What Is Film Capacitor
The capacitor unit shall be charged to a voltage of y/ 2 V B and discharged through a circuit which
satisfies the following conditions:
a) The peak value of the discharge current shall not be less than 120 times the rated ( rms ) current of
the capacitor unit; and
b) The decrement of the discharge current shall be as agreed to between the manufacturer and the
purchaser in conformity with the service conditions.
This discharge shall be repeated 10 times at intervals of 5 seconds. A longer interval may be agreed to
between the manufacturer and the purchaser.
Furthermore, the same unit shall be subjected to a voltage of y/ 2 Sum and then discharge through a
circuit having a negligible impedance. This discharge shall be performed once only, immediately after
the preceding discharges.
As quickly as possible after the last discharge, and preferably within 10 seconds, an ac voltage of 1*6 V n
shall be applied and maintained for 10 min ( for self-healing metalized film capacitor this period shall be
of 30 min ). There shall be no increase in partial discharge level during the last 10 min.
Before and after the test, the capacitance shall be measured accordingly and the two measurements
shall be corrected to the same dielectric temperature. No significant change of capacitance shall be
apparent from these measurements. When interpreting the results of the measurements, the factors
stated in 14.2.5 shall be taken into account.
External fuses intended for units or groups of units shall be subjected to the discharge test either when
tested together with the unit(s) or separately ( see 18.2 ).
The discharge current shall be measured according to IS : 2071 (Part IT)- 1974*. The discharge test shall
always be made on a complete capacitor unit. If the partial discharge measurement can not be made
with satisfactory accuracy on a complete unit (see also 14.2.6) an additional discharge test including
partial discharge measurement shall be made on a model unit.
If the calculated value of the capacitor discharge current which is likely to occur when the overvoltage
protector operates is substantially different from 100 or 50 times the rated current in the case of
overvoltage.