What are the costs of an AVR?
Hello all. I am an electrical engineering student and I was wondering if anyone can give me some lights about the costs associated with an Automatic/Electronic 32-Step Voltage Regulator (for power distribution application...) I mean all the costs associated with it, but separetly: 1- Acquisition cost (average or price range...) 2-Installation cost (average, considering normal conditions...) 3- Operation cost, including cost of power losses and maitenance costs (both average values...) 4- Expected operation lifetime...? (in years) Just to have an idea. This information is for a university task. Regards and thanks in advance. 2 days ago
    

Close viewer Like Comment Follow Flag o Flag as Promotion o Flag as Job o Flag as Inappropriate More o Reply Privately



lasman limbong likes this You, lasman limbong like this 1 comment

PhilippeUnfollow Follow Philippe Philippe Mertens • Hi David, I am familiar with following AVR relays: - TAPCON 230, 240 and 260 from MR

- REG-D and REG-DA from A-Eberle, - SPAU from ABB - KVGC 202 from AREVA - Supertapp / RVM5 from VA-Tech Reyrolle with RTMU1 module Familiar means I was involved in the transformer design and as an option, I ordered them, programmed and assisted installation. Sometimes I went on-site for modifications, error's, customer assistence. I've seen prices of the single relays, the complete build-in relay panel prices and the total package prices including FAT testing, shipping, on-site installation.and on-site testing. I'm not putting commercial information on linked-in but you can mail me [email protected] Of course there are no operation costs and I'm not sure how you want to calculate them. As a small remark, all these AVR's are electronic but there's a huge difference in analog relays and digital relays. The number of steps does not change the price. I guess you must be a bit more accurate on functionality: - suited for transformer parallel opereation yes or no. - If yes, which operating principle master-follower or minimum circulating reactive current - suitable for step-by-step operating principles? - Are there OLTC blocking functions in case of undervoltage, overvoltage, overcurrent - Is there an overvoltage monitoring - Is line-drop compensation possible - programmable dead-band? - programmable time delay One cost factor that also needs to be considered is the extra equipment cost like 1 VT, 1CT (in case of LDC) one tap position output in the OLTC motor drive in case of parallel operation with master-follower. 1 day ago

Sponsor Documents

Or use your account on DocShare.tips

Hide

Forgot your password?

Or register your new account on DocShare.tips

Hide

Lost your password? Please enter your email address. You will receive a link to create a new password.

Back to log-in

Close