Cooper

Published on May 2016 | Categories: Documents | Downloads: 64 | Comments: 0 | Views: 672
of 8
Download PDF   Embed   Report

Comments

Content

Public Address/Voice Announcement High Rise Evacuation System

System Configuration
Basic System Includes:
• Master Panel
• Master Mic Control
• 16 switch control points
• Dual Channel DMR
• High speed communication loop
• Distributed Panel (HMX)
• 4 Output Zones (may be configured for 8)
• Dual Channel Audio Interface
• Dual Channel Amplification
Optional:
• Integrated Fire Phone
• Area-of-Rescue
• Number of distributed panesl to be deteremined
by building specifications
• Maximim System Configuration - Up to 250
Distributed Panels (HMX) and up to 1000
switch points

Master Panel
Description:

Cooper Wheelock’s PA/VA Voice System operates in conjunction
with the Cooper 6000 Fire Alarm Control Panel (FACP) to provide automatic response in a building for emergencies.
The system includes all necessary features to provide and effective evacuation system. The Cooper Wheelock PA/VA can be
easily customized for configuration and applications in any high
rise specification.

Features:

• Works with Analog/Addressable and Microprocessor based
Fire Alarm Panels
• Easy Installation and Operation
• Fully Supervised
• Natural Sound Voice Recordings
• Modular Systems - components added as needed

User friendly controls allow the Fire Department Authority to
easily take command for evacuation or relocation procedures or
emergencies. Emergency response teams can monitor the situation until professional help arrives at the scene.

• Integrated 2 Channel Digital Message Repeater

The Cooper Wheelock PA/VA system includes capacity for 6
channels simultaneous audio, flexibility provides for public address announcements, stay-in-place, evacuation, or automatic
messages.

• Fast RS-485 Communications Protocol

Warden Stations and Fire Fighters telephones can be configured
as required, Area of Rescue can reassure physically challenged
occupants that help is being dispatched to their location.

• Up to 4 Minute Message Capability

• True Multiplex 6 Channel Distributed Audio
• Live Microphone Page to any zone
• Integrated Fire Phone, Area of Rescue and Fan & Damper
Control capability
• Works with 12VDC or 24VDC Fire Alarm Panel
• 3 Minute Message Restart on Microphone Key
• Built in Alarm and Alert Signals

Master Panel
Distributed panel configurations

System Configuration

HMX-MP16
Master Panel, 16 Switch Control

Basic System Includes:
• Master Panel

HMX-MP32
Master Panel, 32 Switch Control

• Master Mic Control

HMX-MP48
Master Panel, 48 Switch Control

• Dual Channel DMR

HMX-MP64
Master Panel, 64 Switch Control
HMX-MP80
Master Panel, 80 Switch Control
HMX-MP96
Master Panel, 96 Switch Control
HMX-MP16/P
Master Panel, 16 Switch Control, Master Fire Phone
HMX-MP32/P
Master Panel, 32 Switch Control, Master Fire Phone
HMX-MP64/P
Master Panel, 64 Switch Control, Master Fire Phone
HMX-MP80/P
Master Panel, 80 Switch Control, Master Fire Phone
HMX-MP96/P
Master Panel, 96 Switch Control, Master Fire Phone

Panel options
Cards may be added as job requirements demand
HMX-MP16
Master Panel, 16 Switch Control
HMX-MP32
Master Panel, 32 Switch Control
HMX-MP48
Master Panel, 48 Switch Control
HMX-MP64
Master Panel, 64 Switch Control
HMX-MP80
Master Panel, 80 Switch Control
HMX-MP96
Master Panel, 96 Switch Control
HMX-MP16/P
Master Panel, 16 Switch Control, Master Fire Phone
HMX-MP32/P
Master Panel, 32 Switch Control, Master Fire Phone
HMX-MP64/P
Master Panel, 64 Switch Control, Master Fire Phone
HMX-MP80/P
Master Panel, 80 Switch Control, Master Fire Phone
HMX-MP96/P
Master Panel, 96 Switch Control, Master Fire Phone

• 16 switch control points
• High speed communication loop
Optional:
• Integrated Fire Phone
• Area-of-Rescue
• Maximim System Configuration - Up to 1000
Monitor and Control Points
Technical Specifications
Primary Power
Battery Power
Electrical Ratings

220 VAC
24 VDC
All circuits @ 24 VDC
RS-485 Standard 1M Baud
Communications Bus
data rate, category 5 cable
Voltage
5V peak-to-peak max
Current
50mA max
Impedence
120 Ohms
Frequency
1.024 MHz
Backbox dimensions 36.8 W x 68.6 H x 10.2 D cm
Color
Cool Grey 1 C
Master Panel

Standby

Alarm

MX-DCC
MX-ASC

80mA
30mA

80mA
30mA

MX-MFP

10mA

10mA

MX-SSC
MX-SLC
MX-MMC
MX-IOI

25mA
6mA
45mA
20mA

25mA
6mA
45mA
20mA

Public Address/Voice Announcement High Rise Evacuation System
Master Panel
HMX-MP64P Master Panel - Ribbon Cable Connection Detail

In the Master Panel system
components are mounted to a
removable back plate. The door
and front panel are removable.
This enables field wiring to be
installed cleanly.
Connections to the User Interface
components (Switch/LED banks,
Mic/System control and Master
Fire Phone) is accomplished with
ribbon cables. The front panel
mounts separately on a continuous
hinge so once installed the access
for system programming is easily
accommodated.

NetComm Loop Wiring (Style 4)

NetComm Loop Wiring (Style 7)

Public Address/Voice Announcement High Rise Evacuation System
Master Panel
HMX True Multiplex System Capabilities
HMX-DP
NetComm Loop:
• Twisted Pair - Low Capacitance
• 4,000 Feet between panels
• Data and 6 Audio Channels Simultaneously
• High speed RS-485 Communications
• Style 4 or 7 Field Selectable

HMX-DP

HMX-MP

Public Address/Voice Announcement High Rise Evacuation System
Distribution Panel
Description:

Cooper Wheelock’s PA/VA Voice System operates in conjunction
with the Cooper 6000 Fire Alarm Control Panel (FACP) to provide automatic response in a building for emergencies.
The system includes all necessary features to provide and effective evacuation system. The Cooper Wheelock PA/VA can be
easily customized for configuration and applications in any high
rise specification.
User friendly controls allow the Fire Department Authority to
easily take command for evacuation or relocation procedures or
emergencies. Emergency response teams can monitor the situation until professional help arrives at the scene.
The Cooper Wheelock PA/VA system includes capacity for 6
channels simultaneous audio, flexibility provides for public address announcements, stay-in-place, evacuation, or automatic
messages.
Warden Stations and Fire Fighters telephones can be configured
as required, Area of Rescue can reassure physically challenged
occupants that help is being dispatched to their location.

Features:
• Works with Analog/Addressable and Microprocessor based
Fire Alarm Panels

Distributed panel configurations

• Easy Installation and Operation

HMX-DPS25
Single Channel, 25W

• Fully Supervised

HMX-DPS50
Single Channel, 50W

• Modular System - components added as needed

HMX-DPS100
Single Channel, 100W

• True Multiplex 6 Channel Distributed Audio

HMX-DPS200
Single Channel, 200W

• Fast RS485 Communications Protocol

HMX-DPS25/P
Single Channel, 25W, Fire Phone

• Natural Sound Voice Recordings
• Integrated 2 Channel Digital Message Repeater
• Live Microphone Page to any zone
• Integrated Fire Phone, Area of Rescue and Fan & Damper
Control capability
• Up to 4 Minute Message Capacity

HMX-DPS50/P
Single Channel, 50W, Fire Phone

• Works with 12VDC or 24VDC Fire Alarm Panel

HMX-DPS100/P
Single Channel, 100W, Fire Phone

• Built-In Alarm and Alert Sounds

HMX-DPS200/P
Single Channel, 200W, Fire Phone

Panel options
Cards may be added as job requirements demand

HMX-DP25
Double Channel, 25W
HMX-DP50
Double Channel, 50W
HMX-DP100
Double Channel, 100W
HMX-DP25/P
Double Channel, 25W, Fire Phone
HMX-DP50/P
Double Channel, 50W, Fire Phone
HMX-DP100/P
Double Channel, 100W, Fire Phone

• 3 Minute Message Restart on Microphone Key

HMX-MBK Motherboard Relay Card
Expands MX-MBR output 8 Class B or 4 Class A circuits
HMX-FPI Phone Interface Card
Included in /P panels, up to 3 additional cards may be
added
HMX-FPO Fire Phone Output Card
Used with additional MX-FPI’s
HMX-AMI
Included with basic panel, additional cards give the
ability to control multiple modules or accommodate full
6 channel operation
Specifications are subject to change without notice. Specifications are
provided for information only and no responsibility is assumed by Cooper
Wheelock.

Public Address/Voice Announcement High Rise Evacuation System
Distribution Panel
System Configuration
Basic System Includes:
• Distribution Panel (HMX-DP)
• 4 Output Zones (may be configured for 8)
• Dual Channel Audio Interface
• Dual/Single Channel Amplification
Optional:
• Integrated Fire Phone
• 4 Circuits expandable to 8, 12 or 16
• Area-of-Rescue
• Maximim System Configuration - Up to 256
Distributed Panels (HMX-DP)

Technical Specifications
Primary Power
220 VAC
Battery Power
24 VDC
Battery Charging
Maximum charging current from CWX-25/50 is 800mA
Max. Battery Size
17Ah. for CWX-25/50, 24Ah for CWx-100
Electrical Ratings
All circuits @ 24 VDC
Communications Bus RS-485 Standard 1M Baud data rate, category 5 cable
Voltage
Current
Impedence
Frequency
Backbox dimensions
Color
Master Panel
MX-DCC
MX-MBR
MX-AMI
MX-FPI

5V peak-to-peak max
50mA max
120 Ohms
1.024 MHz
36.8 W x 68.6 H x 10.2 D cm
Cool Grey 1 C

Standby
55mA
10mA
10mA
13mA

Alarm
55mA
55mA
10mA
135mA

Public Address/Voice Announcement Fire Phone Equipment
Fire Phone accessories give the Cooper Wheelock PA/VA
system two way communication capability.
Fire Phone Jacks are mounted on a single gang plate.
Fixed telephone and warden stations are available in Surface/Semi-Flush cabinet with a Thumb Turn latch.

Ordering Information
MX-FJ Telephone Jack SG Plate
Brushed Stainless Steel Single Gang Plate
MX-FH Portable Handset
Color - Red
(6 mount in MX-TC cabinet)
MX-TC Telephone Cabinet
Holds 6 MX-FH Portable Handset
Cabinet: Charcoal Gray - std. -R Red
(Surface/Semi-Flush Mount/Key 27 x 14-1/2 x 4”)
MX-FS Fire Phone Station
Coil cord / Thumb Turn Latch
Cabinet: Red
(Surface/Semi-Flush Mount 12-3/4 x 7-1/4 x 3-3/4”)
MX-WS
Armored Cable / Thumb Turn Latch
Cabinet: Red
(Surface/Semi-Flush Mount 12-3/4 x 7-1/4 x 3-3/4”)

Low Profile Speakers & Speaker Strobes
Description:
Series E Speakers and Speaker Strobes are
designed for high effeciency sound output with
field selectable input voltage (25/75 VRMS)
and field selectable taps from 1/8 to 2 watts.
Strobe Options:
• Single Candela Wall 1575

Table 1: Average RMS Current

• Multi-candela 15/30/75/110 (wall)
or 15/30/75/95 (ceiling)

E70 Strobe Current - Wall Mount
E90 Strobe Current - Ceiling Mount
E70/E90
24MCW
24MCWH
24MCC
24MCCH
Speaker 241575W
Strobes 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd

24 vdc
UL max*

0.060

0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270

0.090

0.060 0.092 0.165 0.220 0.300 .0420 0.065 0.105 0.189 0.249 0.300 0.420

Table 2: E70/E90 UL Reverberant dBA @ 10 Feet**
watts

1/8

1/4

1/2

1

2

E Speaker

77

81

83

86

89

E Speaker Strobe

76

80

82

85

88

**dBA ratings are based on testing under UL Standard 1480.
* RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range
(16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max
current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.

Agency Approvals
Model Model Model
Mounting OpColor Color Color
tions
RED White Nickel
UL MEA CSFM FM BFP

Strobe Sync w/
SM, DSM or
PS-24-8MC

Strobe
Candela

-

X

15/30/75/110

X

-

X

-

X

15/30/75/110

-

X

-

X

15/30/75/110

-

Model

Order Wall Ceiling
Code Mount Mount

E70-24MCW-FR

9022

X

E70-24MCW-FW

9023

E70-24MCW-FN

3099

E70-241575W-FR

-

L,O,P,Q,R,U,Y

X

X

X

X

X

X

-

L,O,P,Q,R,U,Y

X

X

X

X

X

-

X

Q,U

X

X

X

X

X

7871

X

-

X

15 (75 on Axis)

X

-

-

L,O,P,Q,R,U,Y

X

X

X

X

X

E70-241575W-FW 7876

X

-

X

15 (75 on Axis)

-

X

-

L,O,P,Q,R,U,Y

X

X

X

X

X

E70-241575W-FN

3100

X

-

X

15 (75 on Axis)

-

-

X

L,O,P,Q,R,U,Y

X

X

X

X

X

E70-R

7866

X

X

-

-

X

-

-

Q,U

X

X

X

X

X

E70-W

7868

X

X

-

-

-

X

-

Q,U

X

X

X

X

X

E70-N

3108

X

X

-

-

-

-

X

Q,U

X

X

X

X

X

E70-24MCWH-FR 3470

X

-

X

135/185

X

-

-

L,O,P,Q,R,U,Y

X

X

X

X

*

E70-24MCWH-FW 3474

X

-

X

135/185

-

X

-

L,O,P,Q,R,U,Y

X

X

X

X

*

E70-24MCWH-FN 0059

X

-

X

135/185

-

-

X

Q,U

X

X

X

X

*

E90-24MCC-FW

3166

-

X

X

15/30/75/95

-

X

-

Q,U,V

X

X

X

X

*

E90-24MCC-FR

3165

-

X

X

15/30/75/95

X

-

-

Q,U,V

X

X

X

X

*

E90-24MCC-FN

3185

-

X

X

15/30/75/95

-

-

X

Q,U,V

X

X

X

X

*

E90-W

7869

X

X

-

-

-

X

-

Q,U,V

X

X

X

X

X

E90-R

7867

X

X

-

-

X

-

-

Q,U,V

X

X

X

X

X

E90-N

3109

X

X

-

-

-

-

X

Q,U,V

X

X

X

X

X

E90-24MCCH-FW 3471

-

X

X

115/177

-

X

-

Q,U,V

X

X

X

X

*

E90-24MCCH-FR

3481

-

X

X

115/177

X

-

-

Q,U,V

X

X

X

X

*

E90-24MCCH-FN

0062

-

X

X

115/177

-

-

X

Q,U,V

X

X

X

X

*

273 Branchport Avenue
Long Branch, NJ 07740
Phone: (800) 631-2148
Fax: (732) 222-2588
www.cooperwheelock.com

UL
®

WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
Evac System 01/07