Ohio-Power-Co-Lighting-Incentives

Published on June 2016 | Categories: Documents | Downloads: 46 | Comments: 0 | Views: 472
of 49
Download PDF   Embed   Report

Comments

Content


Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Version: November 19, 2012
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
TABLE OF CONTENTS
STEPS FOR SUBMITTING YOUR APPLICATION 1
CHECKLIST 2
TERMS AND CONDITIONS 3
APPLICANT INFORMATION 7
FINAL PAYMENT AGREEMENT 8
CUSTOMER AGREEMENT 10
LIGHTING WORKSHEET 12
LIGHTING SPECIFICATIONS 16
HVAC WORKSHEET 20
HVAC SPECIFICATIONS 23
MOTORS & DRIVES WORKSHEET 26
MOTORS & DRIVES SPECIFICATIONS 28
COMPRESSED AIR WORKSHEET 29
CUSTOM COMPRESSED AIR SYSTEM DETAILS 31
COMPRESSED AIR SPECIFICATIONS 33
REFRIGERATION/FOOD SERVICE WORKSHEET 35
REFRIGERATION/FOOD SERVICE SPECIFICATIONS 37
AGRICULTURE & MISCELLANEOUS WORKSHEET 39
AGRICULTURE & MISCELLANEOUS SPECIFICATIONS 40
TRANSFORMER WORKSHEET AND SPECIFICATIONS 42
ENERGY STAR® AC-OUTPUT UNINTERRUPTIBLE POWER SUPPLY
(UPS) FOR NON-DATA CENTERS WORKSHEET AND SPECIFICATIONS 43
ENERGY STAR® AC-OUTPUT UNINTERRUPTIBLE POWER SUPPLY
(UPS) FOR NON-DATA CENTERS GLOSSARY 44
CUSTOM WORKSHEET 45
CUSTOM SPECIFICATIONS 46
Page 1
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
STEPS FOR SUBMITTING YOUR APPLICATION
¹A Pre-Approval Application is not a guarantee of an incentive; the actual incentive will be based on the energy savings and equipment installed as determined in the Final Application.
Funds are reserved for 90 days, unless an applicant is granted an extension. The program team reserves the right to contact the customer before the reservation expiration date to ensure
that the project is moving forward. If the project is not underway, the reservation may be cancelled. Reserved funds are not transferable to other projects, facilities and/or customers. A
waiting list will be established if funds become fully subscribed.
Step 1: Verify Project, Equipment and
Customer Eligibility
9 Project is a new facility improvement that produces a
permanent reduction in electrical energy usage (kWh).
9 All installed equipment must meet or exceed the
specifcations in the application.
9 Equipment must be installed in facilities served by AEP
Ohio.
9 Customer has a valid AEP Ohio account number on
an eligible AEP Ohio non-residential account or an
approved agricultural account.
Step 2: Submit Pre-Approval Application to
Reserve Funds¹
9 Submitting a Pre-Approval Application to determine
qualifcation and reserve program funds for a project is
strongly recommended.
9 Some prescriptive measures and all custom measures
require pre-approval. Check the specifcations page for
details.
9 The Pre-Approval Application process consists of:
• Completing the left side of the Checklist page
• Reading the Terms and Conditions
• Completing the Applicant Information form
• Attaching the documentation listed:
- Measure worksheet(s)
- Proposed scope of work (type, quantity and wattage of
old and new equipment)
- Specifcations for all equipment showing it meets
program specifcations
9 Submit the application via email, fax or mail.
9 The program team will contact applicants requiring a
pre-installation inspection for scheduling.
9 Use the same form for the Pre-Approval Application and
Final Application.
9 Incentives will be calculated using the Final Application’s
program year rules and requirements.
Step 3: Install Equipment and Perform
Project Work
9 Complete project within the 90-day reservation
period. Contact the AEP Ohio Business Incentives
program team for specifc questions regarding funding
reservations and extensions.
9 Confrm that equipment meets or exceeds program
specifcations and requirements.
Step 4: Submit Final Application
9 Submit a Final Application within 60 days of project
completion.
9 Use the same form for the Final Application as the Pre-
Approval Application.
9 Complete the right side of the Checklist page.
9 Read the Terms and Conditions.
9 Attach the documentation listed:
• Completed and signed Customer Agreement form
• Measure worksheet(s)
• Scope of work (type, quantity and wattage of old and new
equipment)
• Dated and itemized invoices for the purchase and installation
of all equipment installed
• Specifcations for all equipment installed showing that it meets
program specifcations
9 Submit the Final Application via email, fax or mail.
9 The program team will review your Final Application.
9 If a fnal inspection is required, you will be contacted
for scheduling.
Step 5: Receive Incentive Payment
9 The program team will send incentive payment 4 to 6
weeks after the Final Application has been reviewed, all
measures have been verifed and the project is approved.
AEP Ohio Business Incentives Program
2740 Airport Drive, Suite 160
Columbus, OH 43219
Phone: (877) 607-0739
Fax: (877) 607-0740
[email protected]
Visit our website at aepohio.com/incentives.
Page 2
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
CHECKLIST
PRE-APPROVAL APPLICATION
Required Attachments
ˆ Completed Applicant Information form
ˆ Completed Incentives Requested section of
Application form
ˆ Signed Customer Agreement form
ˆ Proposed scope of work
ˆ Equipment specifcations
Incentive Worksheets
Please complete worksheets for checked boxes.
ˆ Lighting
ˆ HVAC
ˆ Motors & Drives
ˆ Compressed Air
ˆ Refrigeration/Food Service
ˆ Agriculture & Miscellaneous
ˆ Transformer
ˆ UPS
ˆ Custom
Application date_______________
Estimated project cost_______________
Expected completion date__________
Project funds will be reserved for 90 days from reservation date.
FINAL APPLICATION
Required Attachments
ˆ Completed Applicant Information form
ˆ Completed and signed Final Payment Agreement
and Customer Agreement forms
ˆ Completed Third-Party Payment Release
Authorization section (if applicable)
ˆ Itemized invoices
ˆ Equipment specifcations
ˆ Updated scope of work, if project changed
ˆ W-9 (LLC, individual, partnership, property
management companies)
Incentive Worksheets
Please complete worksheets for checked boxes.
ˆ Lighting
ˆ HVAC
ˆ Motors & Drives
ˆ Compressed Air
ˆ Refrigeration/Food Service
ˆ Agriculture & Miscellaneous
ˆ Transformer
ˆ UPS
ˆ Custom
Application date_______________
Final project cost_______________
Final completion date_______________
Incomplete applications will delay processing and incentive payment.
AEP Ohio Business Incentives Program
2740 Airport Drive, Suite 160
Columbus, OH 43219
Phone: (877) 607-0739
Fax: (877) 607-0740
[email protected]
Visit our website at aepohio.com/incentives.
Revised Submittal
Please complete below if this is a revised submittal.
Submittal date__________________________________ AEP Project Number (if known) AEP - 1 __ - __ __ __ __ __
Page 3
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
TERMS AND CONDITIONS
AEP Ohio offers prescriptive and custom incentives under
the AEP Ohio Business Incentives Program to facilitate
the implementation of cost-effective energy effciency
improvements for non-residential accounts or approved
agricultural accounts.
Please note that funds are limited and subject to availability.
Program Effective Dates
AEP Ohio Business Incentives Program offers incentives until
approved funds are exhausted or November 15, , whichever
comes frst. The effective dates of the current AEP Ohio Business
Incentives Program and application submittal requirements are as
follows:
• Projects with a fnal completion date before November
16, 2012, may not be eligible for an incentive through this
application. Self-direct projects must apply via the separate
AEP Ohio Business Incentives Program self-direct application.
• All 2013 AEP Ohio Business Incentives Program projects must
be completed and Final Applications received no later than
November 15, 2013, in order to qualify for incentives identifed
in this application.
Program and Project Eligibility
The AEP Ohio Business Incentives Program offers prescriptive
incentives for some of the more-common energy effciency
measures and custom incentives for other eligible improvements
not included on the list of prescriptive measures. Program
incentives available under the AEP Ohio Business Incentives
Program include non-residential accounts or approved agricultural
accounts served on AEP Ohio’s regulated retail rates.
Qualifying projects must be installed in a facility in AEP Ohio’s
electric service territory in Ohio. Incentives are available to all
non-residential accounts or approved agricultural accounts that
pay into the Energy Effciency and Peak Demand Response (EE/
PDR) rider and receive their electricity over AEP Ohio wires,
regardless from which retail electric supplier the customer has
chosen to purchase power. A customer may neither apply for nor
receive incentives for the same product, equipment or service
from more than one utility.
Custom projects must involve measures that result in a reduction
in electric energy usage due to an improvement in system
effciency. Projects that result in reduced energy consumption
without an improvement in system effciency are not eligible for a
custom incentive. The project simple payback prior to the incentive
payment generally should fall between 1 to 7 years, or pass cost-
effectiveness test(s) determined by AEP Ohio to qualify for an
incentive. Incentives are based on frst-year energy savings.
Projects involving measures covered by the prescriptive incentive
portion of the program are not eligible for custom incentives.
However, the applicant has the option to apply for a custom
incentive for whole building integrated projects or systems, even if
they include prescriptive measures. Prescriptive elements may be
capped at the deemed savings and/or incentive level.
Project requirements under the AEP Ohio Business Incentives
Program include the following:
• Projects must involve a new facility improvement with capital
improvements that results in a permanent reduction in
electrical energy usage (kWh). Existing/old equipment must be
functional and in operation.
• Any measures installed at a facility must be sustainable
and provide 100% of the energy benefts as stated in the
application for a period of at least fve (5) years or for the life
of the product, whichever is less. If the customer ceases to
be a delivery service customer of AEP Ohio or removes the
equipment or systems at any time during the 5-year period or
the life of the product, the customer may be required to return
a prorated amount of incentive funds to AEP Ohio.
• All equipment must be new.
• All installed equipment must meet state, federal and local
codes and requirements.
• Projects must be installed on the AEP Ohio electric account in
Ohio served by an eligible electric rate.
• Equipment must be purchased, installed and operating (or
capable of operating in the case of seasonal uses) prior to
submitting a Final Application for an incentive.
• AEP Ohio will issue incentive payments in the form of checks,
not utility bill incentives.
• The incentive is paid as a one-time, one-program offer and
cannot be combined with incentive payments from other AEP
Ohio programs. The customer may be eligible to participate
in other programs offered by AEP Ohio, as long as no project
receives more than one incentive.
Confdential information contained in any documents associated
with this application will be protected from public flings. However,
this information may be disclosed to the PUCO for further review
and approval.
Projects that are NOT eligible for an incentive include the
following:
• Fuel switching (e.g., electric to gas or gas to electric)
• Changes in operational and/or maintenance practices or
simple control modifcations not involving capital costs (Please
visit aepohio.com/incentives for Retro-Commissioning Program
or Continuous Improvement Program)
• Removal or termination of existing processes, facilities and/or
operations
Page 4
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
• On-site electricity generation
• Projects involving gas-driven equipment in place of or to
replace electric equipment (such as a chiller)
• Projects focused primarily on power factor improvement
• Projects that involve peak-shifting (and not kWh savings)
• Used or rebuilt equipment
• Costs associated with internal labor
• Renewables (Please visit aepohio.com/save for Renewables
Program)
• Projects required by state or federal law, building or other
codes, or projects that are standard industry practice
• Projects easily reverted/removed or projects installed entirely
for reasons other than improving energy effciency
• Other conditions to be determined by AEP Ohio
Incentive Payment Limits
Incentive levels for prescriptive measures are provided in the
technology specifcations included in this application. Incentives
for custom measures are $0.08/kWh (energy). All incentives are
paid as a one-time incentive based on one-year energy and/or
demand savings.
The total incentive payment shall be the lesser of: 1) The
calculated incentive as approved by AEP Ohio or 2) 50% of total
project cost (not including internal labor).
Incentive Tiering
The total incentive paid for any retroft application cannot exceed
50% of the total project cost (not including internal labor). In
addition to the above project cost limit, incentive payment rates
vary when a customer’s calculated incentive exceeds the following
tiers:
• Tier 1 $0 - $100,000 = 100% of eligible calculated incentive
value
• Tier 2 $100,001 - $300,000 = 50% of eligible calculated
incentive value
• Tier 3 $300,001 - $500,000 = 25% of eligible calculated
incentive value
• Tier 4 $500,001 - beyond = 10% of eligible calculated
incentive value
Application Review Process
Applications are not a guarantee of program acceptance and
incentive payment. AEP Ohio will review applications for eligibility
and completeness. Completed applications will be reviewed in
the order received. Funds are reserved for the project when AEP
Ohio receives a complete application and determines that the
project meets the program eligibility requirements. Applicants who
submit incomplete applications will be notifed of defciencies upon
review of the application and may lose their place in the review
process until all requested information is received. Applications
must be completed and all information received by the deadlines
defned above to begin processing. Applicants are encouraged to
call the program hotline with any questions about documentation
requirements.
Pre-Approval Application
Prescriptive projects requiring pre-approval include new T8/T5
fxtures, delamping, LED, induction, lighting controls, guest room
energy management systems (EMS), VSDs on HVAC chillers,
EMS, air-side economizers, window flm and compressed air
measures.
All custom projects require pre-approval.
Final Application
The Final Application must be submitted within 60 days of
project completion. Final Applications and all required supporting
documentation should be received by November 15, 2013, to be
applicable for the 2013 program year.
A signed application with supporting project documentation
verifying project installation and capital improvements must be
submitted to AEP Ohio prior to application approval. Project
documentation, such as (but not limited to) copies of dated
invoices for the purchase and installation of the measures,
equipment specifcation sheets, energy-savings analysis,
complete application and W-9 forms (LLC, individual, partnership,
property management companies), is required. The invoice should
provide suffcient detail to separate the project cost from the costs
of other services not related to the energy effciency project and
other repairs. The location or business name on the invoice must
be consistent with the application information.
AEP Ohio reserves the right to request additional supporting
documentation as deemed necessary to ensure measure
eligibility and verify that the expected energy savings will occur.
Confdential information contained in any documents associated
TERMS AND CONDITIONS
PRESCRIPTIVE/CUSTOM PROGRAM INCENTIVES
Energy effciency incentive
levels are for one-year energy
savings
See tables for prescriptive
incentives. Custom incentives are
paid at $0.08/kWh.
Minimum/maximum simple
payback before energy
effciency incentive(s) applied
Must pass cost-effectiveness
test(s) (determined by AEP Ohio).
Generally 1 year min./7 year max.
Maximum payout
50% of the project cost (additional
caps also may apply)
Incentive calculation order
Measure incentive caps are
applied frst. Project cost incentive
limits are applied second. Incentive
tiering is applied third.
Page 5
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
TERMS AND CONDITIONS
with this application will be protected from public flings. However,
this information may be disclosed to the PUCO and the evaluators
for further review. Requested information as proof of project
completion could include equipment purchase dates, installation
dates, proof that the equipment is operational, manufacturer
specifcations, warranty information, invoices and proof of owner
co-payment.
Inspections
The AEP Ohio Business Incentives Program reserves the right
to inspect all projects to verify compliance with the program
rules and the accuracy of project documentation. This may
include pre-installation and/or post-installation inspections,
verifcation of detailed lighting layout descriptions, metering, data
collection, interviews and utility bill data analyses or monitoring
data analysis. Customers are required to allow access to project
documents and the facility where the measures are installed
for a period of fve years after receipt of incentive payment from
AEP Ohio. In the event a building(s) are turned over to a new
account holder/owner before AEP Ohio has offcially measured
and verifed incentivized equipment, AEP Ohio reserves the right
to do so under new ownership. Customer understands and agrees
that program installations may also be subject to inspections by
the PUCO or its designee, and photographs of installation may be
required.
Requirements for Custom Project Electricity
Savings Calculation
The annual electricity savings for custom projects must be
calculated using industry-accepted engineering algorithms
or simulation models. The applicant may estimate the annual
electricity usage of both the existing and proposed equipment
based on the current operation of the facility. Find a listing of the
pre-existing information requirements at the end of the custom
application section. If equipment is replaced prior to the end of its
rated service life in order to achieve energy savings, the existing
equipment performance may be used as the baseline in the
energy-savings calculations. Documentation of early replacement
decision and/or actual equipment energy usage will be required.
If equipment is replaced due to failure or for other reasons (such
as obsolescence or a need for more capacity), the baseline
performance used in the savings calculation should be either the
minimum performance that would be required by code for that
equipment type and application (where a code applies) or the
performance of the equipment that would have been selected as
the customer’s standard practice when a code does not apply.
The applicant must be able to clearly describe the method used to
calculate the savings. The applicant must provide all assumptions
used in the calculations and document the sources for these
assumptions. If no savings analysis is provided by the customer/
contractors, AEP Ohio reserves the right to utilize its approved
methodology and analysis to determine energy savings.
The method and assumptions used by the applicant to calculate
the annual savings will be reviewed by AEP Ohio. AEP Ohio is
solely responsible for the fnal determination of the annual energy
savings to be used in calculating the incentive amount. AEP
Ohio also reserves the right to require specifc measurement and
verifcation activities, including monitoring both before and after
the retroft to determine the incentive. Verifcation of the pre-
existing consumption may also be required.
For custom projects, the applicant is required to submit a Pre-
Approval Application while the existing equipment is still in
operation in order to allow AEP Ohio the opportunity to verify the
existing equipment. AEP Ohio may need to conduct inspections
both before and after retroft projects to verify equipment and
operating conditions.
Customers are encouraged to submit projects that warrant special
treatment (i.e., non-typical projects) to be considered on a case-
by-case basis by AEP Ohio.
Tax Liability
Incentives are taxable and, if more than $600, will be reported
to the IRS unless the customer is exempt. AEP Ohio is not
responsible for any taxes that may be imposed on your business
as a result of your receipt of payment. A W-9 (for LLC, individual,
partnership, property management companies) must be provided
with all applications.
Disclaimer
Any and all energy savings and coincident demand generated by
the project described in this application are hereby committed to
AEP Ohio. That retained demand can be used to count against
AEP Ohio’s benchmark requirements in S.B. 221, regardless; any
retained demand provided to PJM generation auctions must be
done so by AEP Ohio only.
Peak-demand reduction is defned as the reduction in average
load over the performance hours as a result of replacing existing
electrical equipment with more-effcient electrical equipment.
Peak performance hours are defned as the time between June
1 and August 31 on weekdays and non-holidays, between the
hours 3:00 p.m. and 6:00 p.m. Eastern Standard Time. PJM Peak
Hours are defned as the time between June 1 and August 31 on
weekdays and non-holidays, between the hours 2:00 p.m. and
6:00 p.m. Eastern Standard Time.
AEP Ohio does not guarantee the energy savings and does
not make any warranties associated with the measures eligible
for incentives under this program. AEP Ohio has no obligations
regarding and does not endorse or guarantee any claims,
Page 6
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
TERMS AND CONDITIONS
promises, work or equipment made, performed or furnished by
any contractors or equipment vendors that sell or install any
energy effciency measures. AEP Ohio is not responsible for the
proper disposal/recycling of any waste generated as a result of
this project. AEP Ohio is not liable for any damage caused by the
operation or malfunction of the installed equipment.
Page 7
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
APPLICANT INFORMATION
Important: Please read the Terms and Conditions before signing and submitting this application. Complete all information
and provide required documentation to avoid processing delays.
Name of Applicant’s Business _________________________________________________________________________________
Project Name (if applicable)_________________________ Name as It Appears on Utility Bill______________________________
AEP Ohio Account Number Where Measure Installed __________________ Taxpayer ID (SSN/FEIN) _______________________
Mailing Address ____________________________________ City_____________________________ State_____ Zip___________
r Check if mailing address and installation address are the same.
Installation Address _________________________________ City_____________________________ State_____ Zip___________
Project Information
Customer Contact
Please provide all contacts we may need to process this project. List the project decision-maker, the technical contact, etc. as the
contractor contact.
Name of Contact (preferred contact for documentation)_____________________________________________________________
Title of Contact____________________________________ Phone #____________________________ Ext._________________
Contact Fax #_____________________________________ Contact Email_____________________________________________
Name of Contracting Company ________________________________________________________________________________
Name of Contact Person____________________________________ Title of Contact______________________________________
Mailing Address ____________________________________ City_____________________________ State_____ Zip___________
Phone #___________________ Ext._______ Contact Fax #___________________ Contact Email__________________________
If there are questions about the application who should we contact? r Customer r Contractor
Solution Provider/Contractor Information¹
¹Solution provider/contractor is the party involved in the application submittal (i.e., specs, scope of work, etc.).
Business Type W-9 Tax Status
How Did You Hear About the
Program?
______________________________ ______________________________ ______________________________
Shift Affected Area Square Footage Dodge Report Number
______________ ______________ ______________
Building Operating Hours Equipment Operating Hours
______________ ______________
(Select One) (Select One) (Select One)
(Select One)
OH
OH
OH
Page 8
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
I understand that Final Applications and all required supporting
documentation should be received by November 15, 2013,
to be eligible for the current program year’s incentives. Final
Applications submitted after November 15, 2013, are subject to
the next program year’s incentive rates and program rules.
I understand that the Final Application and all required
documentation must be received by the AEP Ohio Business
Incentives Program within 60 days of project completion. All
equipment must be purchased, installed and fully operational prior
to submitting the Final Application.
I understand that AEP Ohio or its representatives have the right
to ask for additional information at any time. AEP Ohio Business
Incentives Program will make the fnal determination of incentive
levels for this project.
I understand that this project must involve a facility improvement
that results in improved energy effciency.
I understand that once the energy effciency project is complete,
I will resend the application with any as-built changes along with
the signed Final Payment Agreement. As an eligible AEP Ohio
account holder, I certify that decisions to acquire and install the
indicated energy effciency measures, which will be demonstrated
with supporting documentation required by AEP Ohio, were made
after November 16, 2012, and that work was completed on this
project on or before November 15, 2013. The energy effciency
measures are for use in my business facility and not for resale.

I understand that the location and business name on the
project documentation must be consistent with the application
information. Project documentation, product specifcation sheets
and details of measure installation are included. Documentation
indicating contract dates prior to November 16, 2012, may render
this application ineligible. I understand that all submissions
become the property of AEP Ohio. It is recommended to keep a
copy for your records.
I agree that if: (1) I do not install the related product(s) identifed
in my application or (2) I remove the related product(s) identifed
in my application before a period of fve (5) years or the end of
the product life, whichever is less, then I shall refund a prorated
amount of incentive funds to AEP Ohio based on the actual
period of time for which the related product(s) were installed and
operating (or the full amount, if the product was never installed).
This is necessary to assure that the project’s related energy
benefts will be achieved. (3) AEP Ohio will pay the lesser of: 1)
The calculated incentive as approved by AEP Ohio or 2) 50%
of the cost of the project. I understand that AEP Ohio or its
representatives have the right to ask for additional information at
any time. AEP Ohio Business Incentives Program will make the
fnal determination on incentive payments for this project.
I agree to be responsible to comply with any applicable codes
or ordinances. I also understand that all materials removed,
including lamps and PCB ballasts, must be permanently taken
out of service and disposed of in accordance with local codes
and ordinances. I understand it is my responsibility to be aware of
any applicable codes or ordinances. Information about hazardous
waste disposal can be found at epa.gov/epawaste/hazard/index.
htm.
I agree to verifcation by the utility or its representatives of sales
transactions, equipment installation and performance testing.
I understand that these incentives are available to all non-
residential accounts or approved agricultural accounts that pay
the Energy Effciency and Demand Response (EE/PDR) rider
and receive their electricity over AEP Ohio wires, regardless from
which retail electric supplier the customer has chosen to purchase
power.
I understand that AEP Ohio reserves the right to refuse payment
and participation if the customer or contractor violates program
rules and requirements. AEP Ohio is not liable for incentives
promised to customers as a result of misrepresentation of the
program.
I understand that AEP Ohio does not guarantee the energy
savings and does not make any warranties associated with the
measures eligible for incentives under this program. Furthermore,
AEP Ohio has no obligations regarding promises, work or
equipment made, performed or furnished by any contractors
or equipment vendors that sell or install any energy effciency
measures and does not endorse or guarantee same.
I understand that in the event the application receives pre-
approval and funds are reserved based upon the application, such
pre-approval or reservation, including the specifc dollar amount of
reservation, does not represent a guarantee that such funds will
be paid. Payment of incentives will be based upon the fnal review
of the application and program terms and conditions, as well as
the availability of funds.
I understand that the program has a limited budget. Applications
will be processed until allocated funds are reserved or spent. Final
Applications should be received by November 15, 2013, to be
eligible for funding under the current program period.
I certify that the information on this application is true and correct,
and that the taxpayer ID number, tax status and W-9 are the
applicant’s. I understand that incentives exceeding $600 will be
reported to the IRS, unless the applicant is exempt. I understand
that incentive payments assume related energy benefts over a
FINAL PAYMENT AGREEMENT
Page 9
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
period of fve (5) years or for the life of the product, whichever is
less.
I understand that the program may be modifed or terminated
without prior notice.
I understand and agree that all other terms and conditions as
specifed in the application, including all attachments and exhibits
attached to this application, will serve as a contract for the
customer’s commitment of energy and demand resources to AEP
Ohio and shall apply.
Any and all energy savings and coincident demand generated by
the project described in this application are hereby committed to
AEP Ohio. That retained demand can be used to count against
AEP Ohio’s benchmark requirements in S.B. 221, regardless; any
retained demand provided to PJM generation auctions must be
done so by AEP Ohio only.
FINAL PAYMENT AGREEMENT
Page 10
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
CUSTOMER AGREEMENT
ˆ As an eligible customer, I verify the information is correct and request consideration for participation under this program.
Customer Signature (AEP Ohio Customer) Print Name
_____________________________________________ ________________________________________

Total Incentive Requested¹ Date
_____________________________________________ ________________________________________

Estimated Completion Date Estimated Project Cost
_____________________________________________ ________________________________________
Pre-Approval Application
¹AEP Ohio will pay the lesser of 1) the calculated incentive as approved by AEP Ohio or 2) 50% of the total project cost (not including internal labor).
Digital Signature Instructions
1. Click in the signature box.
2. Follow the digital signature directions displayed in the “Add
Digital ID” pop-up box.
3. Establish a digital ID and password.

4. In the “Sign Document” pop-up box, you can select to
change the signature appearance from typed font to an
imported graphic.
5. Follow directions to save signed application; signature and
verifcation information will appear in the signature box.
Complete this section ONLY if incentive payment is to be paid to an entity other than the AEP Ohio customer listed on the Applicant
Information page.
ˆ I authorize the payment of the incentive to the third party named below and understand that I will not receive the incentive payment
from AEP Ohio. I also understand that my release of the payment to a third party does not exempt me from the program requirements
outlined in the measure specifcations, Terms and Conditions, and Final Payment Agreement.
Authorized by Date
_____________________________________________ ________________________________________
Account Holder Signature (AEP Ohio Customer) Print Name
_____________________________________________ ________________________________________
Third Party Payment Release Authorization (optional)
Make checks payable to
Company/Individual _______________________________________________________________________________________________________
Mailing Address ____________________________________ City_____________________________ State_____ Zip___________
Phone #______________________Taxpayer ID # (SSN/FEIN of payee)__________________ Tax Status_______________________
02/18/13
02/18/13
OH

Page 11
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Final Application
ˆ I have read and understand the program requirements, measure specifcations, and Terms and Conditions set forth in this
application and agree to abide by those requirements. Furthermore, I concur that I must meet all eligibility criteria in order to receive
payment under this program. For fnal applications, sign and submit only after all equipment is installed and operational. A customer
signature is required for payment. Signed applications received by email or fax will be treated the same as original applications
received by mail.
AEP Project Number
AEP - 1 __ - __ __ __ __ __
Total Project Cost Total Incentive Requested¹
_____________________________________________ ________________________________________
Customer Signature (AEP Ohio Customer) Print Name
_____________________________________________ ________________________________________

Date Project Completion Date
_____________________________________________ ________________________________________
SUBMIT VIA EMAIL PRINT APPLICATION
¹AEP Ohio will pay the lesser of 1) the calculated incentive as approved by AEP Ohio or 2) 50% of the total project cost (not including internal labor).
CUSTOMER AGREEMENT
ˆ As an eligible customer, I verify the information is correct and request consideration for participation under this program.
02/18/13
Page 12
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
The T12 to T8 incentive was reduced from $5 per lamp to $3 per lamp on December 17, 2012. Measures involving the
replacement of T12 fxtures/lamps received after June 30, 2013, will not be eligible for an incentive.
LIGHTING WORKSHEET
Fluorescent Lighting Retrofts to High Performance (HP) or Reduced Wattage (RW) 4-Foot T8s
Equipment Type
Incentive
per Unit
Unit
Number of Units per Space
Incentive
Interior Exterior
Garage
24-Hour
Total
4-ft HP T8 Lamp and
Ballast (Linear and
U-Bend)
T12 Baseline $3.00 Lamp
4-ft RW T8 Lamp and
Ballast (Linear and
U-Bend)
T12 Baseline $3.00 Lamp
1-Lamp 8-ft T12 to
2-Lamp 4-ft T8s
High Performance (HP) $3.00 4-ft Lamp
Reduced Wattage (RW) $3.00 4-ft Lamp
Retroft 8-Foot T12 With Reduced Wattage (RW) 8-Foot T8
Retroft 8-ft T12 With RW 8-ft T8 Lamp and Ballast $5.00 Lamp
Other Linear Fluorescent Retrofts to T8s or T5s
2-ft T8 Lamp and Ballast T12 Baseline $3.00 Lamp
3-ft T8 Lamp and Ballast T12 Baseline $3.00 Lamp
T12 to 4-ft T5 Lamps and Electric Ballast $3.00 Lamp
Permanent T12 Lamp Removal (Pre-Approval Required)
2-ft Lamp T12 Removed $3.00 Lamp Removed
3-ft Lamp T12 Removed $3.00 Lamp Removed
4-ft Lamp T12 Removed $3.00 Lamp Removed
8-ft Lamp T12 Removed $5.00 Lamp Removed
Total T12 Incentives
Quick Guide to Incentives for Popular T12 to T8 Upgrades (T12 measures are not eligible after June 30, 2013)
Popular T12 to T8 Upgrades Applicable Incentives for Each Fixture
Retroft 4-ft 4-Lamp T12 to 4-ft 4-Lamp F28 T8 4-ft RW Lamps and Ballast $3/Lamp # of Lamps Installed: 4
Retroft 4-ft 4-Lamp T12 to 4-ft 2-Lamp F32 T8
4-ft HP Lamps and Ballast $3/Lamp # of Lamps Installed: 2
Permanent Lamp Removal $3/Lamp # of Lamps Removed: 2
Retroft 2-Lamp 4-ft T12 U-tube to 2-Lamp 2-ft F17 T8
2-ft T8 Lamps and Ballast $3/Lamp # of Lamps Installed: 2
Permanent Lamp Removal $3/Lamp # of Lamps Removed: 1
Retroft 2-Lamp 8-ft T12 to 2-Lamp 4-ft F28 T8
1-Lamp 8-ft to 2-Lamp RW 4-ft T8 $3/Lamp # of Lamps Installed: 2
Permanent Lamp Removal $5/Lamp # of Lamps Removed: 1
Page 13
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Other Lighting (Pre-Approval Required)
Supply project description in existing and replacement tables to populate incentives
Incentive Category Incentive per Unit Unit Watts Reduced Incentive
New T5/T8 Fluorescent Fixtures (Replacing
Old HID/Incandescent/T12 Fixtures)
$0.30 Watts Reduced
Incentive Capped at
$30 per Lamp
Number of New Lamps
Installed
Metal Halide Retrofts and Other Lighting $0.30 Watts Reduced
Interior ENERGY STAR and DesignLights
Consortium (DLC) LED Lamp or Fixture
$0.45 Watts Reduced
Non-Interior ENERGY STAR and
DesignLights Consortium (DLC) LED Lamp
or Fixture
$0.35 Watts Reduced
Interior Non-Standard LED or Induction
Fixture
$0.40 Watts Reduced
Non-Interior Non-Standard LED or Induction
Fixture
$0.30 Watts Reduced
LIGHTING WORKSHEET
The T12 to T8 incentive was reduced from $5 per lamp to $3 per lamp on November 17, 2012. Measures involving the
replacement of T12 fxtures/lamps received after June 30, 2013, will not be eligible for an incentive.
Select Space Type and Incentive Category to determine Total Wattage
Existing
Space Type Incentive Category
Existing
Fixture
Description
Number
of
Existing
Fixtures
Lamps
per
Fixture
Existing
Wattage
Total
Existing
Wattage
Replacement
Space Type Incentive Category
New
Fixture
Description
Number
of New
Fixtures
Lamps
per
Fixture
New
Wattage
Total
New
Wattage










Page 14
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Space Type Equipment Type Type of Fixture
# of
Fixtures
Watts/
Fixture
Watts
Controlled
LIGHTING WORKSHEET
Equipment Type
Incentive
per Unit
Unit
Number of Units per Space
Incentive
Interior Exterior
Garage
24-Hour
Total
Hardwired Compact Fluorescent Fixtures (Complete New Modular Hardwired Fixture)
29W or Less $15.00 Fixture
30W to 60W $15.00 Fixture
61W to 120W $25.00 Fixture
Screw-In Compact Fluorescent Lamps (Replacing Non-Compact Fluorescent Lamps)
15W or Less $1.00 Lamp
16W to 26W $1.00 Lamp
27W to 40W $1.50 Lamp
Lighting Controls (Pre-Approval Required)
Fill in project description in table below to populate incentives
Equipment Type
Incentive
per Unit
Unit
Number of Units per Space
Incentive
Interior Exterior
Garage
24-Hour
Total
Occupancy Sensor $0.08 Watts Controlled
Daylighting Control $0.08 Watts Controlled
Time Clock for Lighting $0.02 Watts Controlled
Daylighting Control With Occupancy Sensor $0.10 Watts Controlled
Photocell $0.02 Watts Controlled
Photocell and Time Clock $0.04 Watts Controlled
Bi-Level Exterior or Garage Lighting Controls $0.10 Watts Controlled





Page 15
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
LIGHTING WORKSHEET
Traffc and Pedestrian Signals
Equipment Type Incentive per Unit Unit Number of Units Incentive
LED Traffc Light - Green 8" $25.00 Lamp
LED Traffc Light - Green 12" $35.00 Lamp
LED Traffc Light - Red 8" $25.00 Lamp
LED Traffc Light - Red 12" $35.00 Lamp
LED Traffc Light - Walk/Don't
Walk or Arrow - 9"
$40.00 Lamp
LED Traffc Light - Walk/Don't
Walk or Arrow - 12"
$50.00 Lamp
Total Lighting Incentives
Equipment Type
Incentive
per Unit
Unit
Number of Units per Space
Incentive
Interior Exterior
Garage
24-Hour
Total
Specialty CFLs (Replacing Non-Compact Fluorescent Lamps)
Cold Cathode $5.00 Lamp
Specialty CFL: PAR, Dimmable or 3-Way $10.00 Lamp
Exit Signs
LED, T1 or Cold Cathode Exit Signs $20.00 Sign
Page 16
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
T8 to T12 LIGHTING SPECIFICATIONS
Lighting projects should comply with the Illuminating Engineering Society of North America (IESNA) recommended lighting
level and local code. Measures involving a change out or removal of T12 lamps will not be eligible after June 30, 2013.
4-Foot HP Lamp and Ballast (Linear and U-Bend)
The installed lamps and ballasts should meet Consortium for
Energy Effciency (CEE) high-performance T8 specifcations and
retroft an existing T12 system. U-bend lamps also qualify. Find a
list of qualifed lamps and ballasts at cee1.org.

4-Foot RW Lamp and Ballast (Linear and U-Bend)
The installed lamps and ballasts should meet CEE reduced
wattage specifcations and retroft an existing T12 system. U-bend
lamps also qualify. Find a list of qualifed lamps and ballasts at
cee1.org.
1-Lamp 8-Foot T12 to 2-Lamp 4-Foot HP or RW T8
Retroft
This measure applies to the retroftting of existing 1-lamp 8-foot
T12 lamps and magnetic ballasts with 2-lamp 4-foot T8 lamps
and electronic ballasts. The installed 4-foot T8 lamps and ballasts
should qualify for the high performance or reduced wattage
measure.
Reduced Wattage 8-Foot Lamp and Ballast
This measure applies to the retroftting of existing 8-foot T12
lamps and magnetic ballasts with reduced wattage 8-foot T8
lamps and electronic ballasts. Use lamps with a minimum mean
LPW of 90 and a nominal wattage of 57W or less.
2- and 3-Foot Lamp and Ballast
This measure applies to the retroftting of existing T12 lamps
and magnetic ballasts with T8 lamps and electronic ballasts.
Use lamps with a CRI ≥ 80 and ballasts a THD ≤ 32% at full light
output; the PF must be ≥ 0.90.
T12 to 4-Foot T5 Lamps and Electronic Ballast
This measure applies to the retroftting of existing T12 lamps and
magnetic ballasts with 4-ft T5 lamp and new electronic ballasts.
Use lamps with a CRI ≥ 80. Use high frequency (≥ 20kHz),
NRTL listed electronic ballasts and THD ≤20% at full light.

Permanent Lamp Removal
Pre-Approval Required
This measure is applicable when retroftting from T12 lamps to
T8 or T5 lamps to reduce the number of lamps. Removing lamps
from a T12 fxture that is not retroftted with T8 or T5 lamps does
not qualify. Delamping T8 or T5 lamps from an existing T8/T5
fxture applies as an Other Lighting measure.

Customers are responsible for determining whether or not to use
refectors in combination with lamp removal in order to maintain
adequate lighting levels. Lighting levels should meet IESNA-
recommended light levels. Permanently remove unused lamps,
lamp holders and ballasts from the fxture and dispose of them in
accordance with local regulations.
Page 17
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
LIGHTING SPECIFICATIONS
Other Lighting Measure
This measure applies to lighting projects that do not qualify for
one of the measures offered elsewhere in the application. New
equipment must have a higher mean effcacy (lumens per watt)
than the existing equipment.
The following are not eligible under this measure:
• Retroftting to T8 lamps that are not on CEE list
• Retroftting to lower-wattage lamps of the same technology
• Retrofts with a measure life of less than three years
Examples of eligible projects include:
• High intensity discharge to compact fuorescent fxtures
• High wattage CFL retrofts
• Delamping T8 lamps from T8 fxtures
• Non-interior LED and induction
Projects will be approved on a case-by-case basis, based on
currently available industry standards.
The following are specifc requirements per certain lighting
categories:
New T8/T5 Fluorescent Fixture With Electronic
Ballast Pre-Approval Required
This measure covers the replacement of one or more existing
fxture with new fxtures containing T8 or T5 lamps and
electronic ballasts. Incentives are only available for new fxtures.
Replacement of any T12 fxture/lamp will not be eligible after June
30, 2013. Retroft kits are not considered new fxtures. High bay
and low bay fuorescent applications qualify.
Use T8 or T5 lamps with CRI ≥ 80. Use high frequency (≥ 20 kHz),
NRTL listed electronic ballasts that have a PF ≥ 0.90. Ballasts for
4-foot lamps must have total THD ≤ 20% at full light output. For
2- and 3-foot lamps, ballasts must have THD ≤ 32% at full light
output. High output T5/T8 lamps also qualify.
Specifcations for new fxtures, lamps and ballasts must
accompany the application. A $30-per-lamp cap applies to this
measure.
Standard T8 to High-Performance or Reduced
Wattage T8 Retroft
This measure applies to the retroftting of standard T8 lamps
with CEE-qualifed T8 lamps. Install CEE-qualifed electronic
ballasts. New, higher-effciency lamps and ballasts may allow for
delamping within the fxture, or ballast factor reduction, resulting in
energy savings. U-bend lamps also qualify. Find a list of qualifed
lamps and ballasts at cee1.org.
Customers are responsible for determining whether or not to use
refectors in combination with lamp removal in order to maintain
adequate lighting levels. Lighting levels should meet IESNA-
recommended light levels. Permanently remove unused lamps,
lamp holders and ballasts from the fxture and dispose of them in
accordance with local regulations.
Metal Halide Fixtures
Total replacement wattage must be lower than existing wattage to
ensure energy savings.
Pulse Start or Ceramic
This measure covers the replacement of mercury vapor, high-
pressure sodium, standard metal halide, incandescent or T12
fxtures (T12 fxture/lamp replacement will not be eligible after
June 30, 2013.) with either new or retroft kit pulse start metal
halide or ceramic metal halide fxtures. Use retroft kits on existing
mercury vapor, standard metal halide or high-pressure sodium
fxtures only.
Probe Start HID to Ceramic Discharge Metal Halide
Lamp
This measure covers the retroftting of probe start high intensity
discharge fxtures with ceramic discharge metal halide lamps.
Compatibility between new lamps and the existing ballast and
socket is required.
Integrated Ballast Ceramic Metal Halide Lamp
Replace incandescent lamps or high intensity discharge fxtures
with qualifying integrated ballast ceramic metal halide PAR lamps
that are 25 watt or less with a rated life of 12,000 hours or greater.
LED Open Sign
LED open signs must replace an existing neon open sign. Use
either electronic switching or linear magnetic LED drivers, with the
electronic switching supplies being the most effcient. Find the on/
off power switch on either the power line or load side of the driver,
with the line side location providing signifcantly lower standby
losses when the sign is turned off and not operating. Replacement
signs cannot use more than 20% of the input wattage of the
existing sign.
LED Channel Sign
This measure applies to retroftting or replacing incandescent,
HID, argon-mercury or neon-lighted channel letter signs with LED
channel signs. Replacement signs cannot use more than 20% of
the input power of the replaced sign. Maximum letter height
determines incentive.
ENERGY STAR
®
and DesignLights Consortium
(DLC) LED Lamp or Fixture Pre-Approval Required
The LED lamp or fxture must appear on one of the following lists:
Page 18
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
• ENERGY STAR Qualifed Products lists, energystar.gov
• DesignLights Consortium Qualifed Products list,
designlights.org
Non-Standard LED or Induction Equipment
Pre-Approval Required
The non-standard LED measure applies to LED equipment not yet
listed by ENERGY STAR or DesignLights Consortium (DLC).
The program promotes the use of nationally recognized
specifcations for LED lighting set forth by ENERGY STAR and
DesignLights Consortium. If LED products do not meet these
standard specifcations, they may be considered for a non-
standard incentive on a case-by-case basis at the discretion
of the program. Customers considering LED lighting (i.e., for
entertainment, signage, display, hospitality or other customer
experience purposes) should contemplate installing a sample to
ensure the equipment satisfes their needs before committing to
a complete retroft. LED lighting used for non-general illumination
purposes such as signage does not have the LM-79 and LM-80
requirement.
Applicants must provide the following required documentation:
Non-Standard LED Requirements
• Manufacturer’s product information sheet
• LED package/fxture specifcation sheet
• Manufacturer methodology for calculation and justifcation of
product lifetime estimates
• Complete IESNA LM-79-08 test report(s) for each product,
for product testing conducted at approved labs. The report
should include:
- Photometric measurements (i.e., light output and effcacy)
- Colorimetry report (i.e., CCT and CRI)
- Electrical measurements (i.e., input voltage, current, power,
power factor, etc.)
• Lumen Maintenance report (compliance through component
performance for the corresponding LED package)
• IESNA LM-80 test report
• In-Situ Temperature Measurements Test (ISTMT) report
• Schematic/photograph from LED package manufacturer that
shows the specifed temperature measurement point (TMP)
LEDs that do not appear on the Qualifed Products list of either
ENERGY STAR or DesignLights Consortium will be evaluated
using the minimum performance criteria in the appropriate product
category from either ENERGY STAR or DesignLights Consortium
for the following variables:
• Light output in lumens
• Luminaire effcacy (lm/W)
• Color rendering index (CRI)
• Correlated color temperature (CCT)
• LED lumen maintenance at 6,000 hours
• Manufacturer’s estimated lifetime for L70 (70% lumen
maintenance at end of useful life)
• Three-year product warranty
Induction Fixture
The induction fxture must have a color rendering index (CRI) of 80
or above and a mean effcacy of 50 or above.
Occupancy Sensor
Passive infrared, ultrasonic detectors or fxture-integrated sensors
are eligible. Use hard-wired sensors that control interior lighting
fxtures.
Daylighting Control
Use on/off, stepped or continuous (dimming) new daylighting
sensor controls. The on/off controller should turn off artifcial
lighting when the interior luminance meets the desired indoor
lighting level.
Time Clock for Lighting
The measure applies to the installation of time clocks on interior
and exterior lighting. Clocks must control on/off schedule
of lighting equipment and protect scheduled events from
interruptions with three-hour back-up system during power
outages. Astronomical time clocks (where on/off times are in
accordance with sunrise and sunset) are required for outdoor
lighting when photocells are not in use.
Daylighting Control With Occupancy Sensor
Fixtures must meet the specifcations for occupancy sensors and
daylighting sensor controls. This measure is not applicable with
any other lighting controls.
Photocell
The measure applies to the installation of photocells on exterior
lighting to switch outdoor lights on at dusk and off at dawn.
Photocells must control the on/off schedule of lighting equipment
based upon the safety guidelines that determine the appropriate
foot candle requirements for the area controlled by the photocell.
Photocell and Time Clock
Fixtures must meet the specifcations for photocells and time clock
measures. Time clocks must turn off lighting equipment at least
three hours per night each night.
Bi-Level Exterior or Garage Lighting Controls
The lighting system must have stepped-dimming occupancy
controls that operate at full power and full light output when the
LIGHTING SPECIFICATIONS
Page 19
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
space is occupied, and at a reduced power level and reduced light
output (must reduce at least 50% of full power) when unoccupied.
To qualify for this measure, the sensors must control exterior or
parking garage lighting fxtures and be hard-wired; passive-infrared
occupancy sensors or microwave occupancy sensors are eligible.
Hardwired Compact Fluorescent Fixture
Only complete new interior fxtures or modular hardwired retrofts
with hardwired electronic ballasts for replacing non-compact
fuorescent fxtures or lamps qualify. Use a CFL ballast with
programmed start or programmed rapid start with a PF ≥ 90 and
a THD ≤ 20%. Multiple-lamp CFL assemblies do qualify for this
measure. Compact fuorescent fxtures must have a minimum
initial light effcacy of 60 LPW. Screw-in CFLs are not eligible for
this measure.
Screw-In Compact Fluorescent Lamp
Screw-in CFLs must replace non-compact fuorescent lamps
and be ENERGY STAR
®
rated lamps or meet ENERGY STAR
®

criteria. Lamps must have a minimum effcacy of 50 LPW.

Cold Cathode
All cold cathode fuorescent lamps (CCFLs) must replace
incandescent lamps between 10 and 40 watts. Cold cathode
lamps may be medium (Edison) or candelabra base. Use products
rated for at least 18,000 average life hours.

Specialty CFL: PAR, Dimmable or 3-Way
This measure applies to the replacement of incandescent, high
intensity discharge or other non-compact fuorescent lamps or
fxtures. Eligible new lamps include PAR, dimmable or 3-way.
Lamps must meet ENERGY STAR
®
criteria, if available for
the type of lamp. The lamp must have an effcacy ≥ 40 LPW.
Maximum replacement lamp wattage is 40W for this measure.

LED Exit Sign
Replace or retroft an existing incandescent or compact
fuorescent exit sign with an electroluminescent, T1 cold cathode
or light-emitting diode (LED) exit sign. Only electrifed signs
qualify.

Use new NRTL listed exit signs or retroft exit signs with a
minimum lifetime of fve years and an input wattage ≤ 5 watts
per face.

Traffc and Pedestrian Signals
The measure requires lamps with a maximum LED module
wattage of 17. Incentives apply to LED traffc lights on a per-
lamp basis (including arrows) that replace or retroft an existing
incandescent traffc signal. Spare lights are not eligible. Lights
must be hardwired, with the exception of pedestrian hand signals.
Glossary of Lighting Terms and Acronyms
CEE: Consortium for Energy Effciency
CFL: compact fuorescent lamp
CRI: color rendering index
DLC: DesignLights Consortium
HID: high intensity discharge
HO: high output
HP: high performance
IESNA: Illuminating Engineering Society of North America
LED: light emitting diode
LPW: lumens per watt or effcacy
MLPW: mean lumens per watt
NRTL: Nationally Recognized Testing Laboratories (e.g., UL)
PAR: parabolic aluminized refector
PF: power factor
RW: reduced wattage
THD: total harmonic discharge
W: watts
Notes
During the pre-inspection, existing lamps that are burned out or
removed are noted to refect actual baseline energy usage. This
will affect the project’s fnal kW and kWh savings, which will be
noted. The calculation of burned out or removed lamps occurs on
a facility-wide basis, where the burned out or removed lamps are
calculated for the entire facility and applied to all fxtures of the
same technology. The process involves:
1. During the pre-inspection, conduct the normal lighting fxture
determination, operation hour determination and fxture count.
2. Note any individual inoperable/burned out/removed lamps and
keep a running tally.
3. At the end of the inspection, calculate the total number of
burned out/inoperable or removed lamps and divide it by the
total number of lamps at the facility.
4. If this factor is greater than 10 percent, apply this burned out or
removed percentage to all lamps included in the project. If total
facility burned out or removed result is less than 10 percent, the
burned out or removed results can be ignored.
LIGHTING SPECIFICATIONS
Page 20
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
HVAC WORKSHEET
Chillers, Unitary/Split Systems, Room Air Conditioners and PTAC/PTHPs
Equipment Type Size Category
Qualifying
Effciency¹
Incentive
(Per Ton)
Effciency
Bonus²
Chillers: Water-Cooled, Centrifugal
< 300 tons 0.536 kW/ton-IPLV
$15.00 $2.00 300-599 tons 0.494 kW/ton-IPLV
≥ 600 tons 0.485 kW/ton-IPLV
Chillers: Water-Cooled, Scroll or Helical-Rotary
< 75 tons 0.567 kW/ton-IPLV
$15.00 $2.00
75-149 tons 0.554 kW/ton-IPLV
150-299 tons 0.522 kW/ton-IPLV
≥ 300 tons 0.486 kW/ton-IPLV
Chillers: Water-Cooled, Reciprocating
< 75 tons 0.567 kW/ton-IPLV
$15.00 $2.00
75-149 tons 0.554 kW/ton-IPLV
150-299 tons 0.522 kW/ton-IPLV
≥ 300 tons 0.486 kW/ton-IPLV
Chillers: Air-Cooled
< 150 tons 0.864 kW/ton-IPLV
$20.00 $2.00
≥ 150 tons 0.847 kW/ton-IPLV
Unitary and Split Air Conditioning Systems and
Air Source Heat Pumps: Air-Cooled
< 65,000 Btuh (5.4 tons) 14 SEER $20.00 $10.00
65,000-239,999 Btuh
(5.4-19.9 tons)
12 EER³
13 IEER
$35.00 $15.00
240,000-759,999 Btuh
(20-63.2 tons)
10.6 EER³
12.1 IEER
≥ 760,000 Btuh (≥ 63.3 tons)
10.2 EER³
11.4 IEER
Variable Refrigerant Flow Air Conditioners:
Air-Cooled
< 65,000 Btuh (5.4 tons) 14 SEER
$20.00 N/A
65,000-134,999 Btuh
(5.4-11.1 tons)
12 EER³
135,000-239,999 Btuh
(11.2-19.9 tons)
12 EER³
≥ 240,000 Btuh (≥ 20 tons) 10.8 EER³
Ground Source Heat Pump All 17 EER $80.00 N/A
Water Source Heat Pump All 17 EER $70.00 N/A
Room Air Conditioner All See specifcations $30.00 N/A
Package Terminal AC or Heat Pump Unit
(PTAC/PTHP)
All
13.08 - (0.2556 x
Btu/h/1000) EER
$30.00 N/A
¹Provide unit effciency for chillers in kW per ton - IPLV (IPLV = integrated part load value) at Standard Air-Conditioning and Refrigeration Institute (ARI) conditions. Provide
unit effciency in AC units less than 65,000 Btu/h in SEER. Provide unit effciency for other unitary and split AC in EER, SEER and IEER.
²Effciency Bonus is dependent on the difference between the Qualifying Effciency and the installed unit effciency. Bonus incentive amount for chillers is per 0.01 kW/ton -
IPLV per ton, and for other HVAC equipment is per 1.0 (S)EER per ton improvement.
³Units with electric resistance heating must have EER values 0.2 higher than the effciencies listed.
Page 21
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
HVAC WORKSHEET HVAC WORKSHEET
Chillers, Unitary/Split Systems, Room Air Conditioners, and PTAC/PTHPs
Equipment
Model
Equipment Type Size Category Effciency Unit Tons Effciency Quantity Incentive
Total Chiller, Unitary/Split System, Room AC and PTAC/PTHP Incentives
Guest Room Energy Management System (Pre-Approval Required)
Type/Description Incentive Unit Quantity Incentive/Unit Incentive
Hotel Guest Room Occupancy Sensor (Electric Heat) Per Room $65.00
Hotel Guest Room Occupancy Sensor (Non-Electric
Heat)
Per Room $25.00
Total Guest Room Energy Management System Incentives
Variable Speed Drive on HVAC Chiller (Pre-Approval Required)
Application Description Size in HP
Number
Installed
Incentive per HP Incentive
$30.00
$30.00
Total Variable Speed Drive on HVAC Chiller Incentives
Use the Tab key to maneuver through the chart and tabulate the incentive.







$ 0.00
Page 22
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Miscellaneous HVAC Measures (Pre-Approval Required)
Type/Description Incentive Unit Quantity Incentive/Unit Incentive
Centralized Energy Management System Control (pre-
approval required)—Maximum allowable space of 50,000
square feet and incentive capped at $10,000 per facility
Square foot (SF) of
conditioned space
$0.20
Air Side Economizer for Air Handling Units (AHUs) and
Roof Top Units (RTUs) (pre-approval required)
Tons of cooling $25.00
Toilet Room Exhaust Occupancy Sensor
(pre-approval required)
per exhaust fan $5.00
Window Film (pre-approval required)
SF of non-north-facing
window
$0.10
Electronically Commutated (EC) Motors for HVAC per motor $75.00
Demand Control Ventilation in Offces
1,000 square feet of
conditioned area
$50.00
Demand Control Ventilation in Parking Garages per HP $90.00
HVAC Occupancy Control per ton $20.00
Total Miscellaneous HVAC Incentives
Total HVAC Incentives
HVAC WORKSHEET
Page 23
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
HVAC SPECIFICATIONS
Disposal of the existing units must comply with local codes and ordinances. Manufacturer’s specifcation sheet(s)
indicating system effciency must accompany application when applicable.
Water- and Air-Cooled Chillers
Eligible chillers have a rated kW/ton for the integrated part
load value (IPLV) at Standard Air-Conditioning, Heating and
Refrigeration Institute (AHRI) conditions that is less than or equal
to the qualifying effciency indicated on the HVAC worksheet.

The chiller effciency rating must be based on AHRI Standard
550/590-2011 for IPLV conditions and not based on full-load
conditions. The chiller must be Nationally Recognized Testing
Laboratory (NRTL) listed and use a minimum ozone-depleting
refrigerant. Use the AHRI net capacity value to determine the
chiller tons. A manufacturer’s specifcation sheet with the rated
kW/ton-IPLV or COP-IPLV must accompany the application. NPLV
ratings are NOT accepted.

Each unit effciency (0.01 kW/ton - IPLV) below the qualifying
effciency is an additional incentive per ton.
Unitary and Split Air Conditioning System and Air
Source Heat Pump
New unitary air conditioning units or air source heat pumps that
meet or exceed the qualifying cooling effciency indicated on the
HVAC worksheet table are eligible for an incentive. Both split
systems and single-package units are eligible.

Water-cooled systems, evaporative coolers and water source
heat pumps do not qualify under this measure, but may qualify for
other prescriptive incentives or a custom incentive.

The effciency of split systems is based on an AHRI reference
number. All packaged and split system cooling equipment must
meet AHRI standards (210/240, 320 or 340/360), be UL listed
and use a minimum ozone-depleting refrigerant. All required
effciencies are based on the Consortium for Energy Effciency
(CEE) high-effciency commercial air conditioning and heat pump
specifcations (cee1.org). A manufacturer’s specifcation sheet
indicating the system effciency must accompany the application.

Each unit effciency (1.0 SEER/EER/IEER) above the qualifying
effciency is an additional incentive per ton.
Variable Refrigerant Flow (VRF)
New VRF air conditioning units that meet or exceed the qualifying
cooling effciency indicated on the HVAC worksheet table are
eligible for an incentive.

All VRF multi-split air conditioning units must meet AHRI
standards (1230), be NRTL listed and utilize a minimum ozone-
depleting refrigerant (e.g., HCFC or HFC).

Ground Source Heat Pump
New ground source heat pumps that meet or exceed the
qualifying cooling effciency of 17 energy effciency ratio (EER)
are eligible for an incentive. Cooling EER is the effciency at
standard (ARI/ISO) conditions of 77°F entering water for closed-
loop models and 59°F entering water for open-loop systems. A
manufacturer’s specifcation sheet indicating the system effciency
for cooling must accompany the application. Unit cooling capacity
must be less than 12 tons.
Water Source Heat Pump
New water source heat pumps that meet or exceed the qualifying
cooling effciency of 17 energy effciency ratio (EER) are eligible
for an incentive. Cooling EER is the effciency at standard
(ARI/ISO) conditions of 86°F entering water. A manufacturer’s
specifcation sheet indicating the system effciency for cooling
must accompany the application. Unit cooling capacity must be
less than 12 tons.
Room Air Conditioner
Room air conditioning units are through-the-wall (or built-in) self-
contained units that are 2 tons or less.

Super Effcient Home Appliance (SEHA) Tier 1 and Tier 2 units
qualify for an incentive. Find the minimum requirements on the
CEE high-effciency room air conditioning webpage, cee1.org;
they also are provided in Table 1.
Package Terminal AC and Heat Pump Units
(PTAC/PTHP)
Package terminal air conditioners and heat pumps are through-
the-wall self contained units that are 2 tons (24,000 Btuh) or less.

Only units that have an EER greater than or equal to 13.08 -
(0.2556 x capacity in Btuh / 1,000) qualify for the incentive. All
EER values must be rated at 95°F outdoor dry-bulb temperature.
Hotel Guest Room Energy Management System
(Electric Heat/AC)
Pre-Approval Required
Incentives are available for sensors that control HVAC units for
individual hotel rooms. Key cards that indicate occupancy also
qualify. Sensors controlled by a front desk system are not eligible.

Automatic occupancy detectors or key cards must control
sensors. During unoccupied periods, the default setting for
controlled units should differ by at least fve degrees from the
operating set point. The incentive is per guest room controlled,
rather than per sensor, for multiroom suites. Replacement or
upgrades of existing occupancy-based controls are not eligible for
an incentive.
Page 24
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
HVAC SPECIFICATIONS
Variable Speed Drive on Chiller
Pre-Approval Required
Variable speed drives (VSDs) installed on existing chillers are eligible
for this incentive. New chillers with integrated VSDs are eligible under
the chiller incentive. VSDs on new equipment are not eligible. For
other VSD fan and pump projects, please use the prescriptive motors
and drives application. The installation of a VSD must accompany the
permanent removal or disabling of any throttling devices.
Centralized Energy Management System Control
Pre-Approval Required
Incentives are available for existing buildings that currently lack
digital automated HVAC controls or have outdated pneumatic
control systems with inoperable time control functions. Existing
HVAC control systems cannot have time-of-day scheduling
(including 7-day programmable thermostats). Upgrading an
obsolete EMS HVAC system with inoperable time clock functions
will be reviewed for incentive eligibility on a case-by-case basis.
Buildings upgrading existing digital EMS systems are not eligible
for prescriptive incentives.

HVAC EMS systems must be new and include:
• Central time control
• Real-time outside air damper positioning
• Graphic operator interface
• Whole-building real-time power and energy monitoring
capability
• Open-protocol architecture (shall consist of either LonTalk
(ANSI/CEA 709.1) or BACNet (ASHRAE/ANSI 135) protocol
being used between all controlled and controlling devices and
every node on the network)
• Web-based interface with PC-based controls
• Minimum setback space temperature of at least 8°F in both
heating and air condition mode
• Minimum setback period that exceeds 2,200 hours per year
• At least three enhanced control strategies (see Table 2)
If incorporated with demand control ventilation, real-time carbon-
dioxide monitoring at the operator interface is required.

Buildings with 2,000 to 50,000 square feet of conditioned space
are allowed under this prescriptive measure. The incentive is
capped at $10,000 per facility. Facilities measuring more than
50,000 square feet may be eligible under the custom program.

Pre-Approval Application MUST include:
• Energy models that are calibrated to within 5% of actual
electric bills
• Proposed EMS sequence of operations
• Scaled foor plan of building with controlled area highlighted
• Specifcations of proposed EMS system
• Estimated cost for proposed EMS system
• Utility billing data and/or building sub-metering data
demonstrating kWh and kW information
Air Side Economizer for AHUs and RTUs
Pre-Approval Required
Air side economizers bring cool outside air into buildings to reduce
the amount of mechanical cooling when outside air is colder than
the return air. Incentives are available for retroftting existing RTUs
or AHUs designed without economizers. The area served by the
air-handling system must be air-conditioned space. In order to
qualify, install new dampers and controllers on an existing system
and have a certifed professional conduct the proper calibration.
Occupancy Control for Toilet Room Exhaust
Retroft
Pre-Approval Required
This incentive is available for the installation of occupancy
sensors in toilet rooms to enable the exhaust fan only when the
room is occupied. The existing toilet room exhaust cannot be
automatically controlled by any other means, such as scheduled
by a building automation system, interlocked with HVAC night
setback or interlocked with existing lighting systems. The area
served by the controlled exhaust fan must be a conditioned space
(electric heated and/or air conditioned) or be taking its makeup air
from a conditioned space (electric heated and/or air conditioned).
The quantity of air exhausted from the toilet room must not be
considered to be any portion of the air quantity exhausted from
the building to meet the minimum outside air requirements by
local or state codes. The existing exhaust volume fow rate
must be a minimum of 75 cfm per toilet room fxture. A toilet
room fxture is defned as either a water closet (toilet) or urinal.
Manual timers controlling the exhaust system do not qualify for
this incentive. Take measurements to assure that the facility air
balance is appropriately maintained.
Window Film
Pre-Approval Required
This measure applies to window flm installed to reduce the
solar heat gain through the affected window. Windows with a
northern exposure (+/- 45 degree of true north) are not eligible.
The incentive is based on per square foot of non-north-facing
windows.
Film must meet one of the following requirements:
• For clear, single-pane glass, the solar heat gain coeffcient
(SHGC) of the window flm must be less than 0.39
• For clear, double-pane glass, the SHGC of the window flm
must be less than 0.25
• For applications that do not meet either of the previous
Page 25
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
HVAC SPECIFICATIONS
Table 1 Qualifying Room Air Conditioning Units
Size (Btuh) Minimum EER
< 8,000 (< 0.67 tons) 11.2
8,000-13,999 (0.68-1.17 tons) 11.3
14,000-19,999 (1.18-1.67 tons) 11.2
≥ 20,000 (≥ 1.68 tons) 9.8
Table 2 List of Enhanced Control Strategies for EMS
Chilled Water Temperature Setpoint Reset
Chiller of Compressor Sequencing
Condenser Water Temperature Setpoint Reset
Cooling Lockout on Outside Air Temperature (OSAT)
Deadband Control for Heating and Cooling
Demand Ventilation Control
Heating and Cooling Setpoint Overlap Restrictions
Cooling Tower Fan Speed Control
Cooling Tower Fan Staging
Dry-Bulb or Wet-Bulb Changeover Temperature Setpoint
Distribution Pump Selection/Sequencing
Distribution Pump Speed Control
Equipment Cycling
Evaporator Fan Speed Control (Groceries)
Floating Head Pressure Control (Groceries)
Head Pressure Controls (Groceries)
Heating Lockout on OSAT
Improved Outside Air Volume Control (Other Than Economizer)
Morning Warm-Up Cycle
Outside Air Damper Control
Optimal Start
Partial Light Shutoff
Static Pressure Reset
Summer/Winter Volume Change
Supply Air Temperature Reset
Unoccupied Temperature Setback
Variable Light Level Control
requirements, the flm must have a SHGC <= 0.47 and a visible
transmittance/solar heat gain coeffcient (VT/SHGC) ratio of 1.3
EC Motor for HVAC
This measure consists of the installation of electronically commutated
motors (ECMs) on a residential-sized hot-air furnace, split AC system
or an air handler serving both heating and cooling systems.
Demand Control Ventilation in Offces
Incentives are available for retroftting existing building ventilation
systems with controls that vary outside air volume based on
carbon dioxide (or other air quality parameter) levels to measure
occupancy. Buildings must have cooling systems and conditioned
spaces must remain between 65°F and 75°F during operating
hours. Systems must currently have fresh air requirements equal
or greater than 10 percent of supply air requirements. Install
carbon dioxide sensors in conjunction with fully functioning
economizers that have zone-level sensors for rooftop units and
return-system sensors for built-up systems. The incentive is
calculated per square foot of area controlled; a foor plan must
accompany the Final Application.

Demand Control Ventilation in Parking Garages
Incentives are available for the control of exhaust ventilation fans
for an existing enclosed parking garage using carbon monoxide
sensor and controls. The control system must vary the number
of fans on-line, the fan speed or fan blade pitch in response to
the carbon monoxide concentration as sensed at representative
locations in the garage. Systems must be capable of turning off
fan power during periods of low activity as compared to high-
activity periods. If code requires controlling garage ventilation
systems, the systems are not eligible for this incentive.

HVAC Occupancy Control
This incentive is available for adding occupancy sensors that
automatically switch an AC unit off for specifc spaces (i.e.,
classrooms, large conference rooms, multifunction rooms, etc.)
when these areas are not in use. The area served by the proposed
HVAC occupancy sensors must be conditioned by a dedicated
unitary AC or heat pump unit (i.e., the AC unit controlled by the
occupancy sensor must not serve any other spaces that require
conditioning when the occupancy sensor dictates unoccupied
mode). The installed occupancy control must be capable of turning
off the compressor and room fan during unoccupied mode. This
incentive is not available for spaces already controlled by outside
air demand control ventilation systems.
Page 26
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
MOTORS & DRIVES WORKSHEET
NEMA Premium
TM
Effciency Criteria—Qualifying Motors Exceed NEMA Premium
TM
Effciency
Horsepower
3600 RPM 1800 RPM 1200 RPM
Incentive
per Motor
Open Closed Open Closed Open Closed
1 77.0% 77.0% 85.5% 85.5% 82.5% 82.5% $8
1.5 84.0% 84.0% 86.5% 86.5% 86.5% 87.5% $10
2 85.5% 85.5% 86.5% 86.5% 87.5% 88.5% $13
3 85.5% 86.5% 89.5% 89.5% 88.5% 89.5% $20
5 86.5% 88.5% 89.5% 89.5% 89.5% 89.5% $25
7.5 88.5% 89.5% 91.0% 91.7% 90.2% 91.0% $40
10 89.5% 90.2% 91.7% 91.7% 91.7% 91.0% $45
15 90.2% 91.0% 93.0% 92.4% 91.7% 91.7% $60
20 91.0% 91.0% 93.0% 93.0% 92.4% 91.7% $75
25 91.7% 91.7% 93.6% 93.6% 93.0% 93.0% $80
30 91.7% 91.7% 94.1% 93.6% 93.6% 93.0% $90
40 92.4% 92.4% 94.1% 94.1% 94.1% 94.1% $100
50 93.0% 93.0% 94.5% 94.5% 94.1% 94.1% $120
60 93.6% 93.6% 95.0% 95.0% 94.5% 94.5% $130
75 93.6% 93.6% 95.0% 95.4% 94.5% 94.5% $140
100 93.6% 94.1% 95.4% 95.4% 95.0% 95.0% $190
125 94.1% 95.0% 95.4% 95.4% 95.0% 95.0% $238
150 94.1% 95.0% 95.8% 95.8% 95.4% 95.8% $285
200 95.0% 95.4% 95.8% 96.2% 95.4% 95.8% $380
250 95.0% 95.8% 95.8% 96.2% 95.4% 95.8% $475
Motor Make and
Model Number
Motor Size
(HP)
Motor
Speed
(rpm)
Motor
Type
Minimum
Qualifying
Motor
Effciency
Actual
Motor
Effciency
Motor
Quantity
Incentive
per Motor
Motor
Incentive
Total Motors Incentives







Page 27
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
VFD Application Options Include:
• Supply/Return Fan
• Chilled Water/Condenser Water Pump
• Hot Water Pump
• Cooling Tower Fan
• Other HVAC Motor
• Process Fan and Pump Motor
MOTORS & DRIVES WORKSHEET
Motor Size (HP) VFD Application Quantity Incentive per HP VFD Incentive
Total VFD Incentives
Link to Incentive Chart









Page 28
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
MOTORS & DRIVES SPECIFICATIONS
Effcient Motor
Incentives apply to three-phase AC induction motors, from 1
to 250 HP, of open drip-proof (open) and totally enclosed fan-
cooled (closed) classifcations. Rewound motors do not qualify.
Incentives cover the motor’s nominal full-load effciencies, tested
in accordance with IEEE (Institute of Electrical and Electronics
Engineers) Standard 112, method B, that exceed NEMA
Premium
TM
effciency levels.
The application must include the manufacturer’s performance data
sheet that shows motor type, motor horsepower, model number
and effciency rating. Customers should consider matching RPMs
of the existing pump or fan when installing energy-effcient motors
that inherently have higher speeds (less slip), which may affect
electric energy use.
Variable Speed Drive
Variable speed drives (VSDs) installed on existing HVAC or non-
HVAC (process) fans or pumps are eligible for this incentive. The
installation of a VSD must accompany the permanent removal
or disabling of any throttling devices such as inlet vanes, bypass
dampers and throttling valves.
Other requirements include:
• VSD project installations must result in energy savings
• Rated motor horsepower ≤ 200 HP (VSDs on motors > 200 HP may
qualify as a custom incentive.)
• Minimum of 1,200 operating hours per year
• The incentive applies only to VSDs installed with an automatic
feedback control technology
• For motors greater than 100 HP, applicant must provide
information regarding the equipment type and location, the
equipment on which the drive is installed, the daily and weekly
operating schedule, a description of the existing fow control
method, the proposed control strategy and, to the extent
possible, an estimate of the fraction of time the system will
operate at full load and 10-percent increments of partial loads
The incentive does NOT apply to:
• Redundant or back-up/standby motors expected to operate less
than 1,200 operating hours per year
• VSDs installed in place of variable pitch fans or VSDs installed
on forward-curve fans where inlet guide vanes are already
present. These projects may qualify for custom incentives, if
applicant can supply proof of savings through logged/metered
data.
The replacement of an existing VSD and multispeed motor •
VFDs on chillers
• New air compressors with VSDs
• Systems with manual controls or fxed-speed operation,
unless applicant supplies proof of kWh savings from logged or
measured data
Pool Pump VSD
Incentives apply to the installation of programmable variable-
speed or multiple-speed systems that vary swimming pool and
spa pump speed to minimum permitted fow rates, resulting in a
reduction in pumping power. The horsepower of the pump that is
replaced or the new pump, whichever is smaller, determines the
incentive.

VFD Application Incentive per HP
Variable Frequency or Variable Speed
Drive on Pump or Fan Motor, ≤ 200 HP
$60.00
Pool Pump VSD $100.00
Page 29
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
COMPRESSED AIR WORKSHEET
Pre-Approval Application required
Variable Speed Drive Air Compressor Incentives
Prescriptive VSD Incentives for Compressor ≤ 100 HP
Air
Compressor
Make and
Model
Nominal HP
Nominal
CFM
Control Type
Primary
Storage
(Gallons)
Annual
Operating
Hours
Incentive per HP
Total
Incentive
$100
$100
Added Compressor Storage on Load/No Load System
Air
Compressor
CFM
Nominal HP
Existing
Storage in
Gallons
Proposed Storage
in Gallons
Additional
Storage
Annual
Operating
Hours
Incentive per Gallon
Total
Incentive
$1.50
$1.50
Refrigerated Cycling Thermal Mass Air Dryer
Dryer Make and Model
Nominal
Compressor HP
Annual
Operating
Hours
Nominal
Dryer SCFM
Incentive
per SCFM
Total
Incentive
$1.50
$1.50
No Loss Condensate Drain
No Loss Condensate Drain
Nominal HP
System
Annual
Operating
Hours
System
Operating
PSI
Flow Control
Method
Type of
Drain
Replaced
Existing
Drain Orifce
Diameter (in.)
Quantity
of Drains
Incentive
per
Drain
Total
Incentive
$50.00
$50.00
0
0


Page 30
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Low-Pressure Drop Filter
Filter Make
and Model
Nominal HP
Nominal
SCFM
Filter
Size
(scfm)
Installed
Filter
Rated
Filter PSI
Loss
Annual
Operating
Hours
Incentive per SCFM
Total
Incentive
$0.80
$0.80
Compressed Air Engineered Nozzle
Nozzle Make and Model
Nominal
Nozzle
Size
SCFM Rating at
80 PSI
Annual
Operating
Hours
Quantity of
Nozzles
Incentive per
Nozzle
Total
Incentive
$25.00
$25.00
Compressed Air Leak Repair 24-Hour Operation
To qualify for the air leaks repair incentive, this measure must be combined with another compressed air measure
Compressor
Quantity
Nominal
Compressor
HP
Nominal
SCFM
System Operating PSI
Annual
Operating
Hours
Identifed and
Repaired Air Leaks
(SCFM)
Incentive
per SCFM
Total
Incentive
$20.00
$20.00
Compressed Air Leak Repair Non-24-Hour Operation
Compressor
Quantity
Nominal
Compressor
HP
Nominal
SCFM
System Operating PSI
Annual
Operating
Hours
Identifed and
Repaired Air Leaks
(SCFM)
Incentive
per SCFM
Total
Incentive
$12.00
$12.00
Total Compressed Air Incentives
COMPRESSED AIR WORKSHEET
Pre-Approval Application required




Page 31
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
CUSTOM COMPRESSED AIR SYSTEM DETAILS
Use this form or supply similar information for custom compressed air applications. Use the custom worksheet for
determining incentives and for specifcations. List all of the air compressors and system components currently located at
your facility.
Air Compressor
Equipment ID/
Manufacturer
HP Compressor Type Capacity Control Mode
Air or
Liquid
Cooled
Back-up
Age
(Years)
Annual
Operating
Hours
Dryer
Equipment ID/
Manufacturer
Associated Compressor ID Type
Status Age
(Years)
Storage
Location Size (Gallons) Wet or Dry















Page 32
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Describe the operating schedule used for your facility’s
compressed air system.
______________________________________________
______________________________________________
______________________________________________
Is a ˆ management system or ˆ manual procedure in place to
shut off compressors when not in use?

If so, is the system properly tuned?
ˆ Yes ˆ No
Describe the facility’s compressed air system controls.
ˆ Cascading with no control
ˆ Central control system
ˆ Manual control
Are you interested in optimizing your ˆ compressed air control
strategy or ˆ usage?
Does your compressed air system trend data pressure or fow?
ˆ Yes ˆ No

Describe your facility’s compressed air system leak management
or maintenance schedule.
______________________________________________

When was the most recent leak detection survey completed?
Date____________
What is the system pressure?
Does your system have trouble maintaining this pressure or
experience signifcant fuctuations at end-use points?
ˆ Yes ˆ No
What is the approximate system capacity?
Is air storage located near large end-use items?
ˆ Yes ˆ No

What is the dry air-quality requirement?
_____________________________________________
Is there a dew point requirement?
ˆ Yes ˆ No

What is the compressed air system’s highest
pressure demand?
Summarize the major/minor compressed air end-use loads
below.
End Use
Name
Quantity
Pressure
Range
(psig)
Flow
Operation
(CFM)
Scheduled
Hours and
Days of
Operation
Air Pressure
Regulators
Air Actuators
Air Motors
Air
Diaphragm
Pumps
Blow-Off
Applications
_____ psig
_____ CFM
_____ psig
CUSTOM COMPRESSED AIR SYSTEM DETAILS
Page 33
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
COMPRESSED AIR SPECIFICATIONS
Variable Speed Drive Air Compressor
Only new air compressors whose rated horsepower (HP) is less
than or equal to 100 HP qualify for this incentive. Air compressors
larger than 100 HP may qualify for a custom incentive. The new
VSD air compressor must replace an existing constant-speed
compressor, having an equal or higher HP rating and annual
operating hours of at least 1,200 hours. Back-up and redundant
air compressors, and air compressors on multiple-compressor
systems are not eligible for this measure.
System and demand conditions requiring the air compressor to
be loaded constantly above eighty percent (80%) or constantly
loaded below thirty percent (30%) are not eligible for this
measure. These operating conditions will not realize savings from
a VFD-controlled compressor. This incentive cannot be combined
with the VFD incentive.

Added Compressor Storage on Load/No
Load System
Air compressor systems rated at 300 HP or less are eligible for
prescriptive incentives. Larger air compressor systems may
qualify for custom incentives.
Eligible air receiver tanks must meet or exceed the minimum
tank size of fve gallons of storage per volume fow rate (SCFM)
compressor output. The existing air receiver capacity must be less
than or equal to two gallons per SCFM compressor capacity.
The air compressor supplying the receiver must have load/no
load controls. Both new and retroft (additional or replacement)
receivers are eligible for this incentive. Compressed air systems
with VFD-controlled compressors or variable displacement are not
eligible.
Submit with application
• HP rating of the air compressor system
• Rated volume fow rate (SCFM) of the air compressor system
• Existing storage capacity per SCFM
• Proposed storage capacity per SCFM

Refrigerated Cycling Thermal Mass Air Dryer
Only compressed air dryer capacities equal to or less than 600
SCFM are eligible for the prescriptive incentive; dryers with larger
capacities are handled on a custom basis.
The proposed compressed air dryer must run exclusively in
cycling mode—it cannot be equipped with a feature that allows it
to run in a non-cycling mode.
Submit with application (to the best of ability)
• HP rating of the air compressor system serviced by the
existing and proposed dryer
• Rated fow rate (SCFM) of existing and proposed dryers
• Rated and maximum operating fow rate of the compressor
• Daily, weekly and annual operating schedule
• Detailed load profle or percentage of time the compressor will
operate at full load and 10% increments of partial load/fow

No Loss Condensate Drain
This prescriptive measure is eligible for compressed air systems
whose rated horse power (HP) is between 50 and 300 HP.

Both new and retroft (additional or replacement) no loss
condensate drains on compressed air systems are eligible. The
existing condensate drain must be a timed drain or manually
opened drain.

The replacement drain must be no loss—it must continuously
measure the presence of condensate and purge it only when
necessary and only long enough to prevent the unintentional
purging of compressed air. Manual drains, timed drains and
electronic solenoid valve drains are not eligible.
Eligible compressed air systems must have a wet air receiver
storage tank greater than two gallons of storage per volume
fow rate (SCFM) compressor output. Ineligible compressed air
systems include equipment that is not in service, redundant or
back-up systems.
Low-Pressure Drop Filter
Only flters installed on compressor systems rated from 25 HP to
300 HP with a rated capacity ≤ 500 SCFM qualify. The flter must:
• Be the deep-bed “mist eliminator” style
• Have a pressure loss at rated fow ≤ 1 psi when new and ≤ 3
psi at element change
• Have particulate fltration that is 100% at ≥ 3.0 microns and at
least 99.98% at 0.1 to 3.0 microns
• Be rated for ≤ 5 PPM liquid carryover
• Have a flter element life greater than or equal to fve years

Compressed Air Engineered Nozzle
The engineered nozzle must replace simple open pipe/tube
assemblies connected to a compressed air system. The nozzle
usage must be 2,000 hours or more per year. Engineered nozzles
must be between
1
/8" and ½" in diameter. At 80 psi, the fow rate
through the air nozzle or air jet should be equal to or less than the
values below:

Qualifying SCFM Ratings
Size (inch) 1/8 1/4 3/8 1/2
SCFM 10 17 18 18
Page 34
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Compressed Air Leak Repair (24-Hour and Non-
24-Hour Operation)
To qualify for the air leaks repair incentive, this measure must be
combined with another compressed air measure. To qualify for the
24-hour operation incentive, the air compressors supplying air to
the leaks must run more than 7,000 hours per year. To quality for
the non-24-hour incentive, the air compressor must run at least
1,200 hours per year. The local pressure of the compressed air
leak must be above 65 psig. The application must include the
decibel readings recorded with an ultrasonic leak detector for
all leaks before the repair work. Use an ultrasonic leak detector
manufacturer’s companion tool to obtain the CFM values of the
leaks; convert from decibel readings using appropriate pressure
level at which the compressed air is leaking. Single leaks larger
than 15 CFM are eligible for a 15 CFM maximum.
COMPRESSED AIR SPECIFICATIONS
Page 35
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
REFRIGERATION/FOOD SERVICE WORKSHEET
Refrigeration Measures
Measure Incentive Unit Quantity
Incentive/
Unit
Incentive
Anti-Sweat Heater Control Linear Foot of Case $25.00
EC Motor for Walk-In Cooler and Freezer Motor $50.00
EC Motor for Reach-In Refrigerator and Freezer Case Motor $35.00
Evaporator Fan Control—Non-EC Motor Motor $60.00
Evaporator Fan Control—EC Motor Motor $60.00
Cooler Control for Unitary Reach-In Cooler Unit $30.00
Floating Head Pressure Control HP $35.00
Oversized Condenser for Refrigeration Ton $10.00
LED Refrigeration Case Lighting in Freezer and Cooler With Doors Linear Foot of Case $12.00
LED Refrigeration Case Lighting in Open Display Case Linear Foot of Case $10.00
Lighting Controls for Freezer and Cooler With Doors Linear Foot of Case $10.00
Lighting Controls for Open Display Case Linear Foot of Case $8.00
New Doors on Open Refrigerated Case, Medium Temperature Linear Foot of Case $250.00
New Doors on Open Refrigerated Case, Low Temperature Linear Foot of Case $300.00
ENERGY STAR
®
Solid-Door Freezer Unit $150.00
ENERGY STAR
®
Glass-Door Freezer Unit $400.00
ENERGY STAR
®
Solid-Door Refrigerator Unit $100.00
ENERGY STAR
®
Glass Door Refrigerator Unit $75.00
Total Refrigeration Incentives
Food Service and Ice Maker Measures
Measure Incentive Unit Quantity
Incentive/
Unit
Incentive
Pre-Rinse Sprayer (<1.6 gpm, Electric Water Heating) Unit $25.00
ENERGY STAR
®
Steam Cooker Unit $400.00
Combination Oven Unit $1,500.00
ENERGY STAR
®
Hot Holding Cabinet Unit $300.00
Ice Maker—101-400 lbs/24 hrs Unit $100.00
Ice Maker—401-1,000 lbs/24 hrs Unit $150.00
Ice Maker > 1,001 lbs/24 hrs Unit $150.00
Total Food Service and Ice Maker Incentives
Page 36
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Demand Control Ventilation for Kitchen Exhaust Hood
Application Description New or Retroft Size in HP
Number
Installed
Incentive per HP Incentive
Total Demand Control Ventilation Incentives
Total Refrigeration/Food Service Incentives
REFRIGERATION/FOOD SERVICE WORKSHEET
Link to Incentive Chart



Page 37
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
Anti-Sweat Heater Control
To qualify for this measure, install a device that senses the relative
humidity in the air outside of the display case and reduces or turns
off the glass door (if applicable) and frame anti-sweat heaters at
low-humidity conditions.
Technologies that can turn off anti-sweat heaters based on sensing
condensation (on the inner glass pane) also qualify. Incentive is
based on the total horizontal linear footage of the case.
Electronically Commutated (EC) Evaporator Fan
Motor (Refrigerated and Freezer Case or Walk-In)
This measure is applicable to the replacement of an existing
standard-effciency shaded-pole evaporator fan motor in
refrigerated display cases or fan-coil in walk-ins. The replacement
unit must be an electronically commutated motor (ECM). New
walk-ins with integrated ECM do not qualify.
Evaporator Fan Control (Non-EC Motor)
This measure applies to the installation of controls in medium-
temperature walk-in coolers. The controller reduces airfow of the
evaporator fans when there is no refrigerant fow. The existing fan
must control a minimum of
1
/20 HP and operate continuously at
full speed. It also must reduce fan motor power by at least 75%
during the off cycle.
This measure is not applicable if any of the following
conditions apply:
1. Compressor runs continuously on high-duty cycle
2. Evaporator fan does not run continuously at full speed
3. Evaporator fan motor runs on poly-phase power
4. Evaporator fan motor is not shaded-pole or permanent split
capacitor (PSC)
5. Evaporator does not use off-cycle or time-off defrost
Evaporator Fan Control (EC Motor)
This measure applies to the installation of controls in medium-
temperature walk-in coolers. The controller reduces airfow in the
evaporator fans when there is no refrigerant fow. The measure
must control a minimum of
1
/20 HP, if fans operate continuously at
full speed. The measure also must reduce fan motor power by at
least 75% during the off cycle and be installed on an EC motor.
This measure is not applicable if any of the following
conditions apply:
1. Compressor runs continuously on high-duty cycle
2. Evaporator fan does not run continuously at full speed
3. Evaporator fan motor runs on poly-phase power
4. Evaporator does not use off-cycle or time-off defrost
Cooler Control for Unitary Reach-In Cooler
The incentive applies to the installation of controls with passive
infrared occupancy sensors that turn off fuorescent lights and
other refrigerated systems (containing only non-perishable
beverages) when the surrounding area is unoccupied for 15
minutes or longer. Stand-alone reach-in coolers with or without
doors are eligible.
Floating Head Pressure Control
This measure applies to the installation of a head pressure control
valve (food-back control valve) to lower minimum condensing
head pressure from a fxed position (180 psig for R-22) to a
saturated pressure equivalent to 70°F or less. Install either a
balanced-port or electronic expansion valve sized to meet the
load requirement at a 70° condensing temperature and vary head
pressure based on outdoor air temperature. Alternatively, install
a device to supplement the refrigeration feed to each evaporator
attached to the condenser that is reducing head pressure.
Compressor must be 1 HP or larger.
Oversized Condenser for Refrigeration
Incentives are available for the design and installation of
oversized condensers for multiplex refrigeration systems. A
design reducing the approach (difference in existing refrigerant
and ambient dry build temperature) lowers the head pressure
and conserves compressor horsepower. The new condenser
must result in 85 Btu/hr of heat rejection per watt of fan power
for air-cooled condensers. For evaporative cooled equipment, a
minimum of 195 Btu/h/Watt is required.
LED Refrigeration Case Lighting (Open and With
Doors)
This measure consists of replacing fuorescent refrigerated
case lighting with light emitting diode (LED) source illumination.
Typically, pre-fabricated LED light bars and LED driver units
replace fuorescent lamps, ballasts and associated hardware. LED
refrigerated case lighting must be DesignLights Consortium (DLC)
listed and included on the DLC Qualifed Products List,
designlights.org, or applicant must provide documentation to meet
these standards. The incentive is per linear foot of case.
Lighting Control for Cases (Open and With Doors)
Passive infrared, ultrasonic detectors or fxture-integrated sensors
are eligible. The incentive is per linear foot of case.
New Door on Open Refrigerated Case, Medium
Temperature
This measure applies to the installation of new glass doors on
existing open, vertical (or multi-deck), medium-temperature (MT)
display cases or for replacing existing, open, vertical (or multi-
deck) display cases with new reach-in, glass-door display cases.
The air temperature inside the cases ranges from 33°F to 50°F.
REFRIGERATION/FOOD SERVICE SPECIFICATIONS
Page 38
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
The case’s horizontal linear length determines the incentive. The
length of a new case determines incentive calculations, unless it
is longer than the original case.
New Door on Open Refrigerated Case, Low
Temperature
This measure covers the installation of new glass doors on
existing open, vertical (or multi-deck), low-temperature (LT)
display cases or the replacement of existing, open, vertical (or
multi-deck) display cases with new reach-in, glass-door display
cases. The air temperature inside the cases ranges from 0°F
to 33°F. The incentive is based on the case’s horizontal, linear
length. Incentives for the installation of a new case are based on
its length, unless it is longer than the original case.
ENERGY STAR
®
Solid- and Glass-Door Freezer
and Refrigerator
Must meet ENERGY STAR Version 2.0 specifcation. Cases with
remote refrigeration systems are not eligible.
Pre-Rinse Sprayer (Electric Water Heating)
The incentive covers pre-rinse spray valves with a fow rate of 1.6
gallons per minute or less, and with a cleanability performance
of 26 seconds per plate or less, based on American Society for
Testing and Materials (ASTM) standard test method. The measure
is only applicable for systems with electric storage water heaters.
ENERGY STAR
®
Steam Cooker
The commercial steam cooker shall have a tested heavy-load
potato-cooking energy effciency of > 50% utilizing ASTM
Standard F1484, and be ENERGY STAR
®
listed.
Combination Oven
The qualifying combination oven shall:
• Meet or exceed a heavy-load cooking energy effciency of
> 60% utilizing ASTM Standard F1639 or ASTM standard
F2861
• Have a steam-cooking energy effciency of ≥ 50%
• Have a convection-cooking energy effciency of ≥ 70%
ENERGY STAR
®
Hot Holding Cabinet
The installed hot holding cabinet must be ENERGY STAR
®

listed. This measure does not include cook-and-hold equipment.
All measures apply to fully insulated electric hot-food holding
cabinets with solid doors in full, three-quarter and half sizes
respectively. Qualifying cabinets shall not exceed the maximum
idle energy rate of 20 watts per cubic foot, in accordance with the
ASTM Standard F2140 test method as stated by ENERGY STAR.
Cook-and-hold equipment and units < half size may be eligible as
a custom incentive.
High-Effciency Ice Maker
The incentive covers ice machines that generate 60 grams
(2 oz.) or lighter ice cubes, faked, crushed or fragmented ice.
Only air-cooled machines qualify (self-contained, ice-making
heads or remote condensing). The machine must have a
minimum capacity of 101 lbs. of ice per 24-hour period (per
day). The minimum effciency required is per ENERGY STAR
®

or Consortium for Energy Effciency (CEE) Tier 2. Find qualifying
model numbers at energystar.gov or cee1.org. A manufacturer’s
specifcation sheet that shows rating in accordance to ARI
standard 810 must accompany the application.
Demand Control Ventilation for Kitchen Exhaust
Hood
This incentive recognizes the installation of a control system that
varies the exhaust rate of kitchen ventilation (exhaust and/or
makeup air fans) based on the energy and effuent output from
the cooking appliances (i.e., the more heat and smoke/vapors
generated, the more ventilation needed). Incentive is based on
exhaust fan HP only (not makeup air fan). VSDs on the makeup
air fan do not qualify for an additional incentive.

This involves:
• Installing a temperature sensor in the hood exhaust collar and/
or an optic sensor on the end of the hood.
• Installing a variable speed drive on the exhaust fan that varies
the rate of exhaust to what is needed.
• Installing a variable speed drive on the makeup air fan unit, if
applicable.
REFRIGERATION/FOOD SERVICE SPECIFICATIONS
Demand Control Ventilation for Kitchen Exhaust Hood
New Hood $300 per Exhaust Fan HP
Retroft Hood $400 per Exhaust Fan HP
Page 39
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
AGRICULTURE & MISCELLANEOUS WORKSHEET
Agriculture Measures
Measure Incentive Unit Quantity Incentive/Unit Incentive
VSD on Dairy Milking
Pump
Vacuum Pump
HP $120.00
100 Gallons of Daily
Milk Production
$10.00
Transfer Pump
Low-Pressure Sprinkler Nozzle Nozzle $0.50
Sprinkler to Drip Irrigation Acre $35.00
Block Heater Timer Unit $25.00
Total Agriculture Incentives
Miscellaneous Measures
Measure Incentive Unit Quantity Incentive/Unit Incentive
Industrial High Frequency Battery Charger Unit $225.00
Beverage Machine Control Unit $100.00
Snack Machine Control Unit $30.00
ENERGY STAR
®
Refrigerated Vending
Machine Refurbishment Kit
Machine $50.00
High-Effciency Electric Hot Water Heater Unit $35.00
ENERGY STAR
®
Heat Pump
Hot Water Heater
Unit $120.00
ENERGY STAR
®
Commercial Clothes Washer Unit $45.00
Intelligent Surge Protector Unit $1.00
Network Power Management Software Unit $10.00
Plug Load Occupancy Sensor¹ Unit $15.00
Total Miscellaneous Incentives
Appliance Recycling Program
Measure Incentive Unit Quantity Incentive /Unit Incentive
Refrigerator Unit $50.00
Freezer Unit $50.00
Total Appliance Recycling Incentives

¹Plug load sensors must control equipment in offces or cubicles, including lighting, shared copiers and/or printers, that use electricity.
Page 40
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
AGRICULTURE & MISCELLANEOUS SPECIFICATIONS
VSD on Dairy Milking Pump
To qualify for the vacuum pump measure, the existing milking
pump must operate at a constant speed.
Submit with application
• Nominal HP of pump
• Number of milking units controlled by pump/VSD
• Estimated hours per day milking pump operates
• Estimated days per year milking pump operates
Only transfer pumps used in conjunction with a once-through
well-water-to-milk pre-cooler qualify; furthermore, existing transfer
pumps must operate at a constant speed.
Low-Pressure Sprinkler Nozzle
The applicant must convert from a one-to-one high-pressure (50
psi or greater at the sprinkler head) sprinkler system nozzle to
a low-pressure sprinkler nozzle. Both permanent (solid set) and
portable (hand-move) sprinkler system nozzles are applicable
for incentives. The incentive application must include an invoice
indicating the number of nozzles.
Complete a pumping plant analysis after the replacement to
ensure a specifed overall pumping effciency of 45% or above.
Sprinkler to Drip Irrigation
The applicant must convert from a high-pressure, impact-type
sprinkler irrigation system (50 psi or greater at the sprinkler head)
to a micro-irrigation system. Irrigation conversion incentives are
not applicable to new plantings of vineyards or orchards, unless
a vineyard or orchard was the previous crop on the feld receiving
the irrigation system conversion. Drip tape systems are not
applicable.
The incentive application must include an assessor’s parcel map
or other documentation to verify acreage.
Block Heater Timer
The incentivized block heater timer must have a timer and
thermostat control and previously have been controlled manually.
The heater must operate at least 45 days per year and have a
rating of at least 250W.
Industrial High Frequency Battery Charger
New three-phase high frequency chargers shall have a minimum
power conversion effciency of 92% and a minimum 8-hour shift
operation for fve days per week. The new battery charger must
replace either a ferroresonant or silicon controlled rectifer (SCR)
charger. This measure is only applicable to battery charging for
forklifts, golf carts and other electric vehicles.
Beverage and Snack Machine Controls
Refrigerated beverage-vending machines that contain only non-
perishable bottled and canned beverages qualify. Non-refrigerated
snack machines qualify.
The controller for both types of systems must include a passive
infrared occupancy sensor to turn off fuorescent lights and
other vending machine systems when the surrounding area is
unoccupied for 15 minutes or longer. For the beverage machine,
the control logic should power up the machine at 2-hour intervals
to maintain product temperature and provide compressor
protection.
ENERGY STAR
®
Refrigerated Vending Machine
Refurbishment Kit
This incentive covers the installation of ENERGY STAR Tier
II refurbishment kits to upgrade a machine that does not meet
ENERGY STAR Tier II requirements. Kits must meet the ENERGY
STAR Program Requirements for Refrigerated Beverage Vending
Machines Eligibility Criteria Version 2.0, Tier II, which uses
ASHRAE 32.1-2004.
High-Effciency Electric Hot Water Heater
New hot water heater must be ≥ 40 gallons and have an energy
factor ≥ 0.93.
ENERGY STAR
®
Heat Pump Hot Water Heater
Must meet ENERGY STAR criteria with an energy factor ≥ 2.0 and
frst hour rating (FHR) ≥ 50 gallons per hour.
ENERGY STAR
®
Commercial Clothes Washer
Incentives are available for high-effciency commercial clothes
washers, which wash more clothes per load than standard
clothes washers and use less water and energy. Qualifed clothes
washers must meet a minimum effciency of Consortium of
Electric Engineers (CEE)
©
Tier 2, with a modifed energy factor
(MEF) ≥ 2.00 and a water factor (WF) ≤ 6.00.
Intelligent Surge Protector
This incentive applies to surge protectors (power strips) with built-
in plug-load detection and control capabilities. The surge protector
must include at least one uncontrolled socket, which would be a
primary device (usually a computer). Turning the primary device
on or off subsequently will turn the associated controlled devices
in the power strip on or off (i.e., printers, monitors, etc.). The
intelligent power strip also may contain sockets for devices that
require a constant supply of power. These will not be affected by
the “control” device.
Network Power Management Software
PC management software enables network administrators to
override computer “on,” “standby,” “sleep” and “off” power modes
Page 41
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
and put all networked computers on low power settings during
appropriate hours.
Installed software must:
• Automatically control the power settings of networked personal
computers at the server level
• Be capable of managing power consumption for each PC
• Be capable of reporting energy saving results
Submit a report generated by the network energy management
software verifying the number of PCs controlled by the system
with the application.
Plug Load Occupancy Sensor
This incentive covers the installation of passive infrared and/
or ultrasonic detectors for plug load offce equipment. Plug load
sensors must control equipment in offces or cubicles, including
lighting, shared copiers and/or printers, that use electricity.
Appliance Recycling
• You must be a current AEP Ohio customer residing in Ohio.
• The refrigerator or freezer must be between 10 and 30 cubic
feet in size.
• The refrigerator or freezer must be clean, empty, defrosted and
in working condition.
• This program is limited to two large appliances (refrigerators
and/or freezers) per customer per year.
• An adult, 18 years of age or older, must be present to sign and
release the unit at the time of pickup.
• The unit needs to be plugged in and running on the day of
pickup.
• Recycling appliance must be disconnected from waterlines
prior to the pickup crew’s arrival.
• You must provide clear and safe access to your appliances for
the removal team. They will not risk injury or be able to move
personal effects or modify your home (e.g., remove door or
railings) to remove the unit(s).
AGRICULTURE & MISCELLANEOUS SPECIFICATIONS
Page 42
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
TRANSFORMER WORKSHEET
NEMA Premium
TM
Effciency Transformers—Minimum Qualifying Effciencies and Incentive Rates
Transformer
Make/Model
Phase
Unit
Size in
kVA
Minimum
Required
Effciency
Effciency of
Unit Installed
# of Units
Installed
Base Incentive
per Unit
Effciency
Bonus Per
Unit
1
Incentive
Total Transformer Incentives
SPECIFICATIONS
Single-Phase and Three-Phase Transformers
Single- or three-phase low-voltage dry-type distribution
transformers meeting or exceeding the NEMA Premium
TM

effciency requirements at 35% load are eligible for incentives.
Find information on the NEMA Premium effciency program at
nema.org/technical/pages/nema-premium-effciency-transformers-
program.aspx.
Low-voltage dry-type distribution transformer have all of the
following characteristics:
• Input voltage of 600 volts or less
• Air-cooled
• Does not use oil as a coolant
The following devices are not eligible for this incentive, but may be
eligible for custom incentives:
• Liquid and medium-voltage transformers
• Non-distribution transformers, such as transformers with
multiple voltage taps where the highest is at least 20% more
than the lowest
• Transformers designed for use in special-purpose
applications, such as drive transformers, rectifer transformers,
auto-transformers, impedance transformers, regulating
transformers, sealed and non-ventilating transformers,
machine tool transformers, welding transformers, grounding
transformers and testing transformers
• Utility-owned transformers
Single Phase
kVA
NEMA Premium
Effciency @
35% Load
Base
Incentive
Effciency
Bonus Level¹
15 98.39% $60 $1.00
25 98.60% $100 $1.75
37.5 98.74% $150 $2.75
50 98.81% $150 $3.00
75 98.95% $225 $5.00
100 99.02% $300 $7.25
167 99.09% $340 $8.75
250 99.16% $500 $14.00
333 99.23% $670 $20.00
Three Phase
15 97.90% $60 $0.75
30 98.25% $120 $1.75
45 98.39% $135 $2.00
75 98.60% $220 $3.75
112.5 98.74% $240 $4.50
150 98.81% $300 $6.00
225 98.95% $450 $10.00
300 99.02% $500 $12.00
500 99.09% $550 $14.25
750 99.16% $750 $21.00
1000 99.23% $1,000 $30.25
1
Effciency bonus is paid for an effciency rating above the qualifying effciency. The
bonus is per 0.01% effciency improvement over NEMA Premium.





Page 43
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
ENERGY STAR
®
AC-OUTPUT UNINTERRUPTIBLE POWER SUPPLY (UPS)
FOR NON-DATA CENTERS WORKSHEET
SPECIFICATIONS
Single-Normal-Mode AC-Output UPS
Minimum Average Effciency Requirements¹
Size in Output kW VFD VI VFI
P ≤ 1.5 kW 0.967
0.0099 x ln(P) +
0.815
1.5 kW < P ≤ 10 kW 0.970 0.967
Single-Normal-Mode AC-Output UPS
Incentive per Output kW
Size in Output kW VFD VI VFI
P ≤ 1.5 kW $4.50 $7.25 $12.50
1.5 kW < P ≤ 10 kW $4.50 $4.75 $5.00
Multiple-Normal-Mode AC-Output UPS
Incentive per Output kW
Size in Output kW VFD/VI VFD/VFI
1.5 kW < P ≤ 10 kW $5.50 $6.50
UPS Make/Model AC Output Mode Input Dependency
Characteristics
Quantity UPS Size in
Output kW
Effciency of
Unit Installed
Incentive Total
Incentive
Total Uninterruptible Power Supply Incentives
¹Minimum Average Effciency Requirements: For multiple-normal-mode AC-output units, the rated average effciency must be greater than the minimum effciency levels
expressed in the table above for the lowest input dependency characteristic. For example, a VFD/VI unit must meet the VI requirements and a VFD/VFI must meet the VFI
requirements.
ENERGY STAR AC-Output UPS
This incentive applies to the installation of ENERGY STAR
qualifed AC-output UPS systems in non-data centers. Data centers
should contact the AEP Ohio Business Incentives Program team for
referral to the AEP Ohio Data Center Program.
The installed UPS system must meet or exceed the average
loading-adjusted effciency values required by the ENERGY STAR
UPS program, reproduced in the worksheet table. Units over
10 kW are not eligible for a prescriptive incentive, but may be
eligible for a custom data center incentive offered through AEP or
for the self-direct program.

Eligible products include:
• Consumer UPS systems intended to protect desktop
computers and related peripherals
• Commercial UPS systems intended to protect small business
and branch offce communication technology equipment such
as servers, network switches/routers and small storage arrays
Contact the AEP Ohio Business Incentives Program team with
questions regarding your project’s eligibility for an incentive.




Page 44
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
ENERGY STAR
®
AC-OUTPUT UNINTERRUPTIBLE POWER SUPPLY (UPS)
FOR NON-DATA CENTERS GLOSSARY
Variable and Frequency Dependent (VFD): Also known as
passive, standby, offine or standby power supply (SPS), VFDs
may be referred to as the UPS with the highest input dependency.
This designation occurs because output voltage is dependent on
changes in AC input voltage and frequency, and is not intended
to provide additional corrective functions. VFDs provide basic
protection to the load against power outage.
Voltage Independent (VI): Also known as a line interactive UPS,
a VI protects the load from power outages, much like a VFD. It
also protects the load from the continuous application of under
and over voltage, typically from 5 to 30 minutes. A VI has a lower
input dependency than a VFD, but a higher input dependency
than a VFI.
Voltage and Frequency Independent (VFI): Also know as double
conversion, or online, a VFI has the lowest input dependency of
the three UPS types. It is similar to VI systems in that it protects
the load from power outages, under and over voltages, and
frequency variations. It also protects the load from the adverse
effects of these variations without depleting the stored energy
source. VFI systems can provide an electrical frewall between the
input power and the sensitive electronic equipment. While VFDs
and VIs provide flters of the input utility power, a VFI functions as
a layer of insulation from power-quality issues.
Single-Normal-Mode: A UPS that operates in only one input
dependency mode (i.e., VFD, VI or VFI mode).
Multiple-Normal-Mode: Also known as hybrid or double
conversion on demand, this type of UPS can operate in more
than one input dependency mode. One mode is always VFD; the
other mode is either VI or VFI. For example, a UPS operates as a
VFD when the power conditions are within certain setpoints and
switches over to a higher input dependency mode when the power
conditions are outside of that pre-set window.
Minimum Average Effciency: The average effciency of the
UPS, based on standardized loadings, which is calculated using
the equation below:
Eff
AVG
= t
25%
x Eff
25%
+ t
50%
x Eff
50%
+ t
75%
x Eff
75%
+ t
100%
x Eff
100%
Where:
• Eff
AVG
is the average loading-adjusted effciency.
• t
n%
is the proportion of time spent at the particular n% of the
reference test load, as specifed in the loading assumptions
provided in the following table.
• Eff
n%
is the effciency at the particular n% of the reference test
load, as measured according to the ENERGY STAR test method.
Output Power
Input
Dependency
Proportion of Time Spent
at Specifed Proportion of
Reference Test Load, t
n%
25% 50% 75% 100%
p<1.5 kw
VFD 0.2 0.2 0.3 0.3
VI or VFI 0 0.3 0.4 0.3
1.5 kW < 10 kW
VFD, VI or
VFI
0 0.3 0.4 0.3
Page 45
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
CUSTOM WORKSHEET
Prior to submitting application, please contact the AEP Ohio Business Incentives Program staff.
Custom Program Incentives
Incentive Levels First Year kWh Savings $0.08/frst year kWh
Payback Period
Maximum 7 years
Minimum 1 year¹
Caps % of Total Incremental Cost 50%
Measure Description
kWh Savings
$/kWh
Subtotal
Measure Category
Before Retroft After Retroft kW Demand Reduction
2
$0.08
Measure Cost
3
Customer’s Cost per kWh
Measure Life
Annual Operating Hours Simple Payback
Measure Description
kWh Savings
$/kWh
Subtotal
Measure Category
Before Retroft After Retroft kW Demand Reduction
2
$0.08
Measure Cost
3
Customer’s Cost per kWh
Measure Life
Annual Operating Hours Simple Payback
¹The project simple payback prior to the incentive payment generally should be greater than one year and less than seven years, or pass cost effectiveness test(s) determined
by AEP Ohio to qualify for an incentive. ²Eligible projects must result from a permanent facility improvement that results in a permanent reduction in electrical (kWh) energy
usage due to an improvement in system efficiency. PJM Peak Hours are defined as the time between June 1 and August 31 on weekdays and non-holidays, between the hours
of 2:00 p.m. and 6:00 p.m. Eastern Standard Time. ³Measure Cost is the cost to implement rebated effciency measures less all costs incurred to achieve other project benefts.
The Measure Cost may be the increment required to deliver an effciency improvement over the base case effciency.
4
Total custom incentives may not exceed 50% of the total
incremental cost.
Calculation Methodology
Please select the calculation methodology used to estimate the savings for this project
ˆ Bin Analysis
ˆ Billing Data
ˆ Modeling Software
ˆ Engineering Formulae
ˆ Load Profles
ˆ Pre & Post M&V
Total Custom Project Cost
Total Custom Incentives
4

$ 0.00

$ 0.00
$ 0.00
$ 0.00
Page 46
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
CUSTOM SPECIFICATIONS
Pre-Approval Application required.
Qualifcations for Custom Projects
Custom project incentives are based on frst-year energy (kWh)
savings. Eligible projects must result from a permanent facility
improvement that results in a permanent reduction in electrical
(kWh) energy usage due to an improvement in system effciency.
Projects involving measures covered by the prescriptive incentive
portion of the program are not eligible for a custom incentive.
Submit with application
• A list of the present and proposed equipment and components
slated for installed, including manufacturer’s catalog/model
numbers
• Manufacturer’s specifcations showing capacities and
performance for all major components
All equipment purchased for custom projects must be new.
The applicant is required to submit a Pre-Approval Application
for all custom projects while the existing equipment is still in
operation to allow AEP Ohio the opportunity to verify the existing
equipment.
Project payback equals the ratio of the project cost divided by
the annual energy bill savings. Eligible custom incentives have a
project payback greater than or equal to one year and less than or
equal to seven years.
Projects that are NOT eligible for a custom incentive
include:
• Fuel switching (e.g., electric to gas or gas to electric)
• Changes in operational and/or maintenance practices or
simple control modifcations not involving capital costs
• On-site electricity generation
• Projects that involve peak-shifting (and not kWh savings)
• Renewable energy
Energy-Savings Calculations
Detailed engineering calculations using industry-standard
engineering algorithms or simulation models that document the
annual total energy savings and on-peak demand savings must
accompany custom applications. The applicant must submit
calculations and methods used to derive the savings, along with
all assumptions used in the calculations. Include the documented
source for these assumptions. AEP Ohio will review the submittal.
AEP Ohio is solely responsible for the fnal determination of the
annual energy savings used to calculate the incentive amount.
AEP Ohio may need to conduct inspections both before and after
the retroft projects to verify equipment and operation conditions.
AEP Ohio also reserves the right to require specifc measurement
and verifcation activities, including monitoring both before and
after the retroft, and to base the incentive payment on the results
of these activities.
The following serves as guidelines for the minimum required
documentation. The program team may be able to assist in
calculating savings. Please contact the team for more details.
Calculations may be performed by “hand,” but spreadsheet
analysis or more rigorous modeling is preferred. Provide all
analysis in electronic format. Include all assumptions such
as operating hours, and existing and proposed equipment
operational details. Use engineering algorithms and procedures
from recognized technical organizations, such as American
Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE), Sheet Metal and Air Conditioning Contractors’
National Association (SMACNA), American National Standards
Institute (ANSI), etc. Use rated performance factors tested under
accepted procedures specifed by recognized rating agencies
such as Air-Conditioning and Refrigeration Institute (AHRI), ANSI,
American Society for Testing and Materials (ASTM), etc. Provide
an explanation when equipment-performance rating conditions
vary from standard conditions.
In support of the calculations, provide extensive documentation
that outlines the basis for the savings estimates. The
documentation must provide information on the equipment
operating schedule, daily and seasonal load profle, and baseline
AND energy-effcient equipment performance at the operating
loads. Typical documentation for custom projects often includes:
• Baseline/existing and proposed equipment make and model
numbers, including operating voltage and rated full-load amps
• Existing equipment condition and age
• Engineering or architectural drawings and equipment schedule
sheets
• Component specifcations that include part-load effciency or
performance factors
• Spreadsheet calculations or input/output fles and results from
system modeling or other engineering analysis using accepted
engineering algorithms and practices
• Log sheets, trend logs from a building management system
or other operating documentation that often are necessary to
document operating hours and equipment loading, and are
used as a basis for the calculations (In some cases, short-term
monitoring may be required to document the load profle.)
• Control sequence of operations that are necessary where
controls play a part in the savings equation
Additional documentation, other than that described in the
application, may be required for program participation. Larger
projects also may require pre- and post-project sub-metering
Page 47
Prescriptive & Custom
Program Application
ENERGY IS PRECIOUS. LET’S NOT WASTE IT.
CUSTOM SPECIFICATIONS
or monitoring of loads and/or power input as part of another
measurement and verifcation activity to demonstrate the actual
energy savings realized.
Baseline for Custom Analysis
In situations where equipment is replaced prior to the end of
its rated service life (more than 5 years) in order to achieve
energy savings, it is permissible to use the existing equipment
performance as the baseline for the energy-savings calculations.
In situations where equipment is replaced due to failure or
for other reasons (such as obsolescence or a need for more
capacity), the baseline performance used in the savings
calculations should refect either the minimum performance
required by federal or local energy code for that equipment type
and application (where a code applies) or the performance of
the equipment that would have been selected as the customer’s
“standard practice” when a code does not apply.

Sponsor Documents

Recommended

No recommend documents

Or use your account on DocShare.tips

Hide

Forgot your password?

Or register your new account on DocShare.tips

Hide

Lost your password? Please enter your email address. You will receive a link to create a new password.

Back to log-in

Close