

15

Line protection components
CT CB

Time-delay overcurrent relay
Detect overcurrent – Wait delay time T – Trip CB Time

PT Relay

CB - Circuit Breaker CT - Current Transformer PT - Potential Transformer T 1

Trip

Constant delay characteristic

Large number of relays needed: One for each phase and fault type
Electric Power Systems - Olof Samuelsson 17

Relative overcurrent
18

Electric Power Systems - Olof Samuelsson

Time-delay overcurrent relay
Detect overcurrent – Wait delay time T(I) – Trip CB Time
R1 CB1

Radial system
•ISC increases when approaching source •R1 has higher current setting than R2 Time
Load1 CB2 R1 R2

Trip

Inverse 1/t characteristic Similar for fuses

R2

1

Relative overcurrent
19

Load2

Relative overcurrent
Electric Power Systems - Olof Samuelsson 20

Electric Power Systems - Olof Samuelsson

Fault in radial system
• R1 and R2 detect overcurrent • Delay of R2 smallest Time • R2 operates CB2 first
R1 R2 CB2 CB1 L1

Fault in radial system: At home
• Both F1 and F2 detect overcurrent • Delay of F2 Time • Fuse F2 blows first
F1 F2 F3

– Isolates fault + Load 2 – R1 reset

– Isolates fault and Me

• If fuse F2 fails
R1 R2

• If R2 or CB2 fails
– – – –

Load2

R1 not reset Current Extra delay of R1 R1 operates CB1 Isolates fault + Load 2 but also Load 1

– Extra delay of F1 – F1 blows – Isolates fault + Me but also Neighbor

F1 F2 Current

Me Neighbor •

Fault clearing is selective
– Coordination works
Electric Power Systems - Olof Samuelsson 22

Electric Power Systems - Olof Samuelsson

21

Coordination
Relays 1 and 2 coordinated in example: For the line, • Relay 2 provides Primary protection • Relay 1 provides Backup protection Always true since t(I) curves do not cross Rule: Longer delay close to source
Electric Power Systems - Olof Samuelsson 23

Line fed from both ends
R1 R2 R3 R4

G

G

– Rule not applicable due to many sources – Use directional relays:
• R1 and R3 only trip for fault to their right • R2 and R4 only trip for fault to their left

– V and I phase difference gives direction

Electric Power Systems - Olof Samuelsson

24

Impedance relay
Let relay measure V/I=Z=R+jX Normally load makes Z > Zline Fault on line makes Z < Zline - TRIP!
X Trip R Radius=|Zline |
Electric Power Systems - Olof Samuelsson 25

Impedance relay types
Directional X Trip R Zline Admittance or MHO X Trip R

Electric Power Systems - Olof Samuelsson

26

Distance protection
– Series impedance ~ distance along line – |Z|<0.8|Zline| equivalent to
• Zero Ω fault within 80% of line length • The reach of the relay is 80%

Distance protection zones
– Zone 1, Primary: 80%, no delay – Zone 2, Backup 1: 120%, delay – Zone 3, Backup 2: 120+100%, longer delay
A B C D

G
Time Zone 3 Zone 2 Zone 1

G

Distance
Electric Power Systems - Olof Samuelsson 27 Electric Power Systems - Olof Samuelsson 28

Distance protection coordination
A B C D

Current differential protection
• Compare iin and iout
• |iin– iout|≈0 no internal fault • |iin– iout|>>0 internal fault: Trip CB

G
Time

Distance Time

• Generators
• iin and iout of each winding

• Communication needed for lines
G
Distance
Electric Power Systems - Olof Samuelsson 29

M

Ex

Electric Power Systems - Olof Samuelsson

30

Example: Permanent fault Automatic sectionalizer
– Cost-effective restoration of service
• Sectionalizer with transducers and logic
R S Load3 S Load2 S Load1 R
S1 Load1

R S

R S

R S

R S

R S

– Operates when recloser R is open
• Need not interrupt fault current • Simpler than circuit breaker • Operation not electrically powered

S

S2 Load2 Load3

S

S

S

S

S

S

– Counts periods of fault current
• Opens after preset number • Maximum area restored • Radio message to repairman
Electric Power Systems - Olof Samuelsson 31

Normal S1 preset to 3 S2 preset to 2

Fault occurs S1 count 1 S2 count 1

R opens

R recloses S1 count 2 S2 count 2 Fault not temporary!

R opens S2 opens
32

R closes

Electric Power Systems - Olof Samuelsson

System protection
• ”Unit protection”=Fault protection
– Protects generator, line, transformer… – Weakens system when tripping CB

Calculating fault current
• Short-circuit protection input data
– Minimum short-circuit current – Maximum load current

• System protection=Blackout protection
– Acts to avoid system blackout – E.g. Sacrifice some load to save the rest

• Circuit breaker selection input data
– Maximum short-circuit current

• All protection is based on knowledge
– Normal and abnormal operation – Coordinating protection in nuclear plant!
Electric Power Systems - Olof Samuelsson 33

• Short-circuit current calculation
– Based on network data – Detailed like load flow or Thévenin-based
Electric Power Systems - Olof Samuelsson 34

Summary
• Short-circuit most common fault (lightning) • Fuses and protection
– Dependable = not miss a fault – Selective = not overreact – Many relay types – One zone for each relay

• Limiting blackout-area
– Coordination, autoreclosing, autosectionalizing
Electric Power Systems - Olof Samuelsson 35

Sponsor Documents

Or use your account on DocShare.tips

Hide

Forgot your password?

Or register your new account on DocShare.tips

Hide

Lost your password? Please enter your email address. You will receive a link to create a new password.

Back to log-in

Close