Auto

Published on June 2016 | Categories: Documents | Downloads: 68 | Comments: 0 | Views: 530
of 3
Download PDF   Embed   Report

Comments

Content

Schmidbauer transformers. Get the power. Turn it on.

3 PHASE AUTOTRANSFORMER
Coolant bores | natural convection Horizontal mounting version
TYPICAL APPLICATIONS
3 phase autotransformer according to IEC/ EN61558-2-13 for general applications without the need of a galvanic isolation, e.g. for transforming typical mains voltage to other voltages needed by tools, machinery or other devices. Autotransformers do not provide any electrical protection due to the lack of galvanic isolation between input and output windings.

DAL
2kVA … 5kVA

3 phase autotransformer according to EN61558-2-13 Voltage range for input / output: 100 … 550 V Power range: 2 kVA ... 5 kVA

EN61558-2-13

SPECIFICATIONS
3 phase transformer, protection class I ready. Autotransformers are provided for a voltage range from 100V up to 550V (special voltage versions on request). Standard switching matrix: Yan0 (typical star load approx. 10%). If typical star load should reach rated current, switching matrix Zan0 is used. Please add switching matrix requested when ordering the transformer. For further information, don´t hesitate to contact us. Final operation position must allow natural convection through coolant bores. Due to innovative vacuum impregnation in polyester varnish, the noise level is extraordinary low. Screw terminals are contact proof according to VBG4. Transformer provides 2 loops for safe transportation or craning (core sizes > 3UI150 / 65 – 4.5kVA).

TECHNICAL DATA
Description Voltage range for input / output Frequency Power range Important transformer features 3 phase autotransformer according to IEC/EN615582-13 100 … 550 V 50/ 60 Hz 2 kVA ... 5 kVA Transformer completely vacuum impregnated No galvanic isolation Standard switching matrix: Yan0 (typical star load approx. 10%) Switching matrix - on request: Zan0 (typical star load 100%) Protection class I ready B UL94 HB (V0 possible) 40°C IP00 - open transformer Screw terminals contact proof according to VBG4 Ready for horizontal mounting including angle brackets Final operation position must allow natural convection through coolant bores.

Output design

Protection class Insulation class Fire protection class Max. ambient temperature Degree of protection Connections

Other data

©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: [email protected] • www.schmidbauer.net

Schmidbauer transformers. Get the power. Turn it on.

DAL
2kVA … 5 kVA

STANDARD TYPES

Power kVA 2.0 2.5 3.2 4.0 4.5 5.0
*)

A 290 290 290 330 330 360

B*) 120 110 125 125 150 142

Dimensions D approx. mm 200 258 C 220 220 250 250 280 258 258 298 298 322

E 160 176 176 200 200 224

F 9.0 x 13.0 9.0 x 13.0 9.0 x 13.0 9.0 x 13.0 9.0 x 13.0 9.0 x 13.0

Copper weight KG 6.30 7.50 8.20 12.20 11.40 17.00

Total weight KG 19.30 20.50 25.50 31.80 36.50 44.00

Size 3UI 120 / 51 3UI 132 / 46 3UI 132 / 60 3UI 150 / 52 3UI 150 / 65 3UI 168 / 58

Type and ordering no. DAL0200 DAL0250 DAL0320 DAL0400 DAL0450 DAL0500

Note: Dimension „B“ indicates a reference value only. Phase current and therefore size of screw terminals used depends on transformer ratio (identical size).

Coolant bore between primary and secundary winding. Winding on polyamide coil former.

©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: [email protected] • www.schmidbauer.net

Schmidbauer transformers. Get the power. Turn it on.

USE OF 1 PHASE AND 3 PHASE AUTOTRANSFORMERS

INFO
Mains supplied power without transformer „serial winding“

Autotransformers do not provide galvanic isolation. Electroconductive connection between input and output winding. If difference between input voltage and output voltage is small...: ...mains power may be higher ...transformed power is lower ...size can be reduced (core, copper winding)
Input

Transformed power „parallel winding“

Output Load

Please note: Equation: Regarding input/ output „upper“ or „lower voltage“ is independant, voltage related only For of 3 phase autotransformers value phase voltage is important.

Equation to calculate the requested size: Example: 1 phase autotransformer Input voltage 440V | Output voltage 400V „Rated power“ needed for application: 5kVA
lower voltage

Example shows 90% power saving compared isolating transformers. Identical equation works with 3 phase transformers. Standard circuit design autotransformers is Yan0. of 3 phase

Size

load

upper voltage

Size

Size

Max. load at neutral wire is approx. max. 10% of nominal current (phase current). If 100% neutral wire load is requested, circuit design Zan0 is manufactured (Note: Yan0 design can be used in certain circumstances, if neutral wire at input provides full load and transformer star point is permanently connected to load. Please don´t hesitate to contact us for further informations.

Description
Code Circuit design

Schematic

Circuit diagram

Star point

Approx. 10% load

100% load

©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: [email protected] • www.schmidbauer.net

Sponsor Documents

Or use your account on DocShare.tips

Hide

Forgot your password?

Or register your new account on DocShare.tips

Hide

Lost your password? Please enter your email address. You will receive a link to create a new password.

Back to log-in

Close