website http://www.lgservice.com e-mail http://lgservice.com/techsup.html

LG

LG Multi Type Air Conditioner
SERVICE MANUAL
MODEL
• Indoor Unit: Room Type AMNH076LQL0 AMNH096LQL0 AMNH096LRL0 AMNH126LRL0 AMNH186LTL0 AMNH246LTL0 Art Cool Type AMNH096AP*1 AMNH126AP*1 Art Cool Deluxe Type AMNH076DZ*0 AMNH096DU*0 AMNH126DU*0 • Outdoor Unit: A2UW146FA0 A2UW186FA0 A3UW186FA0 A3UW246FA0 A4UW246FA0 A4UW306FA0 A6UW406FA0 A7UW486FA0 A8UW566FA0

Duct Type
AMNH096BTG0 AMNH126BTG0 AMNH186BTG0 AMNH096BPA0 AMNH126BPA0 AMNH186BHA0 AMNH246BHA0 AMNH306BGA0 AMNH366BGA0

1 Way CST
AMNH096TCC0 AMNH126TCC0

4 Way CST
AMNH126TEC0 AMNH186TEC0 AMNH246TFC0 AMNH306TFC0 AMNH366TDC0 AMNC126TEC0 AMNC186TEC0 AMNC246TFC0

CVT
AMNH096VEA0 AMNH126VEA0 AMNH186VBA0 AMNH246VBA0 AMNC246VBA0 A2UQ166FA0 A3UQ186FA0 A6UQ406FA0 A8UQ566FA0

CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL. • ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Multi type Air Conditioner Service Manual

TABLE OF CONTENTS
Model Number Nomenclature ....................................................................................................................3 Symbols Used in this Manual ...................................................................................................................5 Safety Precautions ......................................................................................................................................6 Dimensions ................................................................................................................................................12 Indoor Unit.............................................................................................................................................12 Outdoor Unit ...........................................................................................................................................20 Product Specifications ............................................................................................................................22 Installation .................................................................................................................................................28 Select the best location of indoor unit ....................................................................................................28 How to fix ...............................................................................................................................................31 Piping and Drainage of Indoor Unit ........................................................................................................38 Connection of indoor unit piping.............................................................................................................39 Remote Controller Installation ................................................................................................................62 Connecting Pipings and the cable to Outdoor unit .................................................................................64 Checking the Drainage and Pipe forming...............................................................................................66 Maximum Length of Pipe and Extra Charge of Refrigerant Charge.......................................................71 Test Running ..........................................................................................................................................78 System Layout and Piping Length..........................................................................................................81 Installation ..............................................................................................................................................82 Installation of The Main Unit...................................................................................................................83 Connection of Piping ..............................................................................................................................84 Connection of Wiring ..............................................................................................................................85 Operation ..................................................................................................................................................86 Function of control..................................................................................................................................86 Function of Indoor Unit ...........................................................................................................................91 Function of Outdoor Unit ........................................................................................................................97 Remote Control Operation .....................................................................................................................98 Control Devices and Function ...............................................................................................................106 Simple Central Control .........................................................................................................................106 Term of Each part and Function ...........................................................................................................106 Electrical wiring ....................................................................................................................................107 Deluxe Central Control .........................................................................................................................113 Disassembly of the parts (Indoor unit) .................................................................................................119 Indoor unit ............................................................................................................................................119 Schematic Diagram .................................................................................................................................133 Electronic Control Device .....................................................................................................................133 Wiring Diagram.....................................................................................................................................142 Components Locations.........................................................................................................................146 Troubleshooting Guide ...........................................................................................................................161 Refrigeration Cycle Diagram ................................................................................................................161 Self-diagnosis Function ........................................................................................................................166 Cycle Troubleshooting Guide................................................................................................................167 Electronic Parts Troubleshooting Guide ...............................................................................................168 General Information..............................................................................................................................173 (3-way) Valve ...........................................................................................................................................189 Exploded View & Replacement Parts List ............................................................................................193 Indoor Unit ...........................................................................................................................................193 Outdoor Unit ........................................................................................................................................222

2 Multi type Air Conditioner

Model Number Nomenclature

Model Number Nomenclature
Indoor Unit
AMN H 07 6 L Q A 0
Serial Number Function
A : Basic, L : Nano Plasma + Auto Clean(Wall Mounted) C: Plasma(Ceiling Cassette), G: Low Static Motor

ART COOL(DELUXE) Type Front Panel Color
B : Blue, D : Wood, M : Meta, R : Mirror, W : White

Chassis Name Indoor Unit Type
L : Wall Mounted , A : ART COOL D : ART COOL DELUXE, T : Ceiling Cassette B : Ceiling Concealed Duct V : Ceiling & Floor(Convertible)

Electrical Rating
6 : 1Ø, 220-240V, 50Hz

Nominal Cooling Capacity in Btu/h
Ex) 7,000 Btu/h '07', 18,000 Btu/h '18'

Model Type
H : Heat Pump C : Cooling Only

MPS Inverter Multi System Indoor Unit

Outdoor Unit
A2U W 18 6 F A 0
Serial Number Function
A : Basic

Multi Type
F : Free Joint Multi Type

Electrical Ratings
6 : 1Ø, 220-240V, 50Hz 8 : 3Ø, 380-415V, 50Hz

Nominal Cooling Capacity in Btu/h
Ex) 18,000 Btu/h '18', 48,000 Btu/h, '48'

Model Type
W : DC Inverter Heat Pump Q : DC Inverter Cooling Only.

R410A MPS Inverter Multi System Outdoor Unit. And No. of Connectable Indoor Units Ex) A2U : Connectable max. 2 Indoor Units A6U : Connectable max. 6 Indoor Units

Service Manual 3

Model Number Nomenclature

Panel (Cassette, Built in Duct)
Category CHASSIS PANEL NAME PT-CFA TF PT-CFC PT-HFA PT-HFC PT-CCA TC CST PANEL TE(family look) PT-CCC PT-HCA PT-HCC PT-HEA PT-HEC PT-CEA PT-CEC PT-HAD TD(family look) PT-HDC PT-CDA PT-CDC BUILT IN DUCT BP BQ PB-HPA PB-HQA PANEL P/NO. 3721A10072B 3721A10072G 3821A10072A 3721A10072E 3721A10023Z 3721A10023W 3721A10023Y 3721A10023V 3721A10105A 3721A10105B 3721A10105C 3721A10105D 3721A10106A 3721A10106B 3721A10106C 3721A10106D 3721A20168A 3721A20168B SERIAL NO. 8435002992862 8435002992879 8435002992886 8435002992893 8435002994095 8435002994101 8435002994118 8435002994125 8435002992978 8435002992985 8435002992954 8435002992961 8435002994057 8435002994064 8435002994071 8435002994088 Remark COOLING COOLING + PLASMA HEATING HEATING + PLASMA COOLING COOLING + PLASMA HEATING HEATING + PLASMA HEATING HEATING + PLASMA COOLING COOLING + PLASMA HEATING HEATING + PLASMA COOLING COOLING + PLASMA 9K/12K 18K/24K

P 1

T 2

3

H 4

E 5

A 6

6. Function Function Basic A B C D E F 0 1

Number 1, 2 3 4 5 6

Contents Panel for Cassette Cooling/Heatpump Chassis Name Function

Plasma Filter Elevation Grille Elevation Grille + Plasma Filter TE/TB/TD Before 2003 : Basic TE/TD Before 2003 : Plasma Filter

5. Chassis Name Chassis Abbrevation TC C TB B TD D TE E TF F TH H TJ J BP P BQ Q

4 Multi type Air Conditioner

Model Number Nomenclature

Indoor Units
Category Type Chasiss 2.1 (7000) AMNH 076LQL0 AMNH 076DZ*0 2.6 (9000) AMNH 096LQL0 AMNH 096LRL0 AMNN 096AP*1 AMNH 096DU*0 AMNH 096TCC0 AMNH 096BTG0 AMNH 096BPA0 AMNH 096VEA0 Model Name Capacity, kW(Btu/h) 3.5 5.3 (12000) (18000) AMNH 126LRL0 AMNN 126AP*1 AMNH 126DU*0 AMNH 126TCC0 AMNH/C 126TEC0 AMNH 126BTG0 AMNH 126BPA0 AMNH 126VEA0 AMNH 186LTL0 AMNH/C 186TEC0 AMNH 186BHA0 AMNH 186BTG0 AMNH 186VBA0 7.0 (24000) AMNH 246LTC0 AMNH/C 246TFC0 AMNH 246BHA0 AMNH/C 246VBA0 8.8 (30000) AMNH 306TFC0 AMNH 306BGA0 10.6 (36000) AMNH 366TDC0 AMNH 366BGA0 -

SQ Wall Mounted General SR ST General ART COOL Mirror SU 1Way Ceiling Cassette TC TE 4Way TF TD High Static Low Static Built in Ceiling & Floor Convertible VB BH BG BT BP VE SP1 SZ

Ceiling Concealed Duct

Outdoor Units
MPS Inverter Multi Series
Heat Pump Rated Capacity

Multi Piping Type

Distributor Type
A6UW406FA0 11.7(40000) 13.5(46000) Max.6 Units 4.7~15.2 16000~52000 A7UW486FA0 14.0(48000) 16.2(55200) Max.7 Units 5.6~18.3 19200~62400 A8UW566FA0 16.4(56000) 18.9(64400) Max.8 Units 6.6~21.3 22400~72800

Model Name A2UW146FA0 A2UW186FA0 A3UW186FA0 A3UW246FA0 A4UW246FA0 A4UW306FA0 Cooling kW(Btu/h) 4.7(1600) 5.3(18000) 5.3(18000) 7.0(24000) 7.0(24000) 8.8(30000) Heating kW(Btu/h) 5.3(1800) 6.3(21600) 6.3(21600) 8.2(28000) 8.2(28000) 10.1(34500) Number of Indoor Units to be Connected Max.2 Units Max.2 Units Max.3 Units Max.3 Units Max.4 Units Max.4 Units Indoor Units kW 2.1~6.2 2.1~7.0 2.1~7.0 2.1~9.7 2.1~9.7 2.1~11.4 Connectable Capacity Btu/h 7000~21000 7000~24000 7000~24000 7000~33000 7000~33000 7000~39000 Power Supply 1Ø, 220-240V, 50Hz

Notes : A2UW146FA0, A2UW186FA0 and A3UW186FA0 are not TPS inverter system but one inverter compressor system.

Symbols Used in this Manual
This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the air conditioner.
NOTICE

This symbol indicates special notes.

Service Manual 5

Safety Precautions

Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. s Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.

WARNING CAUTION

This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.

s Meanings of symbols used in this manual are as shown below.

Be sure not to do. Be sure to follow the instruction.

WARNING
s Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.

For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or electric shock.

Always ground the product.

• There is risk of fire or electric shock.

Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.

Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock

Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.

6 Multi type Air Conditioner

Safety Precautions Do not modify or extend the power cable.
• There is risk of fire or electric shock.

Do not install, remove, or reinstall the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.

Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.

For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.

Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.

Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.

Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.

Take care to ensure that power cable could not be pulled out or damaged during operation.

Do not place anything on the power cable.

• Moisture may condense and wet or • There is risk of fire or electric damage furniture. shock.

• There is risk of fire or electric shock.

Service Manual 7

Safety Precautions Do not plug or unplug the power supply plug during operation.
• There is risk of fire or electric shock.

Do not touch(operate) the product with wet hands.
• There is risk of fire or electrical shock.

Do not place a heater or other appliances near the power cable.
• There is risk of fire and electric shock.

Do not allow water to run into electric parts.
• It may cause There is risk of fire, failure of the product, or electric shock.

Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.

Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.

Gasolin

When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
• Do not use the telephone or turn switches on or off. There is risk of explosion or fire

If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
• There is risk of electric shock or fire.

Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
• There is risk of property damage, failure of product, or electric shock.

8 Multi type Air Conditioner

Safety Precautions Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.

When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.

Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.

Ventilate the product from time to time when operating it together with a stove, etc.
• There is risk of fire or electric shock.

Turn the main power off when cleaning or maintaining the product.
• There is risk of electric shock.

When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.

Take care to ensure that nobody could step on or fall onto the outdoor unit.

• There is risk of product damage or failure, or unintend- • This could result in personal injury and product damed operation. age.

CAUTION
s Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.

Install the drain hose to ensure that water is drained away properly.

Keep level even when installing the product.

• A bad connection may cause water • To avoid vibration or water leakleakage. age.

90°

Service Manual 9

Safety Precautions Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.

Use two or more people to lift and transport the product.

Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.

• Avoid personal injury.

s Operational
Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
• This could harm to your health.

Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
• There is risk of damage or loss of property.

Do not block the inlet or outlet of air flow.
• It may cause product failure.

Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
• There is risk of fire, electric shock, or damage to the plastic parts of the product.

Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of personal injury.

x Wa Thinner

10 Multi type Air Conditioner

Safety Precautions Do not step on or put anyting on the product. (outdoor units)
• There is risk of personal injury and failure of product.

Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
• A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.

Do not insert hands or other objects through the air inlet or outlet while the product is operated.
• There are sharp and moving parts that could cause personal injury.

Do not drink the water drained from the product.

Use a firm stool or ladder when cleaning or maintaining the product.

Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
• There is risk of fire or explosion

• It is not sanitary and could cause serious health issues.

• Be careful and avoid personal injury.

Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.

If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.

• They may burn or explode.

Service Manual 11

Dimensions

Dimensions
Indoor Unit
1. Split Type Indoor 2. Art Cool Type Indoor Unit
W D

H

H

W

Pipe Hole

Hanger Hole

Tubing hole cover
Installation plate

Fix Hole

Left rear piping
80mm

Right rear piping

Left rear piping
A

Right rear piping
A

Left rear piping

Right rear piping

"D"
20mm
Center
A A

"C"

20mm

Center

50mm ø70mm ø70mm
ø70mm ø70mm

Hole Center

ø70mm

(7K, 9K)
MODEL DIM W H D mm mm mm SQ 7K,9K 824 260 155

(9K, 12K)
SR 9K, 12K 900 285 156

(18K, 24K)
ST 18K, 24K 1,080 314 172

12 Multi type Air Conditioner

Dimensions

3. Art Cool Deluxe Type

H

D W

Installation plate

MODEL DIM W H D Unit mm mm mm

SZ 7K 900 272 135

SU 9K, 12K 1030 290 153

Service Manual 13

Dimensions

4. Duct Type

W

D

H

BH/BG

W

D W D

H H

BP

BT/BT1

MODEL DIM W(mm)

BT 9K/12K 708

BT1 18K 1060

BH 18K/24K 880

BG 30K/36K 1180

BP 9K/12K 580

H(mm)

230

230

260

298

300

D(mm)

537

357

450

450

750

14 Multi type Air Conditioner

Dimensions

5. CVT Type VB(18K/24K)
W H

R

D
63mm 38mm

26

5m

39 m

2m

m

250mm

36

mm

46

8m

m

175mm

10

76

mm

(Installation Plate)
36 mm

(Rear Side)

VE(9K/12K)
D

H

W

Installation plate

MODEL DIM W H D Unit mm mm mm

VE 9K/12K 900 285 156

VB 18K/24K 1200 615 205

Service Manual 15

Dimensions

6. CST Type - TC (9K/12K)
1,000 (Ceiling opening) 931.6 893.4 (Hanging bolt) 860 430 (Ceiling opening) 390
4 16.7 7 931.6 893.4 860 846
328.4 (Hanging bolt) 30.8

30.8

1 3 2

50 194.4 42.7

390 328.4

164

37 97.7 116.3 141.8 180 91.6 Ø55 130 180 Ø80 430

155

91.6 180

1050 694.5

5

480

6

(unit : mm) Number 1 2 3 4 5 6 Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air suction grill Descripition ø6.35 flare ø9.52 flare

16 Multi type Air Conditioner

Dimensions

7. CST Type - TE (12K/18K)
600 (Ceiling opening) 39.5 521(Hanging bolt) 39.5

450 (Hanging bolt) 75 75

269
570 Unit size

670 670

570 Unit size

Unit:mm

670

570 450

5

570

670

6

CLOSE

OPEN

OPEN

CLOSE

521

40
4

600 (Ceiling opening)
1 2 3

30

110 269 90 30 120.4

110 90 190.5 160

(unit : mm) Number 1 2 3 4 5 6 Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air suction grill Descripition ø6.35 flare 12k: ø9.52, 18k: ø12.7 flare

Service Manual 17

52

Dimensions

8. CST Type - TF (24K/30K)
790 (Ceiling opening) 109 572(Hanging bolt) 109

66
292 850 850

744 Unit size 744 Unit size

Unit:mm

850 744 658

5

850

572 744
6

70
4 1 2

117

110 90

110 90 150
3

292

66

790 (Ceiling opening)
212

192

30

(unit : mm) Number 1 2 3 4 5 6 Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air suction grill Descripition ø6.35 flare ø12.7 flare-24K, ø15.88 flare-30K

18 Multi type Air Conditioner

54

658 (Hanging bolt)

Dimensions

9. CST Type - TD(36K)
875 (Ceiling opening) 45 785 (Hanging bolt) 45

101.5 672 (Hanging bolt) 101.5
110

288 950 950

840 Unit size 840 Unit size

950

Unit:mm
840 678

950

5

6

55

840

4

785

40
1 2

30

290

110 90

875 (Ceiling opening)
52 180
3

Fresh Air Inlet

140

(unit : mm) Number 1 2 3 4 5 6 Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air suction grill Descripition ø6.35 flare ø15.88 flare

Service Manual 19

210.5

90

Dimensions

Outdoor Unit
D

W

W

L2

L1

D

H

30K/40K

H

L3

L4

L6

L5

L7

14K/16K/18K/24K
MODEL DIM W H D L1 L2 L3 L4 L5 L6 L7 mm mm mm mm mm mm mm mm mm mm

16K
800 555 262 340 37 544 11 590 105 105

14K,18K
870 655 320 370 25 775 25 546 160 160

24K
870 800 320 370 25 775 25 546 160 160

30K
870 1060 320 360 20 1040 20 550 160 165

40K
900 1165 370 460 45 1135 30 550 175 175

20 Multi type Air Conditioner

Dimensions

A7UW486FA0/A8UW566FA0 A8UQ566FA0
15 153 806 500(bolt hole) 153

730 700(bolt hole) 690

Air outlet
40

Air inlet Air inlet
1512 1444

Service Panel

670

220

Knockout hole (For the control wiring, the power supply, refrigerant connecting pipe)

100 28

Knockout hole (For the control wiring, the power supply, refrigerant connecting pipe)

(Unit : mm)

Service Manual 21

Product Specifications

Product Specifications
Indoor Unit
Indoor Unit Type Model Rated Cooling Capacity 5 Rated Heating Capacity 5 Air Circulation H/M/L Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L) Noise Level(Sound Press,1m) H/M/L Temperature controller Coil Tube Size (OD) Fins per inch No. of Rows & Column Dehumidification Rate Dimensions (W*H*D) Net Weight Piping Liquid Connection Gas Drain hose (ID Ø) Packing Dimension (W*H*D) Stuffing Quantity Without S/Parts Front Panel Color "5" Position kcal/hr(W) Btu/hr kcal/hr(W) Btu/hr CMM(CFM) °C W AMNH076LQL0 AMNH096LQL0 Wall Mounted AMNH096LRL0 2267(2638) 9000 2520(2929) 10000 8.5(300) 18~30 / 16~30 14.4 IC-8420LG48A 4 37 0.16 0.9 / 400 Cross Flow Fan 1/3.43(87) 1200/1100/1000 1200/1100/1000 35 / 33 / 31 Thermistor 0.197(5.0) 20 2R,12C 1.4 35.4*11.2*6.1(900*285*156) 8(17.6) 1/4 (6.35) 3/8 (9.52) 20 38.4*9.2*14.6(976*233*372) 338/714 (340/720) Morning Beige AMNH126LRL0 3024(3515) 12000 3326(3867) 13200 9.0(318) 18~30 / 16~30 14.4 IC-8420LG48A 4 37 0.16 0.9 / 400 Cross Flow Fan 1/3.43(87) 1290 / 1200 / 1120 1290 / 1200 / 1120 39 / 36 / 34 Thermistor 0.197(5.0) 20 2R,12C 1.8 35.4*11.2*6.1(900*285*156) 8(17.6) 1/4 (6.35) 3/8 (9.52) 20 38.4*9.2*14.6(976*233*372) 338/714 (340/720) Morning Beige AMNH186LTL0 4536(5275) 18000 4990(5803) 19800 13(459) 18~30 / 16~30 22 AMR-023E2 4 54 0.21 2.0 / 370 Cross Flow Fan 1/3.74(95) 1140 / 1040 / 940 1140 / 1040 / 940 42 / 39 / 36 Thermistor 0.276(7.0) 20 2R,13C 2.0 42.9*12.4*6.8(1090*314*172) 12(26.5) 1/4 (6.35) 1/2 (12.7) 20 45.9*10.0*15.3(1165*255*388) 264/536 (270/540) Morning Beige AMNH246LTL0 5544(6446) 22000 6099(7091) 24200 14(494) 18~30 / 16~30 29 AMR-023E5 6 59 0.21 2.0 / 370 Cross Flow Fan 1/3.74(95) 1260 / 1140 / 1000 1260 / 1140 / 1000 46 / 43 / 39 Thermistor 0.276(7.0) 20 2R,13C 2.5 42.9*12.4*6.8(1090*314*172) 12(26.5) 1/4 (6.35) 1/2 (12.7) 20 45.9*10.0*15.3(1165*255*388) 264/536 (270/540) Morning Beige

W A µF/Vac EA/inch(mm) rpm rpm dBA inch(mm)

l/h inch(mm) kg(lbs) inch(mm) inch(mm) mm inch(mm) 20/40ft

1764(2051) 2267(2638) 7000 9000 2016(2343) 2520(2929) 8000 10000 5.5(194) 8.5(300) 18~30 / 16~30 18~30 / 16~30 8.4 8.4 IC-8415LG62A IC-8415LG62A 4 4 25 25 0.11 0.11 0.9 / 400 0.9 / 400 Cross Flow Fan Cross Flow Fan 1/3.43(87) 1/3.43(87) 1080 / 970 / 880 1170 / 1100 / 1020 1080 / 970 / 880 1170 / 1100 / 1020 35 / 32 / 29 37 / 33 / 31 Thermistor Thermistor 0.197(5.0) 0.197(5.0) 19 19 2R,10C 2R,10C 1.0 1.2 32.4*10.2*6.1(824*260*155) 32.4*10.2*6.1(824*260*155) 7(15.4) 7(15.4) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 20 20 35.4*9.2*13.4(900*233*340) 35.4*9.2*13.4(900*233*340) 354/774 (360/780) 354/774 (360/780) Morning Beige Morning Beige

Indoor Unit Type Model Rated Cooling Capacity 5 Rated Heating Capacity 5 Air Circulation H/M/L Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L) Noise Level(Sound Press,1m) H/M/L Temperature controller Coil Tube Size (OD) Fins per inch No. of Rows & Column Dehumidification Rate Dimensions (W*H*D) Net Weight Piping Liquid Connection Gas Drain hose (ID Ø) Packing Dimension (W*H*D) Stuffing Quantity Without S/Parts Front Panel Color "5" Position kcal/hr(W) Btu/hr kcal/hr(W) Btu/hr CMM(CFM) °C W AMNH076DZ*0

ART COOL DELUXE AMNH096DU*0 AMNH126DU*0

ART COOL AMNH096AP*1 AMNH126AP*1

W A µF/Vac EA/inch(mm) rpm rpm dBA inch(mm)

l/h inch(mm) kg(lbs) inch(mm) inch(mm) mm inch(mm) 20/40ft

1764(2051) 2267(2638) 2772(3224) 7000 9000 12000 1940(2257) 2495(2901) 3049(3546) 8000 10000 13200 5.5(194) 8.5(300) 9.0(318) 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 4.7 7.8 7.8 OBM-1547P2 OBM-1547P2 OBM-1547P2 4 4 4 27 40 40 0.12 0.18 0.18 0.9/400 0.9/400 0.9/400 Cross Flow Fan Cross Flow Fan Cross Flow Fan 1/3.43(87) 1/3.43(87) 1/3.43(87) 1330/1230/1130 1320/1220/1120 1400/1300/1200 1330/1230/1130 1320/1220/1120 1400/1300/1200 35 / 32 / 29 37 / 33 / 31 39 / 36 / 34 Thermistor Thermistor Thermistor 0.197(5.0) 0.197(5.0) 0.197(5.0) 19 19 19 2R,12C 2R,12C 2R,12C 1.0 1.2 1.5 42.9*12.4*6.8(1090*314*172) 35.4*10.7*5.3(900*272*135) 40.6*11.4*6.0(1030*290*153) 8.1(17.9) 9.5(20.9) 9.5(20.9) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8(9.52) 3/8(9.52) 3/8(9.52) 20 20 20 38.8*8.7*14.3(985*220*363) 44.0*8.9*14.8(1117*225*377) 44.0*8.9*14.8(1117*225*377) 340/720 324/684 324/684 R:Mirror, M:Metal, N:Walnut, W:White, B:Blue, C:Cherry

2267(2638) 2772(3224) 9000 12000 2520(2929) 3049(3546) 10000 13200 7.5(264) 8.5(300) 18~30 / 16~30 18~30 / 16~30 24 24 SIC-39CV-D828-1 SIC-39CV-D828-1 8 8 18 18 0.08 0.08 Turbo Fan Turbo Fan 1/24.32(617.7) 1/24.32(617.7) 510/350/290 560/460/360 510/350/290 560/460/360 38 / 35 /32 43 / 40 / 33 Thermistor Thermistor 0.197(5.0) 0.197(5.0) 20 20 2R,20C 2R,20C 1 1.2 22.4*22.4*5.4 (570*568*137) 22.4*22.4*5.4 (570*568*137) 9(19.84) 9(19.84) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8(9.52) 20 20 25.7*25.2*8.5(653*641*216) 25.7*25.2*8.5(653*641*216) 239/539 239/539 M:Metal, B:Blue, D:Wood

Note : 1.5 See the page "Combination Table" 2. Due to our policy of innovation some specifications may be changed without notification.

22 Multi type Air Conditioner

Product Specifications Indoor Unit
Indoor Unit Type Model Rated Cooling Capacity 5 kcal/hr(W) Btu/hr kcal/hr(W) Btu/hr CMM(CFM) mmAq °C W Ceiling Cassette - 1way AMNH096TCC0 Ceiling Cassette - 4way AMNH306TFC0 AMNH366TDC0 9072(10551) 36000 9979(11600) 39600 25/23/21(883/812/742) 18~30 / 16~30 52.5 IC-1630LGPJ 6 175 0.8 4/450 Turbo Fan 1/15.0(382) 550/510/470 550/510/470 40/38/36 Thermistor 0.275(7) 21 2R12C 4 33.0*33.0*11.3(840*840*288) 37.4*37.4*1.2(950*950*30) 32(70.5) 1/4 (6.35) 1/2 (12.7) 32 36.4*13.8*36.4(925*350*925) 30/64(36/72)

AMNH126TCC0 AMNH(C)126TEC0 AMNH186(C)TEC0 AMNH(C)246TFC0 3024(3515) 12000 3326(3867) 13200 10(353) 18~30 / 16~30 14 AMR-023E7 4 50 0.56 0.9/400 Cross Flow Fan 1/4(102) 1000 / 900 / 800 1000 / 900 / 800 37 / 33 / 29 Thermistor 0.275(7) 18 2R11C 1.5 33.8*15.3*7(860*390*190) 41.3*18.9*1.2(1050*480*30) 22(48.5) 1/4 (6.35) 3/8(9.52) 32 38.6*10.0*18.1(980*255*460) 263/539 3024(3515) 12000 3326(3867) 13200 11(353) 18~30 / 16~30 18.4 IC-9630LGAE 6 75 0.35 2.5/440 Turbo Fan 1/13.0(330) 670 / 620 / 550 670 / 620 / 550 38 / 35 / 32 Thermistor 0.275(7) 19 2R11C 1.2 22.4*10.5*22.4 (570*269*570) 26.4*26.4*1.2(670*670*30) 19(41.9) 1/4 (6.35) 3/8(9.52) 32 25.2*13.0*25.2(640*330*640) 189/378

2267(2638) 9000 2520(2929) Rated Heating Capacity 5 10000 9(317) Air Circulation H/M/L External Static Pressure 18~30 / 16~30 Setting temperature range 14 Fan motor Output AMR-023E7 Model 4 No. of Poles 50 Input W 0.56 Running Current A 0.9/400 Capacitor µF/Vac Cross Flow Fan Fan Type 1/4(102) No. Used / Diameter EA/inch(mm) 900 / 800 / 700 Fan RPM Cooling(H/M/L) rpm 900 / 800 / 700 Heating(H/M/L) rpm 35 /32 / 28 Noise Level(Sound Press,1m) H/M/L dBA Thermistor Temperature controller 0.275(7) Coil Tube Size (OD) inch(mm) 18 Fins per inch 2R11C No. of Rows & Column 1.2 Dehumidification Rate l/h Dimensions (W*H*D) Indoor inch(mm) 33.8*15.3*7(860*390*190) Panel inch(mm) 41.3*18.9*1.2(1050*480*30) 22(48.5) Net Weight kg(lbs) 1/4 (6.35) Piping Liquid inch(mm) 3/8(9.52) Connection Gas inch(mm) 32 Drain hose (ID Ø) mm 38.6*10.0*18.1 Packing Dimension (W*H*D) inch(mm) 263/539 Stuffing Quantity Without S/Parts 20/40ft

4536(5275) 6048(7033) 7056(8206) 18000 24000 28000 4990(5803) 6653(7736) 7761(9027) 19800 26400 30800 13(459) 15/14/13(53/494/459) 18(636) 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 22.4 40.3 45 IC-9630LGAC OBM-350292 OBM-401592 6 6 6 90 121 146 0.75 0.53 0.67 2.5/440 4/440 4/440 Turbo Fan Turbo Fan Turbo Fan 1/13.0(330) 1/15.0(382) 1/15.0(382) 720 / 670 / 620 600/540480 660/590/530 720 / 670 / 620 600/540480 660/590/530 41 /39 / 37 43/41/39 44/41/39 Thermistor Thermistor Thermistor 0.275(7) 0.275(7) 0.275(7) 19 21 21 2R11C 2R12C 2R12C 2.4 3 3.5 22.4*10.5*22.4 (570*269*570) 29.3*11.5*29.4 (744*292*744) 29.3*11.5*29.4 (744*292*744) 26.4*26.4*1.2(670*670*30) 33.5*33.5*1.2(850*850*30) 33.5*33.5*1.2(850*850*30) 19(41.9) 24(52.9) 24(52.9) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 32 32 32 25.2*13.0*25.2(640*330*640) 32.6*14.4*32.6 (828*365*828) 32.6*14.4*32.6 (828*365*828) 189/378 84/168 84/168

Indoor Unit Type Model Rated Cooling Capacity Rated Heating Capacity Air Circulation H/M/L External Static Pressure Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L) Noise Level(Sound Press,1m) H/M/L Temperature controller Coil Tube Size (OD) Fins per inch No. of Rows & Column Dehumidification Rate Dimensions (W*H*D) Net Weight Piping Liquid Connection Gas Drain hose (ID Ø) Packing Dimension (W*H*D) Stuffing Quantity Without S/Parts Front Panel Color "*" Position kcal/hr(W) Btu/hr kcal/hr(W) Btu/hr CMM(CFM) mmAq °C W AMNH096BTG0 AMNH126BTG0

Ceiling Concealed Duct AMNH186BTG0 AMNH096BPA0 2268(2637) 9000 2520(2930) 10000 11.5/10/8.5 4 18~30 118 IC-13450LG31A 4 180 4.3 6/370 Sirocco Fan 1/Ø177 1125/990/870 1125/900/870 38/36/34 Thermistor 0.276(7.0) 18 2R14C 1.6 750*300*580(695*56.5*396) 30(6) 1/4(6.35) 3/8(9.52) 25.4(OD) 845*370*760(735*90*435) 228/468 NOBEL WHITE AMNH126BPA0 3024(3516) 12000 3326(3868) 13200 11.5/10/8.5 4 18~30 118 IC-13450LG31A 4 180 4.3 6/370 Sirocco Fan 1/Ø177 1125/990/870 1125/990/870 38/36/34 Thermistor 0.276(7.0) 18 3R14C 2 750*300*580(695*56.5*396) 30(6) 1/4(6.35) 3/8(9.52) 25.4(OD) 845*370*760(735*90*435) 228/468 NOBEL WHITE

W A µF/Vac EA/inch(mm) rpm rpm dBA inch(mm)

l/h inch(mm) kg(lbs) inch(mm) inch(mm) mm inch(mm) 20/40ft

2268(2637) 3024(3516) 4536(5274) 9000 12000 18000 2520(2930) 3326(3868) 4990(5802) 10000 13000 19800 8/7/6(282/246/211) 10/9/8(352/317/282) 13.5/12/10(477/424/353) 2 2 2 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 35 35 47 YDK110-35-4L YDK110-35-4L YSK110-70-4L 4 4 4 68 68 126 0.31 0.31 0.58 2.5/400 2.5/400 2.5/370 Sirocco Fan Sirocco Fan Sirocco Fan 1/7.8(197) 1/7.8(197) 2/7.8(197) 930/840/810 950/850/780 1000/900/800 930/840/810 950/850/780 1000/900/800 34/32/30 37/34/31 38/36/34 Thermistor Thermistor Thermistor 0.276(7.0) 0.276(7.0) 0.276(7.0) 18 18 18 2R,12C 3R,12C 2R, 12C 1 1.2 2 25.6*9.0*21.1(650*230*535) 25.6*9.0*21.1(650*230*535) 39.4*9.0*21.1(1000*230*535) 22(48.5) 22(48.5) 29(63.9) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 1/2 (12.7) 25.4 25.4 25.4 29.9*24.6*11.8(760*625*300) 29.9*24.6*11.8(760*625*300) 29.9*24.6*11.8(760*625*300) 172/356 172/356 123/251 -

Note : 1.5 See the page "Combination Table" 2. Due to our policy of innovation some specifications may be changed without notification.

Service Manual 23

Product Specifications Indoor Unit
Indoor Unit Type Model Rated Cooling Capacity Rated Heating Capacity Air Circulation H/M/L External Static Pressure Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L) Noise Level(Sound Press,1m) H/M/L Temperature controller Coil Tube Size (OD) Fins per inch No. of Rows & Column Dehumidification Rate Dimensions (W*H*D) Net Weight Piping Liquid Connection Gas Drain hose (ID Ø) Packing Dimension (W*H*D) Stuffing Quantity Without S/Parts Indoor Unit Type Model Rated Cooling Capacity Rated Heating Capacity Air Circulation H/M/L External Static Pressure Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L) Noise Level(Sound Press,1m) H/M/L Temperature controller Coil Tube Size (OD) Fins per inch No. of Rows & Column Dehumidification Rate Dimensions (W*H*D) Net Weight Piping Liquid Connection Gas Drain hose (ID Ø) Packing Dimension (W*H*D) Stuffing Quantity Without S/Parts kcal/hr(W) Btu/hr kcal/hr(W) Btu/hr CMM(CFM) mmAq °C W AMNH096VEA0 kcal/hr(W) Btu/hr kcal/hr(W) Btu/hr CMM(CFM) mmAq °C W AMNH186BHA0 Ceiling Concealed Duct AMNH246BHA0 AMNH306BGA0 AMNH366BGA0

W A µF/Vac EA/inch(mm) rpm rpm dBA inch(mm)

l/h inch(mm) kg(lbs) inch(mm) inch(mm) mm inch(mm) 20/40ft

4536(5275) 6048(7034) 7560(8792) 9072(10551) 18000 24000 30000 36000 4990(5803) 6653(7737) 8316(9671) 9979(11606) 19800 26400 33000 39600 16.5/14.5/13(583/512/459) 18/16.5/14(636/583/494) 28/25/23(989/883/812) 32/29/26.5(1130/1024/936) 8 8 8 8 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 118 118 124 272 IC-13450LG13C IC-13450LG13C IC-13450LG13J IC-13450LG13A 4 4 4 4 180 180 250 323 0.92 0.92 1.1 1.42 6/370 6/370 6/370 6/370 Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan 2/6.97(177) 2/6.97(177) 2/6.97(177) 2/6.97(177) 1356/-/1270 1417/1350/1255 1415/1360/1290 1415/1360/1290 1356/-/1270 1417/1350/1255 1415/1360/1290 1415/1360/1290 36/34/32 37/35/33 40/38/36 42/40/38 Thermistor Thermistor Thermistor Thermistor 0.275(7) 0.275(7) 0.275(7) 0.275(7) 21 21 21 21 3R10C 3R10C 3R 12C 3R 12C 2.0 2.5 3 3.5 34.6*10.2*17.7 (880*260*450) 34.6*10.2*17.7 (880*260*450) 46.4*11.7*17.7(1180*298*450) 46.4*11.7*17.7(1180*298*450) 35(77.2) 35(77.2) 38(83.8) 38(83.8) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/2(12.7) 1/2(12.7) 5/8(15.88) 5/8(15.88) 25.4(OD) 25.4(OD) 25.4(OD) 25.4(OD) 44.7*13.4*23.0(1135*340*585) 44.7*13.4*23.0(1135*340*585) 18.5*14.8*23.0(1435*375*585) 18.5*14.8*23.0(1435*375*585) 120/252 120/252 95/191 95/191 Ceiling & Floor(Convertible) AMNH126VEA0 AMNH186VBA0 AMNH(C)246VBA0

W A µF/Vac EA/inch(mm) rpm rpm dBA inch(mm)

l/h inch(mm) kg(lbs) inch(mm) inch(mm) mm inch(mm) 20/40ft

2268(2637) 3024(3516) 4536(5274) 6048(7032) 9000 12000 18000 24000 2520(2930) 3326(3867) 4990(5801) 6350(7384) 10000 132000 19800 25200 7.8/6.4/5.0(276/226/177) 10.0/8.3/6.5(353/293/230) 135./12/11(477/424/388) 15/13.5/12(530/477/424) 18-30/16-30 18-30/16-30 18~30 / 16~30 18~30 / 16~30 14.5 17.5 30 35 IC-18422LG31B IC-18422LG31A IC-9430LGCM IC-9430LGCM 4 4 4 4 35 43 53 63 0.18 0.23 0.23 0.27 1.5/370 1.5/370 1.5/370 1.5/370 Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan 1/3.7(95) 1/3.7(95) 1/3.1(80) 1/3.1(80) 960/870/760 1240/1120/900 1090/990/890 1160/1060/960 960/870/760 1240/1120/900 1090/990/890 1160/1060/960 36/32/28 40/36/31 43 / 40 / 37 45 / 42 / 39 Thermistor Thermistor Thermistor Thermistor 0.197(5) 0.197(5) 0.275(7) 0.275(7) 20 20 18 20 2R 12C 2R 12C 2R 12C 2R 14C 1 1.2 2.3 3.2 35.4*7.9*19.3 (900*200*490) 35.4*7.9*19.3 (900*200*490) 47.24*24.21*8.07(1200*615*205) 47.24*24.21*8.07(1200*615*205) 12(26.5) 12(26.5) 30(66.1) 30(66.1) 1/4 (6.35) 1/4 (6.35) 1/4(6.35) 1/4(6.35) 3/8 (9.52) 3/8 (9.52) 1/2(12.7) 1/2(12.7) 20 20 20 20 38.2*11.2*22.2 (970*285*565) 38.2*11.2*22.2 (970*285*565) 50*10.9*27(1272*278*686) 50*10.9*27(1272*278*686) 189/383 189/383 102/219 102/219

Note : 1.5 See the page "Combination Table" 2. Due to our policy of innovation some specifications may be changed without notification.

24 Multi type Air Conditioner

Product Specifications Outdoor Unit - Multiple piping models
Model Cooling Capacity 5 kcal/hr W Btu/hr Heating Capacity 5 kcal/hr W Btu/hr Input 5 Running Current 5 Starting Current Power Supply Power Factor Max. Number of Connectable Indoor Units Compressor (Invertor) Compressor (Constant) Refrigerant Type O.L.P Type(model name) Type O.L.P Type(model name) Charge Type Control Coil Tube Size (OD) Fins per inch No. of Rows & Column/No. Fan Motor Model Output Capacitor Fan Type No. Used / Diameter Discharge Air Circulation Noise Level(Sound Press,1m) Defrosting SVC Valve Dimensions (W*H*D) Net Weight Power Supply Cable Interunit Cable Max. Interunit Piping Length Max. Installation Height Difference Stuffing Quantity Total of Each Room For One Room Indoor Unit~Outdoor Unit Indoor Unit~Indoor Unit Without S/Parts Liquid Gas inch(mm) inch(mm) inch(mm) kg(lbs) No.* mm2 No.* mm2 m m m m inch(mm) 20/40ft EA/inch(mm) Side / Top CMM(CFM) dBA µF/Vac W inch(mm) g(oz), type Cooling/Heating Cooling/Heating Cooling/Heating W A A Ø,V,Hz % % A2UQ166FA0 1159~4410 1348~5128 4600~17500 380~1600 1.7~7.3 8 1,220~240,50 94~98 2 Twin Rotary 950(33.5) at 7.5m R-410A L.E.V 0.276(7.0) 18 2R,24C OBM-3018P2 47 2.0/400 Propeller 1/16.5(420) Side Discharge 35(1236) 51 Invertion cycle 1/4 (6.35)*2EA 3/8 (9.52)*2EA 30.3*21.3*10 (770*540*245) 37(81.6) 3*2.5 4*0.75 (Includes earth) 30 20 15 7.5 36.2*22.8*14.2(920*580*360) 144/312 A2UW146FA0 1159~4031 1348~4688 4600~16000 1210~4535 1407~5274 4800~18000 380~1450/450~1350 1.6~6.5/2.0~5.8 1 1,220~240,50 94~98 2 e-Scroll 1650(59.97) at 7.5m R-410A L.E.V 0.276(7.0) 18 1R,28C IC28640LG28S 120 6/370 Propeller 1/18.1(460) Side Discharge 49(1730) 50/47 Invertion cycle 1/4 (6.35)*2EA 3/8 (9.52)*2EA 52(115) 3*3.5 4*0.75 (Includes earth) 40 25 15 7.5 34.2*25.8*12.6(870*655*320) 81/171 A2UW186FA0 A3UW186FA0 1159~5443 1348~6330 4600~21600 1210~6249 1407~7268 4800~24800 420~2400/480~2600 3.5~11.5/4~12 1 1,220~240,50 94~98 3 e-Scroll 1650(59.97) at 7.5m R-410A L.E.V 0.276(7.0) 18 2R,28C IC28640LG28S 120 6/370 Propeller 1/18.1(460) Side Discharge 49(1730) 51/48 Invertion cycle 1/4 (6.35)*3EA 3/8 (9.52)*3EA 75(165) 3*3.5 4*0.75 (Includes earth) 40 25 15 7.5 34.2*25.8*12.6(870*655*320) 81/171 A3UQ186FA1 1159~5443 1348~6330 4600~21600 1210~6249 1407~7268 4800~24800 420~2400/480~2600 3.5~11.5/4~12 1 1,220~240,50 94~98 3 e-Scroll 1650(59.97) at 7.5m R-410A L.E.V 0.276(7.0) 18 2R,28C IC28640LG28S 120 6/370 Propeller 1/18.1(460) Side Discharge 49(1730) 51/48 Invertion cycle 1/4 (6.35)*3EA 3/8 (9.52)*3EA 75(165) 3*3.5 4*0.75 (Includes earth) 40 25 15 7.5 81/171 A3UW246FA0 A4UW246FA0 1159~7257 1348~8,440 4600~28800 1210~8063 1407~9376 4800~32000 440~2970/560~2950 3.08~13.0/4.6~12.9 28 1,220~240,50 94~98 4 e-Scroll Rotary MRA99150-9090 1950(68.78) at 7.5m R-410A L.E.V 0.276(7.0) 18 2R,36C IC28640LG28J 130 6/370 Propeller 1/18.1(460) Side Discharge 53(1872) 51/48 Invertion cycle 1/4 (6.35)*4EA 3/8 (9.52)*4EA 75(165) 3*2.5 4*0.75 (Includes earth) 50 25 15 7.5 54/114 A4UW306FA0 1159~9072 1348~10549 4600~36000 2116~10332 2461~12014 8,400~41,000 450~3580/620~3580 3.2~15.7/4.6~15.7 28 1,220~240,50 95~98 4 e-Scroll Rotary INTERNAL 2500(88.18) at 7.5m R-410A L.E.V 0.276(7.0) 18 2R,48C IC9625LGSY 65 * 2 2.0/370 Propeller 2/16.5(420) Side Discharge 31(1094)*2 50/46 Invertion cycle 1/4 (6.35)*4EA 3/8 (9.52)*4EA 84(185) 3*2.5 4*0.75 (Includes earth) 70 25 15 7.5 51/111

34.3*31.5*12.6 (870*800*320) 34.3*31.5*12.6 (870*800*320) 34.3*31.5*12.6 (870*800*320) 34.3*31.5*12.6 (870*808*320) 34.3*31.5*12.6 (870*1038*320)

Packing Dimension (W*H*D)

34.2*25.8*12.6(870*655*320) 40.1*34.2*17.3 (1020*870*440) 40.1*34.2*17.3 (1045*1140*440)

Notes: 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB - Interconnecting Piping Length 7.5m - Interconnecting Piping Length 7.5 m - Level Difference of Zero. - Level Difference of Zero. 2. Capacities are Net Capacities. 3. 5 : See the page "Combination Table" 4. Due to our policy of innovation some specifications may be changed without notification.

Service Manual 25

Product Specifications Outdoor Unit - Distributor type models

Model Cooling Capacity5 kcal/hr W Btu/hr Heating Capacity5 W(kcal/hr) Btu/hr Input5 Running Current5 Starting Current Power Supply Power Factor Max. Number of Connectable Indoor Units Compresso (Invertor) Compressor (Constant) Refrigerant charge Type O.L.P Type(model name) Type O.L.P Type(model name) Charge Type Control Coil Tube Size (OD) Fins per inch No. of Rows & Column/No. Fan motor Model Output Capacitor Fan Type No. Used / Diameter Discharge Air Circulation Noise Level Defrosting SVC Valve Dimensions Net Weight Power Supply Cable Interunit Cable Max. Interunit Piping Length Total Piping Total Main Piping Total Branch Piping For One Room Max. Installation Height Difference Packing Dimension Stuffing Quantity Indoor Unit~Outdoor Unit Indoor Unit~Indoor Unit W*H*D With(Without) S/Parts m m m m m m inch(mm) 20/40ft Liquid Gas W*H*D Outdoor inch(mm) inch(mm) inch(mm) kg(lbs) No.* mm2 Outdoor Sound Press,1m EA/inch(mm) Side / Top CMM(CFM) dB(A)±1 W µF/Vac inch(mm) g(oz) Cooling/Heating Cooling/Heating Cooling/Heating W A A Ø,V,Hz %

A6UW406FA0 A6UQ406FA0 4032~12095 4689~14067 16,000~48,000 4838~13356 5627~15533 19,200~53,000 1695~4980/2343~4600 7.9~22/10.5~20.6 67 1,220~240,50 87.1~99.4 6 e-Scroll Internal Rotary Internal 4100(144.6) at 5m R-410A L.E.V 0.276(7.0) 18 2R,52C IC28640LG28J 120 * 2 6/370 Propeller 1/18.1(460) Side Discharge 53(1872) *2 60/-/57 Invertion cycle 3/8 (9.52) 3/4 (19.05) 35.4*45.8*14.5 (900*1,165*370) 110(242) 3*5.0 4*0.75 (Includes earth) 100 50 50 15 30 10 40.6*47.7*17.1 (1032*1212*436) 22/48

A7UW486FA0 4032~14515 4689~16878 16000~57600 4838~16027 5627~18636 19200~63600 750~5810/1450~5830 3.4~26/6.6~24.3 43 1,220~240,50 90~97 7 e-Scroll Internal Rotary Internal 7100(250.4) at 5m R-410A L.E.V 0.276(7.0) 18 ARE676E01 270 10/370 Propeller 1/20.7(526) Top discharge 90(3179) 59/56 Invertion cycle 3/8(9.52) 3/4 (19.05) 31.7*59.5*28.7(806*1512*730) 110(242) 3*5.0 4*0.75 (Includes earth) 110 50 60 15 30 10 33.9*61.0*28.7(860*1550*730)

A8UW566FA0 A8UQ566FA0 4032~16934 4689~19691 16000~67250 4848~19051 5627~22152 19200~75600 750~6600/1550~6800 3.4~29.6/7.1~30.5 74 1,220~240,50 90~97 8 e-Scroll Internal Rotary Internal 7100(250.4) at 5m R-410A L.E.V 0.276(7.0) 18 ARE676E01 270 10/370 Propeller 1/20.7(526) Top discharge 90(3179) 59/56 Invertion cycle 3/8(9.52) 3/4 (19.05) 31.7*59.5*28.7(806*1512*730) 120(264) 3*5.0 4*0.75 (Includes earth) 120 50 70 15 30 10 33.9*61.0*28.7(860*1550*730)

Notes: 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB - Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB - Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB - Interconnecting Piping Length 7.5m - Interconnecting Piping Length 7.5 m - Level Difference of Zero. - Level Difference of Zero. 2. Capacities are Net Capacities. 3. 5 : See the page "Combination Table" 4. Due to our policy of innovation some specifications may be changed without notification.

26 Multi type Air Conditioner

Product Specifications LG Branch Distributor
Model Connectable Indoor Units Combination(Min~Max.) Casing color Powre Source Power Consumption Runing Current Refrigerant Dimensions Packing Dimension Net Weight Connecting Cable Piping Connection (Main) Piping Connection (Indoor Unit) Piping length (Max.) Piping Elevation (Max.) Drain hose Heat Insulation Accessories Hanger Screw EA EA 4 8 4 8 Direction Indoor Unit Direction Outdoor Unit Liquid Gas Liquid Gas Total Outdoor ↔ BD BD ↔ Indoor Outdoor ↔ Indoor Indoor ↔ Indoor m m m m m inch(mm) type charge W*H*D W*H*D kg mm mm kg No. * mm2 No. * mm2 inch(mm) W A Btu/h PMBD3640 1~4 7,000~24,000 Ø1 , 50/60Hz ,220~240/220V 10 0.05 R410A 302*143*252 422*202*300 5 4*0.75 (Includes earth) 4*0.75 (Includes earth) 3/4(19.05) 3/8 (9.52) 1/4 (6.35) 3/8 (9.52) 100 40 20 30 10 PMBD3630 1~3 7,000~24,000 Ø1 , 50/60Hz ,220~240/220V 10 0.05 R410A 302*143*252 422*202*300 5 4*0.76 (Includes earth) 4*0.76 (Includes earth) 3/4(19.05) 3/8 (9.52) 1/4 (6.35) 3/8 (9.52) 100 40 20 30 10 Not available Both Liquid and Gas pipes 4 8 4 8 PMBD3620 1~2 7,000~24,000 Ø1 , 50/60Hz ,220~240/220V 10 0.05 R410A 302*143*252 422*202*300 5 4*0.77 (Includes earth) 4*0.77 (Includes earth) 3/4(19.05) 3/8 (9.52) 1/4 (6.35) 3/8 (9.52) 100 40 20 30 10 PMBD7230 1~3 7,000~36,000 Ø1 , 50/60Hz ,220~240/220V 10 0.05 R410A 302*143*252 422*202*300 5 4*0.77 (Includes earth) 4*0.77 (Includes earth) 3/4(19.05) 3/8 (9.52) 1/4 (6.35) 3/8 (9.52) 100 40 20 30 10

Service Manual 27

Installation

Installation
Read completely, then follow step by step.

Select the best location of indoor unit
1. Split Type Indoor Unit
• There should not be any heat source or steam near the

Front Left Rear left Down right Right Rear right

unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

Connecting cable

Drain hose

2. Art Cool Type Indoor Unit
• Do not have any heat or steam near the unit. • Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 50cm. The unit should be installed as high on the wall as possible, allowing a minimum of 10cm from ceiling. • Use a stud finder to locate studs to prevent unnecessary damage to the wall.

More than 10cm More than 50cm

More than 50cm

More than 2m

28 Multi type Air Conditioner

Installation

3. Art Cool Deluxe Type Indoor unit
• Do not have any heat or steam near the unit. • Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 20cm. The unit should be installed as high on the wall as possible, allowing a minimum of 30cm from ceiling. • Use a stud finder to locate studs to prevent unnecessary damage to the wall.
More than 30cm More than 20cm

More than 30cm More than 2.3m

CAUTION

Install the indoor unit on the wall where the height from the floors more than 2.3 meters.

4. Duct Type Indoor Unit
Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight. • The place shall be able to inspect the unit as the figure.
600 1000

Top view
(unit: mm)

Inspection hole (600X600) Control box

• The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit

600

Front

Front view

H

5. CST Type Indoor Unit
• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have the maintenance space around.
50 or more Ceiling Ceiling Board 30 or more

• A place where drainage can be easily obtained.

Ceiling Board 30 or less Unit:cm

100 or more

Above 250 330 or less

50 or more

Floor

Service Manual 29

Installation

6. CVT Type Indoor Unit
• There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
R

More than 20cm More than 20cm
R

More than eye-level More than 20cm

(Ceiling installation)

More than 20cm

(Floor/Wall installation)

30 Multi type Air Conditioner

Installation

How to fix
1. Room Type Indoor Unit Installation
The mounting wall should be strong and solid enough to protect it from the vibration. 1) Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always mount the Installation plate horizontally by aligning the marking-off line by means of the thread and a level. 2) Drill the piping hole with 70mm dia. holecore drill. • Line according to the arrows marked on lower the left and the rght side of the Installation Plate. The meeting point of the extended line is the center of the hole. • Drill the piping hole at either the right or the left and the hole should be slightly slant to the outdoor side.

Installation Plate

Type "A" screw Weight

marking-off line Thread

The lower left and the right side of Installation Plate

C

Installation plate
D
Ø70mm

A
Right rear piping

Left rear piping

CHASSIS (Grade) SQ(7/9k) SR(9/12k) ST(18/24k)

Distance(mm) A 75 0 105 B 12 40 0 C 80 20 210 D 12 40 0

Service Manual 31

B
Ø70mm

Installation

2. Art Cool Type Indoor Unit
The wall you select should be strong and solid enough to prevent vibration 1) Open panel front • First,Pull the grille bottom, then remove screws (2 pieces), and close grille bottom again. • The moment of lifting the both lower parts of panel front, you can hear sound this panel came out, In this time panel front is separated • After pull down this panel a bit, and separate connecting wire with product.

2) Cover pipe and cover side remove • Remove two screws(for fixing cover pipe) • Pull up the cover side of desired connecting direction, then cover side is separated. • In case connecting direction is left or right, path through the hole of cover side.

CAUTION: After removing the pipe hole, cut the burr for safety.

Pipe hole

NOTE: When connecting pipe path through rear wall, don’t remove the hole. 3) Drain hose junction • Remove the rubber stopple of desired drain direction. • As the following picture, Insert drain hose in the handle of drain pan, and join drain hose and connecting hose.

Panel Front Connector

32 Multi type Air Conditioner

Installation s Sticking the installation guide map and fixing Indoor unit
1. Put an Installation Guide Map on the desired surface.
INSTALLATION GUIDE MAP

7. Drill the piercing part for connecting pipe as diameter 50mm. (In case of piercing rear surface)

Refer to No. 5 on this page when making a hole in the wall.

2. Make a hole with diameter of 6mm and depth of 30-35mm when piercing a screw point.
IN ST AII AT IO N GU ID EM AP

8. First, Drive the two points of the upper parts by screws. (Leave 10mm for hanging product)
mm

10

IN ST AL LA TIO N

3. Drive the fore plastic anchors into drilled points.
IN ST AL LA TIO N

GU

GU ID EM AP

9. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws.
Plastic anchors

Plastic anchors

4. Hang the hole of product at the upper screws. (In this time, Remove the map)
(Falling attention)
INS TAL LAT ION GUID EM AP

In case of nothing wrong in the matter, connect the pipe and the wire. (Installation manual reference)

Hanger hole (Rear side of product)

5. Check the fixed product with light power.

s Drill a hole in the wall
• Drill the piping hole with a ø50mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.

WALL Indoor Outdoor

6. Look at suited horizon by horizontal meter on the horizontal setting line, and Fix lightly the map by adhesive tape.
GU ID EM AP

Service Manual 33

5-7mm

Horizontality

(0.2~0.3")

IN ST AL LA TIO N

Installation

3. Art Cool Deluxe Type Indoor Unit
The wall you select should be strong and solid enough to prevent vibration 1) Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level.
Installation Plate

3). Drill a hole in the wall • Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.

WALL Indoor Outdoor

Type "A" screw

2) Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely. (SU)
C

Installation plate
D
Ø70mm

A
Right rear piping

Left rear piping

(SZ)
Installation plate
D C
Left rear piping

B

Ø70mm

A
Right rear piping

CHASSIS (Grade) SU (9k, 12k) SZ (7k)

Distance (mm) A 92 35 B 44 33 C 67 156 D 44 33

34 Multi type Air Conditioner

B

(3/16"~5/16")

5-7mm

Installation

4. Duct Type Indoor Unit - BH/BG chassis
Install the unit above the ceiling correctly.

A B

CASE 1
POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. (Unit:mm)
Dimension A B C D E F (G) H I Capacity 18k, 24k 932 880 355 45.5 450 30 87 750 163

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

H
Drainage hole

CASE 2
POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.
M10 Nut X4 (Local M10 SP. washer X 4 supply) M10 washer X4

NOTE:
• Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators.

M10 washer

X4

(Local M10 SP. washer X 4 supply) M10 Nut X4

Service Manual 35

1-3 mm

30k, 36k 1232 1180 355 45.5 450 30

87 830 186

I

F

(G)

D

C E

Installation

- BT chassis
Install the unit above the ceiling correctly.

A B

CASE 1
POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. (Unit:mm)
Dimension Capacity 9/12K 18K A 708 B 678 C 434 D 51 51 E 537 535 F G H 172 175

455 230 805 230

1060 1030 434

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

F
Drainage hole

CASE 2
POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

M10 Nut

X4

(Local M10 SP. washer X 4 supply) M10 washer X4

M10 washer

X4

(Local M10 SP. washer X 4 supply) M10 Nut X4

36 Multi type Air Conditioner

1-3 mm

G H

D

C E

Installation
C A

- BP chassis
Install the unit above the ceiling correctly.
G H

CASE 1
POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. (Unit:mm)
Capacity Dimension

A

B

C

D

E

F

G

H

I

J

K

B

9k/12k BTU/h 633 580 695 660 750 45 369 797 20 232 372

F

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

H
Drainage hole

CASE 2
POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

M10 Nut

X4 (Local M10 SP. washer X 4 supply) M10 washer X4

M10 washer

X4

(Local M10 SP. washer X 4 supply) M10 Nut X4

Service Manual 37

1-3 mm

I

D E

Installation

Piping and Drainage of Indoor Unit
1. Preparation of pipings
1) Cut the pipes and the cable. • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than the measured distance. • Cut the cable 1.5m longer than the length of the pipe.

Pipe cutter

90

Slanted

Rough

Pipe
2) Remove burrs. • Remove burrs from cut edges of pipes. • Turn the pipe end toward down to avoid the metal powder entering the pipe.

Reamer

CAUTION: If burrs are not removed, they may cause a gas leakage.

Point down

3) Flaring the pipes. • Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some refrgerant gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting. • Fit the copper pipe end into the Bar of flare tool about 0~0.5mm higher. (See illustration) • Flare the pipe ends. 4) Tape the flaring portion to protect it from the dust or damages.

"A": ø15.88 mm (5/8") ¡ 0~1.0 mm ø12.7 mm (1/2") ¡ 0~0.5 mm ø9.52 mm (3/8") ¡ 0~0.5 mm ø6.35 mm (1/4") ¡ 0~0.5 mm

Handle Yoke Cone

Bar Bar

Copper pipe

"A"
Clamp handle

Red arrow mark

= Improper flaring =

Inclined

Surface damaged

Cracked

Uneven thickness

When properly flared, the internal surface flare will evenly shine and be of even thickness. Since the flare part comes into contact with the connectors, carefully check the flare finish.

38 Multi type Air Conditioner

Installation

Connection of indoor unit piping
1. Split Type Indoor Unit
• Preparing the indoor unit's piping and drain hose for installation through the wall. • Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. • Replace the plastic tubing holder in the original position. 3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Loop Connecting cable Gas side piping Liquid side piping

Tubing holder
Drain hose

To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.

2 Pull 1 Press

NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. 4. Indoor unit installation • Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

CAUTION When install, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.

For left rear piping
1. Route the indoor tubing and the drain hose in the direction of rear left.

Connecting cable

Drain hose

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound). 5. Connecting the pipings to the indoor unit and drain hose to drain pipe.
Drain hose

• Align the center of the pipings and sufficiently tighten the flare nut by hand.

2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. • Do not connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later.

Indoor unit tubing

Flare nut

Pipings

Service Manual 39

Installation
• When extending the drain hose at the indoor unit, install the drain pipe.

For right rear piping
1. Route the indoor tubing and the drain hose to the required piping hole position.

Drain pipe

Indoor unit drain hose Vinyl tape(narrow) Adhesive

6. Wrap the insulation material around the connecting portion. • Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands Insulation material

2. Insert the piping, drain hose and the connecting cable into the piping hole.

Connecting cable Drain pipe

3. Insert the connecting cable into the indoor unit. • Don't connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later. 4. Tape the drain hose and the connecting cable. • Connecting cable
Connection pipe Vinyl tape (wide) Connecting cable Indoor unit pipe Wrap with vinyl tape

• Wrap the area which accommodates the rear piping housing section with vinyl tape.

Pipe Vinyl tape(narrow)

5. Indoor unit installation • Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Wrap with vinyl tape Pipe

• Hang the indoor unit from the hooks at the top of the installation plate. • Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.

Vinyl tape(wide) Drain hose

40 Multi type Air Conditioner

Installation
6) Connecting the pipings to the indoor unit and the drain hose to drain pipe. • Align the center of the pipings and sufficiently tighten the flare nut by hand. 8) Reroute the pipings and the drain hose across the back of the chassis.

Indoor unit tubing

Flare nut

Pipings Piping for passage through piping hole

• When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

9) Set the pipings and the drain hose to the back of the chassis with the tubing holder. • Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Indoor unit drain hose Vinyl tape (narrow) Adhesive

7) Wrap the insulation material around the connecting portion. • Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands Insulation material 1 Hook 2 Push

Tubing holder

• Wrap the area which accommodates the rear piping housing section with vinyl tape.
Connection pipe Vinyl tape (wide) Indoor unit piping Wrap with vinyl tape

10) Indoor unit installation • Remove the spacer. • Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Pipe Vinyl tape (narrow) Connecting cable Drain hose

Connecting cable

• Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section. Pipe
Drain hose Vinyl tape (narrow)

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Wrap with vinyl tape(wide)

Service Manual 41

Installation 2. Art Cool Type Indoor Unit
• Preparing the indoor unit's piping and drain hose for installation through the wall. 1) Route the indoor tubing and the drain hose in the direction of rear left or right. 2) Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit. • When extending the drain hose at the indoor unit, install the drain pipe.

Drain pipe

Indoor unit drain hose Adhesive Vinyl tape(narrow)

4) Wrap the insulation material around the connecting portion. • Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands Insulation material

Loop

Connecting cable Drain hose

Gas side piping Liquid side piping

NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.

• Wrap the area which accommodates the rear piping housing section with vinyl tape.

Connection pipe Vinyl tape (wide) Wrap with vinyl tape

Indoor unit pipe

3) Connecting the pipings to the indoor unit and drain hose to drain pipe. • Align the center of the pipes and sufficiently tighten the flare nut by hand.

Connecting cable

Pipe Vinyl tape(narrow)

Indoor unit tubing

Flare nut

Pipes

• Tighten the flare nut with a wrench.
Open-end wrench (fixed)

• Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Wrap with vinyl tape Pipe

Flare nut Wrench Indoor unit tubing Connection pipe Vinyl tape(wide) Drain hose

42 Multi type Air Conditioner

Installation s Panel Assembly
1. First, Check the side cover assembly exactly, Fix power cord in the bottom groove of cover side left.

2. Assemble connecting lead wire with controller and first fix the upper part of panel front, then match the lower part of panel front

Panel Front Connector

3. Drive two screws.

Service Manual 43

Installation 3. Art Cool Deluxe Type Indoor Unit
Connection of piping Indoor • Preparing the indoor unit's piping and drain hose for installation through the wall. • Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. • Replace the plastic tubing holder in the original position. (Optional) NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. 4. Indoor unit installation • Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting cable

Drain hose

For right rear piping
1. Route the indoor tubing and the drain hose in the direction of rear right.

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound). 4. Connecting the pipings to the indoor unit and drain hose to drain pipe. • Align the center of the pipes and sufficiently tighten the flare nut by hand.

Drain hose

Indoor unit tubing

Flare nut

Pipes

• Tighten the flare nut with a wrench.

2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. • Do not connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later. 3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

Open-end wrench (fixed) Flare nut Wrench Indoor unit tubing Connection pipe

• When extending the drain hose at the indoor unit, install the drain pipe.

Tape Connecting pipe Drain hose

Connecting cable

44 Multi type Air Conditioner

Installation
5. Wrap the insulation material around the connecting portion. • Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands Insulation material

4. Tape the drain hose and the connecting cable. • Connecting cable

• Wrap the area which accommodates the rear piping housing section with vinyl tape.
Connection pipe Vinyl tape Wrap with vinyl tape (wide) Connecting cable Indoor unit pipe

5. Indoor unit installation • Hang the indoor unit from the hooks at the top of the installation plate. • Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Indoor unit Spacer

Pipe

Installation plate
Vinyl tape(narrow)

8cm

• Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Wrap with vinyl tape Pipe

6. Connecting the pipings to the indoor unit and the drain hose to drain pipe. • Align the center of the pipes and sufficiently tighten the flare nut by hand.

Vinyl tape(wide) Drain hose

Indoor unit tubing

Flare nut

Pipes

For left rear piping
1. Route the indoor tubing and the drain hose to the required piping hole position.

• Tighten the flare nut with a wrench.
Open-end wrench (fixed) Flare nut Wrench Indoor unit tubing Connection pipe

2. Insert the piping, drain hose, and the connecting cable into the piping hole.

• When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

Connecting cable Drain pipe
Adhesive Indoor unit drain hose Vinyl tape (narrow)

3. Insert the connecting cable into the indoor unit. • Don't connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later.

Service Manual 45

Installation
7. Wrap the insulation material around the connecting portion. • Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands Insulation material

9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. • Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.

Tubing holder

• Wrap the area which accommodates the rear piping housing section with vinyl tape.
Connection pipe Vinyl tape (wide) Wrap with vinyl tape Pipe Vinyl tape(narrow) Connecting cable Indoor unit piping

10. Indoor unit installation • Remove the spacer. • Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting cable

Drain hose

• Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Pipe Drain hose Vinyl tape(narrow)

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Wrap with vinyl tape(wide)

8. Reroute the pipings and the drain hose across the back of the chassis.

Piping for passage through piping hole

46 Multi type Air Conditioner

Installation

CAUTION
• Bad case s Following bending type from right to left could cause problem of pipe damage.

Installation Information (For left piping) • Good case For left piping. Follow the instruction below. • Press on the upper side of clamp. ( )

• Bend the tubing to the left side of chassis.

• Bend the tubing to the left side of chassis.

Service Manual 47

Installation

4. Duct Type Indoor Unit
1) Indoor Unit Installation • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

Old building
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

New building

1 Set anchor 2 Plate washer 3 Spring washer 4 Nut 5 Suspension bolts
• Local supply ➀ Set anchor ➁ Plate washer ➂ Spring washer ➃ Nut ➄ Suspension bolt

CAUTION: Tighten the nut and bolt to prevent unit falling.

- M10 - M10 - W3/8 or M10 - W3/8 or M10

48 Multi type Air Conditioner

Installation

5. CVT Type Indoor Unit - VB chassis
s Before Installing, prepare Installation Plates • 'Installation Plates' are attached at the bottom of indoor unit. Detach them by removing each 3 screws at both sides. • Detach 'Side Plate (R,L)' by removing each 2 screws on both sides. • Pull the upper right and left side of 'Inlet Grille' to the front, and it will stop at slightly tilted position. • Unhook the 'Inlet hanger' from the 'Hanger screw' on the both left and right side. • Detach the 'Inlet Grille' from the Indoor Unit.
Side Plate
R

Install Plate

Inlet hanger
R

1) Installation on the ceiling
• Measure and mark the position for the Suspension bolts and the piping hole. • Drill the hole for anchor nut on the ceiling.
Inlet Grille

Hanger screw 1076 265

1)

Before secure the Installation Plates, select the bent direction of the Installion Plate to the inside or the outside according to the installation circumstances.

Suspension bolt

Center-line for the piping hole 265

2)

1236

• Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
Indoor
WALL

Outdoor 5~7mm

Service Manual 49

Installation

• Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the anchor-nuts firmly. • Secure the Installation plates onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers.

1)
Nut

Anchor nut Ceiling

Washer

Suspension bolts

Suspension bolts Spring washer Nut

max. 12mm

Washer

2)

• Engage 2 hooks on the both left and right side of the unit to the lower slot of Installation Plates. • Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts. • Move the hooks on the unit to the upper slot of Installation Plates. Then the unit will be declined to the bottomside so as to drain well.

Lower slot Level gauge

R

Suspension bolt

Adjust a level

Installation plate

R

Upper slot

R

50 Multi type Air Conditioner

Installation

- VE chassis
The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level.
Type "A" screw Installation Plate

2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.

C

Installation plate
D
Ø70mm

A
Right rear piping

Left rear piping

CHASSIS (Grade) VE

Distance (mm) A 180 B 115 C D 115 E 50
D C E

Installation plate
A B

B
Ø70mm

Left rear piping

Right rear piping

Ø70mm

Mounting the anchor Nut & Bolt (Ceiling Mounting)
• Prepare 4 suspension bolts (Each bolts length should be same.) • Measure and mark the position for the Suspension bolts and the piping hole. • Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the anchor-nuts firmly.

Service Manual 51

Installation
• Secure the Installation plates onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers. • Engage 2 hooks on the both left and right side of the unit to the lower slot of Installation Plates. • Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts. • Move the hooks on the unit to the upper slot of Installation Plates. Then the unit will be declined to the bottomside so as to drain well.

Anchor nut Ceiling Nut Suspension bolts

Washer

235 820

Suspension bolt

Center-line for the piping hole

Suspension bolts Spring washer Hangen Max. 12mm Nut

Washer

Drill a Hole in the Wall
• Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
WALL Indoor Outdoor

52 Multi type Air Conditioner

(3/16"~5/16")

5-7mm

Installation

CAUTION: Installation Information For Declination CAUTION

1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 7mm. 3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.

Front of view
• The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling

Drain hose Ceiling

Side of view
• The unit must be declined to the bottomside of the unit when finished installation.

Ceiling

Service Manual 53

Installation
• Secure the unit to the Installation Plates with four M8 bolts and washers.

R

• Before working, refer to "Connecting pipe and cable to Indoor Unit".
• Hook up the Inlet Grille Hook to the cabinet. • Hang the Inlet Hanger to the screw.
Inlet hanger

R

Hook Cabinet Bottom

• Fit the projection hooks of the side plates to the 'Side Panel' and the 'Front Panel' by lifting it. • Fasten the screws.
2

R

1

R

54 Multi type Air Conditioner

Installation 2) Installation on the Wall
• Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor nut on the wall.
1076 mor e th 260 an

265

• Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
Wall Indoor Outdoor

• Secure the 'Install Plate' onto the wall with four anchor bolts, washers and spring washers.
Spring washer

Wall

Nut

Washer Anchor nut

Less than 12mm

Before secure the Install Plates, select the bent direction of the 'Install Plate' to the inside or outside according to the installation circumstances.

123

6

Service Manual 55

5~7mm

Installation
Install the Indoor unit onto Installation Plate. • Insert 2 hooks on the both left and right side of the unit to the inner slot (wall side) of the Installation Plate. • Secure the unit to the Installation Plate with four M8 bolts and washers.

Inner slot

R

• Before working, refer to "Connecting pipe and cable to Indoor Unit".
• Hook up the Inlet Grille Hook to the cabinet. • Hang the Inlet Hanger to the screw.

2

1

• Fit the projection hooks of the side plates to the 'Side Panel' and the 'Front Panel' by lifting it. • Fasten the screws.

56 Multi type Air Conditioner

Installation 3) Installation on the floor
Installation of Mount Bracket. • Select and mark the position for Mount Brackets and the piping hole. • Drill the hole for the anchor nut on the wall. • Drill the piping hole using a ø70 hole-core drill. • Secure the Mount Brackets on the wall with four M4 screws. Install the indoor unit onto the Mount Brackets. • Engage the slot at the back of the unit with Mount Bracket.

From the left wall more than 760mm From the right wall more than 840mm

Slot Floor mount bracket

448mm

• Drill the piping hole with 70mm dia, hole core drill. • Piping hole should be slightly slant to the outdoor side.

Wall Indoor Outdoor

After Installing, reassemble detached parts. • Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the Hanger Screw. • Assemble the 'Side Plates(R,L)' with 2 screws on both left and right side.

Slot Wall

Floor mount bracket Install plate Piping hole

Service Manual 57

5~7mm

Installation 6. Ceiling Cassette Type Indoor Unit

- TC chassis
1) Ceiling opening dimensions and hanging bolt location
• The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.
1,000 (Ceiling opening) 931.6 893.4 (Hanging bolt) 860 430 (Ceiling opening) 390
328.4 (Hanging bolt) 30.8

Ceiling Level gauge

CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires. • Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

Ceiling board

NOTE:
• Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

58 Multi type Air Conditioner

Installation

2) Indoor Unit Installation
Ceiling Hanging bolt (W3/8 or M10) Nut (W3/8 or M10) Spring washer (M10) Keep the length of the bolt from the bracket to 40mm Flat washer for M10 (accessory) Ceiling board

Air Conditioner body

Ceiling board

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Paper model for installation

Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model

Adjust the same height

• The following parts are local purchasing. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10

• Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.

Wall Indoor Outdoor

CAUTION • Tighten the nut and bolt to prevent unit from falling off.

Service Manual 59

5~7mm

103mm

Installation 7. Ceiling Cassette Type Indoor Unit

- TE/TF/TD chassis
1) Ceiling opening dimensions and hanging bolt location
• The dimensions of cardboard for installing are the same as those of the ceiling opening dimensions.
600 (Ceiling opening) 39.5 521(Hanging bolt) 39.5

TE

75 570 Unit size

Level gauge

570 Unit size

CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, be careful not to damage electric wires.
790 (Ceiling opening) 109 572(Hanging bolt)

75
109

450 (Hanging bolt)

Ceiling

Unit:mm

66 744 Unit size

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

744 Unit size

Ceiling board

875 (Ceiling opening) 45 785 (Hanging bolt) 45

66
Unit:mm

101.5 672 (Hanging bolt) 101.5

840 Unit size 840 Unit size

Unit:mm

60 Multi type Air Conditioner

875 (Ceiling opening)

790 (Ceiling opening)

658 (Hanging bolt)

600 (Ceiling opening)

TF

TD

Installation

NOTE:
• Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

2) The Indoor Unit Installation
Ceiling Hanging bolt (W3/8 or M10) Nut (W3/8 or M10) Spring washer (M10) Keep the length of the bolt from the bracket to 40mm Flat washer for M10 (accessory) Ceiling board Air Conditioner body

Ceiling board

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Cardboard for installation

Set screw of cardboard (4 pieces) Open the ceiling board along the outer edge of the paper model

Adjust the same height

• The following parts are local purchasing. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10

• Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.

Wall Indoor Outdoor

CAUTION

Service Manual 61

5~7mm

• Tighten the nut and bolt to prevent the unit from falling off.

150mm

Installation

Remote Controller Installation
• Although the room temperature sensor is in the indoor unit, the remote controller should be installed in such places away from direct sunlight and high humidity. Installation of the remote controller • Select places that are not splashed with water. • Select control position after receiving customer approval. • The room temperature sensor is built in the indoor unit. • This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult to see.(The standard height is 1.2 ~ 1.5m high) Routing of the remote controller cord • Keep the remote controller cord away from the refrigerant piping and the drain piping. • To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power cables (audio equipment, television set, etc.) • If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water droplets from running.

WIRED REMOTE CONTROL INSTALLATION
DISASSEMBLING
Front case
Th

• Separate the under plate from Remote control box.

el

ow er

pa

rt

Lever carefully the box open using a screw driver, etc.

Remote control box body

• Fix the under plate on the wall
Face of wall Under plate

• Fix the cord clamps on the wall by ø 3 tapping screws (accessory). • Fix the remote control cord.

Cord clamp (accessory)

Screw (accessory)

ELECTRICAL WIRING
(Main board)
CN REMO

Remote controller

Wire and make sure that teminal numbers are matched on unit side and remote controller side. The maximum length of the cord is 100m. If the length of the cord exceeds 50m, 2 use a wire size greater than 0.5mm .

62 Multi type Air Conditioner

Installation REMOTE CONTROL PREPARATION(OPTIONAL)
HOW TO MOUNT ONTO A WALL

HOW TO INSERT BATTERIES Remove the battery cover from the remote controller. • Slide the cover according to the arrow direction. Insert the two batteries. • Be sure that the (+) and (-) directions are correct. • Be sure that both batteries are new. Re-attach the cover. • Slide it back into position.

• Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and performance. • Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.

Service Manual 63

Installation

Connecting Pipings and the cable to Outdoor unit
1. Connecting the pipings to the Outdoor unit
1) When piping installation work you must be used the connector. Indoor Units 18K/24K 30K/36K Gas A¡B Ø9.52¡Ø12.7 Ø9.52 ¡Ø15.88 Liquid Not available Not available 2) Align the center of the pipings and sufficiently tighten the flare nut by hand

Connector

A

B

3) Finally, tighten the flare nut with torque wrench until the wrench clicks. s When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.

Outdoor unit
*Connecting pipe size Indoor Units 7K/9K/12K 18K/24K 30K/36K Gas side Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Liquid side Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4)

A-UNIT Gas side piping B-UNIT Liquid side piping

Torque wrench

CAUTION: After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source. 5) Confirm that electrical capacity is sufficient. 6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

64 Multi type Air Conditioner

Installation

CAUTION: If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Main power source

Circuit Breaker
Air Conditioner

18k~30k Btu
Circuit Breaker Use a 30A circuit breaker or time delay fuse.

25A 60A 75A

31k~40k Btu 41k~56k Btu

CAUTION
The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
ø8.5mm

The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H07RN-F approved by HAR or SAA).
ø7.5mm

GN

/YL 20

NORMAL CROSS SECTIONAL AREA 3.5mm2 (18k~30k Btu) 5.0mm2 (31k~56k Btu)
mm

GN

/YL 20

NORMAL CROSSSECTIONAL AREA 0.75mm2
mm

Service Manual 65

Installation

Checking the Drainage and Pipe forming
1. Split Type Indoor Unit
1) Remove the Grille from the cabinet • Set the up-and-down air direction louver to open position(horizontally) by finger pressure. • Remove the securing screws. • To remove the Grille, pull lower the left and right side of the grille toward you (slightly tilted) and lift it straight upward.

Screw
Pull the right and the left side.

2) Check the drainage • Pour a glass of water on the evaporator. • Ensure if water flows drain hose of indoor unit without any leakage.

2. Art Cool Type Indoor Unit
• Pour a glass of water on the evaporator. • Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

66 Multi type Air Conditioner

Installation

3. Art Cool Deluxe Type Indoor Unit
1) To remove the front panel from the indoor unit. • Set the air direction louvers up-and-down to the position(horizontally) by hand. • Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.

3) Drain piping • The drain hose should point downward for easy drain flow.
Downward slope

• Do not make drain piping.
Air filter
Do not raise

Inlet Grille
Water leakage

2) To check the drainage. • Pour a glass of water on the evaporator. • Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Connecting area drain hose

Accumulated drain water Air

Water leakage

Waving

Tip of drain hose dipped in water Water leakage

Leakage checking

Ditch

Less than 50mm gap

Service Manual 67

Installation

4. Convertible Type Indoor Unit
To remove the front panel from the indoor unit.
1. Set the air direction louvers up-and-down to the position(horizontally) by hand. 2. Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.

Pull the right and the left side.

To check the drainage.
1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

Drain piping
1. The drain hose should point downward for easy drain flow.
Downward slope

2. Do not make drain piping like the following.

Do not raise

Accumulated drain water Air

Tip of drain hose dipped in water Water leakage

Less than 50mm gap

Water leakage

Water leakage

Waving

Ditch

68 Multi type Air Conditioner

Installation

5. Duct Type Indoor Unit
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling
1~3mm
CORRECT

Drainage hole

INCORRECT

Drainage hole

CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
• Always lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part. • 5mm or thicker formed thermal insulator shall always be provided for the drain pipe.

Lay the drain hose with a downware inclination so water will drain out.
Thermal insulator (Local supply) Drainage pipe (Local supply)

Unit

Make sure to be closed.

Drainage hole

• Upward routing not allowed

700mm

(Drain pump model only)

INCORRECT Applied U-Trap Dimension
A ≥ 70mm B ≥ 2C C ≥ 2 x SP SP = External Pressure (mmAq) Ex) External Pressure = 10mmAq A ≥ 70mm B ≥ 40mm C ≥ 20mm

CORRECT

B C U-Trap A

• Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.

Service Manual 69

Installation

6. CST Type Indoor Unit
• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings • Be sure to install heat insulation on the drain piping. Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Pipe clamp Indoor unit

Upward routing not allowed

Maintenance drain port

1/50~1/100
MAX 700mm

Drain test
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose (accessory) Main drain pipe Drain port

Drain Pump

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is finished. • When the test is completed, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

70 Multi type Air Conditioner

Installation

Maximum Length of Pipe and Extra Charge of Refrigerant Charge
1. TPS Inverter Multi -Multi Piping Type
1.1 The maximun allowable level and piping length

[Outdoor Unit]

It does not matter which unit is higher.

[Indoor Unit] A

B 15m C 7.5m

D

Model [Outdoor Unit] A2UW146FA0 A2UW186FA0 A3UW186FA0 A3UW246FA0 A4UW246FA0 A4UW306FA0

Standard Length A,B,C,D 7.5m 7.5m 7.5m A

Max piping length each indoor unit B 25m 25m 25m C 25m 25m D 25m

Max total piping length

25m 25m 25m

40m(A+B) 50m(A+B+C) 70m(A+B+C+D)

1.2 Refrigerant Charge
Indoor Unit Capacity (Btu/h) Pipe Size Gas Liquid Rated Length Max Length Additional Refrigerant

7k, 9k, 12k 18k, 24k

3/8"(9.52mm) 1/2"(12.7mm)

1/4"(6.35mm) 1/4"(6.35mm)

7.5m 7.5m

25m 25m

25g/m 35g/m

❈ Extra refrigerant = (Extended length - Rated length) x Additional refrigerant

Service Manual 71

Installation

2. TPS Inverter Multi - Distributor Type
2.1 The maximum allowable level and piping length
Outdoor Unit Installation of the outdoor unit in an upper position

A

BD Unit

L1 L2

R

Place the BD unit and indoor units within a level distance of 10m from each other.

L3 30m B

BD Unit

L4 L5

10m

Main piping Branch piping L6

• Total main piping length : 50m( A + B ) • Total branch piping length : 50m(L1+L2+ L3+L4 +L5+L6) • Each branch piping length : 15m(L1,L2,L3,L4 ,L5,L6) • Total system piping length : 100m(40+60)
R

BD Unit
Place the BD unit and indoor units within a level distance of 10m from each other.

10m

BD Unit Outdoor Unit
30m

Installation of the outdoor unit in a lower position

72 Multi type Air Conditioner

Installation
• A7UW486FA0 Outdoor Unit

Installation of the outdoor unit in an upper position
A Place the BD unit and indoor units within a level distance of 10m from each other.

BD Unit

L1 L2

R

L3 30m B

BD Unit

L4 L5

10m

Main piping Branch piping L6

L7

• Total main piping length : 50m( A + B ) • Total branch piping length : 60m( L1+L2+ L3+L4 +L5+L6 +L7) • Each branch piping length : 15m( L1,L2,L3,L4 ,L5,L6 ,L7) • Total system piping length : 110m(50+60)
R

BD Unit
Place the BD unit and indoor units within a level distance of 10m from each other.

10m

BD Unit
30m

Outdoor Unit

Installation of the outdoor unit in a lower position

Service Manual 73

Installation
• A8UW486FA0 Outdoor Unit

Installation of the outdoor unit in an upper position
A Place the BD unit and indoor units within a level distance of 10m from each other.

BD Unit

L1 L2 L3 L4

R

30m

B

BD Unit

L5 L6

10m

Main piping Branch piping L7

L8

• Total main piping length : 50m( A + B ) • Total branch piping length : 70m(L1+L2+ L3+L4 +L5+L6 +L7 +L8) • Each branch piping length : 15m(L1,L2,L3,L4 ,L5,L6 ,L7 ,L8) • Total system piping length : 120m(50+70) R BD Unit
Place the BD unit and indoor units within a level distance of 10m from each other.

10m

BD Unit Outdoor Unit
30m

Installation of the outdoor unit in a lower position

74 Multi type Air Conditioner

Installation

2.2 Refrigerant charge
The calculation of the additional charge should be taken in account for the length of pipe.

A B

A6UW406FA0 charge = 4100g Additional charge (g)
A
A C

= + +

Total Main pipe length - rated length 7,9,12 k Branch pipe length - rated length 18,24 k Branch pipe length - rated length ( ❇ Rated length = 5m)

x 50g/m x 20g/m x 30g/m
B

a 7k

b 9k

c 9k

d 9k

e 18k

Total Amount (g)

= A + B • Total main pipe(A+B+C) = 30m • Each branch pipe(a, b, c, d, e) = 10m • Additional Charge = (30-5) x 50 + (10-5) x 20 x 4 + (10-5) x 30 = 1800g

Caution
Regulation for refrigerant leakage(in Europe) : the amount of refrigerant leakage should satisfy the following equation for human safety. Total amount of refrigerant in the system Volume of the room at which indoor unit of the least capacity is installed

0.3 ( kg / m3 )

❐ If the above equation can not be satisfied, then follow the following steps. - Selection of air conditioning system: select one of the next 1. Effective opening part Installation 2. Reconfirmation of outdoor unit capacity and piping length 3. Reduction of the amount of refrigerant 4. 2 or more security device installation of alarm for gas leakage - Change indoor unit type : installation position should be over 2m from the floor (Wall mounted type ¡ Cassette type) - Adoption of ventilation system : choose ordinary ventilation system or building ventilation system - Limitation in piping work : design for earthquake-proof and prevention against thermal stress

Service Manual 75

Installation 2.3 Piping connection size

A Liquid Gas mm mm Ø 9.52 Ø19.05

B Adjust to indoor unit piping size

BD Unit

A A

A

A6UW406FA0

B

B

B

B

B

B

Y-Branch

2.4 Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping.

In case more then 5m

CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of reliability. • Oil trap should be installed every 5~7 meters.

76 Multi type Air Conditioner

Installation

2.5 Y-Branch(Standard accessory)
[unit:mm]

Gas Pipe

Liquid Pipe

Ø19.05

Ø19.05 Ø19.05

Ø9.52

Ø9.52 Ø9.52

Y branch
A To Outdoor Unit A B B To BD Unit

• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
Horizontal plane Facing upwards

Within +/- 10°

A
Viewed from point A in direction of arrow

• There is no limitation on the joint mounting configuration. • If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter. • Branch pipe should be insulated with the insulator in each kit.

Tape (field supply)

Insulator (included with kit)

Liquid and gas pipe joints

Insulator for field piping

Service Manual 77

Installation

Test Running
SPLIT, ART cool, ART cool deluxe Type
1. Check that all tubing and wiring have been properly connected. 2. Check that the gas and liquid side service valves are fully open. 1) Prepare remote controller Remove the battery cover by pulling it according to the arrow direction. Insert new batteries making sure that the (+) and (–) of battery are installed correctly. Reattach the cover by pushing it back into position.
Bolt

Tubing connection

4) Evaluation of the performance Operate unit for 15~20 minutes, then check the system refrigerant charge: 1. Measure the pressure of the gas side service valve. 2. Measure the temperature of the intake and discharge of air. 3. Ensure the difference between the intake temperature and the discharge is more than 8°C (Cooling) or reversely (Heating).

NOTE: • Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries. • Remove the batteries from the remote controller if the system is not going to be used for a long time. 2) Precautions in test run s The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated. s For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compressor. Then attention must be paid. s Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later automatically) s The forced operation is started by pressing button for 2 seconds. (Cassette Type) The test run is started by pressing button for 5 seconds. (Cassette Type) The test run is started by pressing timer cancel button five times continuously. (Room type) s To cancel the test run, press any button. 3) Settlement of outdoor unit s Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount. s When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake. s In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.

Intake temperature

Discharge air

Discharge temperature Intake temperature
Discharge air

Discharge temperature

Intake temperature

Discharge air

Discharge temperature

78 Multi type Air Conditioner

Installation CVT Type 1) Connection of power supply
1. Connect the power supply cord to the independent power supply. • Circuit breaker is required. 2. Prepare the remote control. • Insert two batteries provided. Remove the battery cover from the remote controller. • Slide the cover according to the arrow direction. Insert the two batteries. (Two "R03" or "AAA" dry-cell batteries or equivalent.) • Be sure that the (+) and (-) directions are correct. • Be sure that both batteries are new. Re-attach the cover. • Slide it back into position. 3. Operate the unit for fifteen minutes or more.

2) Evaluation of the performance
1. Measure the temperature of the intake and discharge air. 2. Ensure the difference between the intake temperature and the discharge one is more than 8°C (Cooling) or reversely (Heating).
Thermometer
R

3) Selection of the slide switch according to installation method
1. In case the indoor unit is installed on the floor, please change the side switch which is on the Main PCB Assembly to the 'BOTTOM' state. 2. In case the indoor unit is installed under the ceiling, please change the slide switch which is on the Main PCB Assembly to the ' CEILING' state. The initial state of the slide switch is set for the bottom installation.

CN_INSTALL

CEILING BOTTOM

Service Manual 79

Installation Ceiling Cassette Type 1) PRECAUTIONS IN TEST RUN
• The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated. For test run, carry out the cooling operation first even during winter season. If heating operation is Caution carried out first, it leads to the trouble of compressor. Carry out the test run more than 5 minutes without stopping. (Test run will be cancelled 18 minutes later automatically) • The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time. • To cancel the test run, press any button.

CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured data, etc. • Measuring data are room temperature, outside temperature, suction temperature, blow out temperature, air velocity, air volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature. • As to the structure and appearance, check following items. ❏ Is the circulation of air adequate? ❏ Is the drainage OK? ❏ Is the heat insulation complete (refrigerant and drain piping)? ❏ Is there any leakage of refrigerant? ❏ Does the romote controller works properly? ❏ Is there any error on wiring? ❏ Aren't terminal screws loosened?

M4......118N.cm{12kgf.cm} M5......196N.cm{20kgf.cm} M6......245N.cm{25kgf.cm} M8......588N.cm{60kgf.cm}

80 Multi type Air Conditioner

Installation 5. Branch Distributor PRECAUTIONS FOR SELECTING THE LOCATION
The BD unit is for indoor use. Install in a location such as above a ceiling or behind a wall in accordance with the following conditions: • That the unit is fully supported, and is in a location with little or no vibration. • That the refrigerant pipes for the indoor and outdoor units can be repaired with ease, and that the units are placed well within the distance from each other allowed by the pipe length. • That there is nothing nearby that produces heat or steam(gas). • When installing, that there is enough carity for servicing the unit. • Do not install in location that is hot or humid for long periods of time. • A well-ventilated area. • Do not install near bedrooms. The sound of refrigerant flowing through the piping may sometimes be audible. For restrictions on installation, refer to "INSTALLATION".

System Layout and Piping Length
For installation of the indoor units. Follow the instructions in the installation manual for each unit.

System Layout
Distributor Unit For 2 rooms : PMBD3620 (Ø9.52, Ø6.35) For 3 rooms : PMBD3630 (Ø9.52, Ø6.35) For 4 rooms : PMBD3640 (Ø9.52, Ø6.35) For 3 rooms : PMBD7230 (A: Ø12.7, Ø6.35) (B: Ø15.88, Ø6.35) (C: Ø15.88, Ø6.35) Do not connect more than 8 indoor units together choose the distributor unit type (2rooms,3rooms or 4rooms) according to the installation pattern

Branch Distributor A

Branch Pipe L1 L2

L3

L4

h2 Branch Distributor

L5 h1

L6

L7

L8

• Y Branch Pipe - Included in outdoor unit - Can not be purchased separately

Main Pipe

B 40K(6rooms) 48K~56K(7~8rooms)

Service Manual 81

Installation Piping length and elevation
(m)

No.

Length

6 room

7 room

8 room

(1) (2) (3) (4) (5) (6)

Total main piping length Total branch piping length Max. each branch piping length Total system piping length Maxium Level in - out Maxium Level in - in

A+B L1+L2+L3+L4+L5+L6+(L7)+(L8) L1, L2, L3, L4, L5, L6, L7,L8 (Total main) + (Tatal branch) h1 h2

50 50 15 100 30 10

50 60 15 110 30 10

50 60 15 120 30 10

Installation
• This unit may be installed suspended from the ceiling or mounted on the wall. • This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up) However, it may be freely installed in any direction forward or back, and to the sides. • Be sure to leave a 600mm square opening for service and inspection as shown in the diagram below, for both ceiling - suspended installation and wall-mounted installation. • This unit "does not require drain treatment" as it uses internal foam treatment as low-pressure piping insulation. • Service direction is the side B and C • The piping for the indoor unit may be led around in direction A • The inclination of side B must be within ±5°C degrees forward or back or to the sides.
Ø6.35 Ø9.52

(298)

250

A

Ø9.52

Ø19.05 245 Suspension bolt pitch. (36) 50 50 50 (150) Main Pipe

B
30 50

(38) 50

(56) 50 50 50

72 Branch Pipe

300

60 Cover Control

(111)

C

Min 400 Min 30 (Servicing space)

Min 400

Min 300

Inspection opening

82 Multi type Air Conditioner

(337)

Installation

Installation of The Main Unit
NOTICE

:

• This unit has two different installation types: (1) Ceiling-suspended type and (2) wall-mounted type. • Choose the proper installation pattern according to the location of installation. • The installation location for printed wiring board can be changed. Follow the procedure specified in the "CONNECTING THE WIRING" section to change the location.
(1) Ceiling-suspended type (2) Wall-mountde type

(1) Ceiling-suspended type

Procedure
(1) Fix the fumished hanger metal with two screws.(4 locations in total). (2) Using an insert-hole-in- anchor, hang the hanging bolt. (3) Install a hexagon nut and a flat washer (locally-procured)to the hanging bolt as shown in the figure in the left, and ift the main unit to hang on the hanger metal. (4) After checking with a level that the unit is level, tighten the hexagon nut. * The tilt of the unit should be within ±5° in front/back and left/right.
BD unit Six-sided Nut (M10 or M8) Hanger metal Flat washer washer 15.00

Hanging bolt (M10 or M8)

(2) Wall-mounted type

Procedure
(1) Fix the fumished hanger metal with two screws. (3 locations in total). (2) After checking with a level that the unit is level, fix the unit with the furnished wood screws. * The tilt of the unit should be within ±5° in front/back and left/right.

Screws(M5) Scre ws(M5) (locally procude)

CAUTIONS • Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again or cover it with alumium tape.(This is to prevent condensation) • Be sure to install the unit with the ceiling-sie up. • Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be audible.

Service Manual 83

Installation

Connection of Piping
• When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate connection ports maked with matching alphabets. (A, B, C, D)
NOTICE

:

A

B

C

D

• Be sure to mark all the local refrigerant piping(liquid pipes, gas pipes, etc.) for each indoor unit designating clearly which room it belongs in.(A, B, C, D)

: For flaring work the piping, follow the instructions in the installation manual to each unit.
NOTICE

Connecting the pipings to the indoor unit and drain hose to drain pipe
1. Align the center of the pipings and sufficiently tighten the flare nut by hand. 2. Tighten the flare nut with a wrench.
Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4 Torque kg.m 1.8 4.2 5.5 6.6 6.6
Open-end wrench (fixed) Flare nut Wrench BD Unit Socket Connection pipe

BD Unit Socket

Flare nut

Pipes

Wrap the insulation material around the connecting portion.
1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. 2. Wrap the area which accommodates the rear piping housing section with vinyl tape.

BD Unit

Indoor unit pipe

Wrap with vinyl tape Vinyl tape (wide) Connecting cable Pipe Vinyl tape(narrow)

Close up a socket for unoccupied room with a brass cap.
1. Align the center of the piping and sufficiently tighten the brass cap by hand. 2. Tighten the brass cap with a wrench. 3. Wrap the joint part with insulation.
CAUTIONS • Never use the plastic cap for sealing. • Make sure to use brass cap with the end of pipe sealed or welded tightly. BD Unit Socket Brass cap Pipe sealed or welded

84 Multi type Air Conditioner

Installation

Connection of Wiring
• Connect refrigerant pipes and connection wires to the appropriate ports maked with matching alphabets (A, B and C) on this unit. • Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor units to terminal board numbers.(1, 2 and 3) Always fix each ground wire separately with a ground screw.(See the figure below.) • After completing the wiring, fix the outer coating of wires securely with wire clamps. The wire clamp on indoor unit side is furnished. Follow the procedure below to install. • Refer to the circuit diagram on the control cover inside outdoor unit.

: The terminal board numbers are arranged from top to bottom in order of 1, 2 and 3.
NOTICE

In Case of 3 rooms
Warning Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overtheating, electrical shock, or fire.

C room B room A room

A B C CN-PWR

Connection wire for indoor units (H05VV, 4wires, 0.75mm)

Connection wire for outdoor units (H05RV, 4wires, 1.2mm)

(1) Remove the control cover. Loosen the two screws, and slide the cover in the direction of the arrow.

(3) Put in the cover in the direction of the arrow then tighten the screws.

(2) Perform wiring with reference the wiring diagram on a control cover of outdoor unit. Allow 300 mm for the pulling-out section of harness. Fix the wires completely with wire clamps(4 locations).

Service Manual 85

Operation

Operation
Function of control
1. MAIN UNIT FUNCTION
• DISPLAY
Operation Indicator • On while in appliance operation, off while in appliance pause • Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on) Sleep Timer Indicator • On while in sleep timer mode, off when sleep timer cancel or appliance operation pause Timer Indicator • On while in timer mode (on/off), off when timer mode is completed or canceled Defrost Indicator • Off except when hot start during heating mode operation or while in defrost control

s Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop. • When it reaches 0.5°C above the setting temp, they start to operate again. Compressor ON Temp ➲ Setting Temp+0.5°C Compressor OFF Temp ➲ Setting Temp-0.5°C • While in compressor running, operating with the airflow speed set by the remote control. While compressor is off fan operates at low speed regardless of the setting.

s Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature. 26°C ≤ Intake Air Temp ➲ 25°C 24°C ≤ Intake Intake Air Temp<26°C ➲ Intake Air Temp-1°C 18°C ≤ Intake Intake Air Temp<24°C ➲ Intake Air Temp-0.5°C Intake Air Temp<18°C ➲ 18°C • While compressor off, the indoor fan repeats low airflow speed and stop. • While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat. Compressor ON Temp. ➲ Setting Temp+0.5°C Compressor OFF Temp. ➲ Setting Temp-0.5°C • In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

s Heating Mode Operation
• When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp. ➲ Setting Temp. Compressor OFF Temp. ➲ Setting Temp.+3°C • While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 27°C , it

86 Multi type Air Conditioner

Operation
operates with the low or setting speed. When the indoor pipe temp is between 20°C and 27°C, it operates with Super-Low(while in sleep mode, with the medium airflow speed). • While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it operates with the low airflow speed. • While in defrost control, the indoor is outdoor fans are turned off.

s Defrost Control(Heating)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe. • The first defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed from starting of heating operation and more than 4 minutes operation of compressor. • Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature rises over 15°C even before 12 minutes. • The second defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed from ending of the first defrost and more than 4 minutes operation of compressor.

s Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected. • When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows. 24°C ≤ Inatake Air Temp ➲ Fuzzy Operation for Cooling 21°C ≤ Inatake Air Temp<24°C ➲ Fuzzy Operation for Dehumidification Inatake Air Temp<21°C ➲ Fuzzy Operation for Heating • If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated. 1) Fuzzy Operation for Cooling • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp +0.5°C Compressor OFF Temp ➲ Setting Temp + 0.5°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C≤ Intake Air Temp ➲ 25°C 24°C≤ Intake Air Temp<26°C ➲ Intake Air Temp + 1°C 22°C≤ Intake Air Temp<24°C ➲ Intake Air Temp + 0.5°C 18°C≤ Intake Air Temp<22°C ➲ Intake Air Temp Intake Air Temp<18°C ➲ 18°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

Service Manual 87

Operation
2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲ Setting Temp+0.5°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C ≤ Intake Air Temp ➲ 25°C 24°C ≤ Intake Air Temp<26°C ➲ Intake Air Temp+1°C 22°C ≤ Intake Air Temp<24°C ➲ Intake Air Temp+0.5°C 18°C ≤ Intake Air Temp<22°C ➲ Intake Air Temp Intake Air Temp<18°C ➲ 18°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation. 3) Fuzzy Operation for Heating • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp Compressor OFF Temp ➲ Setting Temp + 3°C • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 20°C≤Intake Air Temp ➲ Intake Air Temp + 0.5°C Intake Air Temp<20°C ➲ 20°C • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.

s Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow speed selection key on the remote control.

s On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate. • The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached. • If the appliance is operating at the time set by the timer, the operation continues. While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

s Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer, the pause continues.

88 Multi type Air Conditioner

Operation s Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.

s Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance operation, the operation of the appliance stops. • While the appliance is on pause, the sleep timer mode cannot be input. • While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again. • When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low. • When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.

s Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction. • While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

s Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation.

s Jet Cool Mode Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C. • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further.

s Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.

Service Manual 89

Operation s Forced Operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions. • When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting (or test operation) position or switched from the remote control position to the forced operation position while the power is on, the forced operation is carried out. • When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating. • In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows. 24°C≤Intake Air Temp ➲ Cooling Mode Operation, 22°C, High Speed 21°C≤Intake Air Temp<24°C ➲ Dehumidification Operation, 23°C, High Speed Intake Air Temp<21°C ➲ Heating Mode Operation, 24°C, High Speed

s Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds. • When the appliance-pause key is input by the remote control, the long "beep—" sounds.

90 Multi type Air Conditioner

Operation

Function of Indoor Unit
Split Type Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. Time Delay Safety Control • Restarting is delayed for approx. 3 minutes. Indoor Fan Speed Control • High, Med, Low, Chaos Operation indication Lamps (LED) --- Lights up in operation --- Lights up in Sleep Mode --- Lights up in Timer Mode --- Lights up in Deice Mode

Soft Dry Operation Mode • Intermittent operation of fan at low speed. Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Natural Air Control by CHAOS Logic • The fan is switched to intermittent or irregular operation • The fan speed is automatically switched from high to low speed. * Airflow Direction Control • The louver can be set at the desired position or swing up and down automatically.(Model base) "Wall Mounted Type is standard" * Functions is dependent on model type. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during deicing. • Hot start after deice ends. Hot-start Control (Heating) • The indoor fan stops until the evaporator piping temperature will be reached at 27°C.

Service Manual 91

Operation Art Cool Type Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 sec at the starting. Time Delay Safety Control • Restarting is inhibited for approx. 3 minutes. Indoor Fan Speed Control • High, Med, Low, CHAOS, JET COOL Operation indication Lamps (LED) --- Lights up in operation --- Lights up in Sleep Mode --- Lights up in Timer Mode --- Lights up in Defrost Mode (for Heating Model) OUTDOOR--- Lights up in compressor operation (for Cooling Model) Soft Dry Operation Mode • Intermittent operation of fan at low speed. Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Natural Air Control by CHAOS Logic • The fan is switched to intermittent or irregular operation • The fan speed is automatically switched from high to low speed. Airflow Direction Control • The louver can be set at the desired position or swing up and down automatically. PLASMA • The function will be operated while in any operation mode with selecting the function. • The function is to be stopped while it is operating with selecting the function. Defrost(Deice) control (Heating) • Both the indoor and outdoor fan stops during defrosting. Hot-start Control (Heating) • The indoor fan stops until the evaporator pipe temperature will be reached at 28°C.

92 Multi type Air Conditioner

Operation
Art Cool Deluxe Type Remote Controller
Operation ON/OFF

Operation Mode Selection Cooling Operation Mode.(
(Cooling (Heating model only) model only)

)

Auto Operation Mode.( ) Heating Operation Mode.(

) )

Healthy Dehumidification Operation Mode.(

Fan Speed Selection (Low) Room, Temperature Checking (Med) (High)

: (High:39°C
Temperature Setting
TEMPERATURE LOW HIGH

Low:11°C)

Cooling
JET COOL

Down to 18°C Up to 30°C

Heating

Down to 16°C Up to 30°C

Setting the Time or Timer

Timer Selection

: OFF, ON, OFF
ON OFF

ON

Timer Setting
SET

Timer Cancel
CANCEL

: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation

: 1, 2, 3, 4, 5, 6, 7, Off Timer
Airflow Direction Control 2nd F Air Circulation Reset

: Fan Operates without cooling or heating.
Horizontal Airflow Direction Control Button(Optional)

Service Manual 93

Operation

Duct Type Remote Controller
Operation ON/OFF

Operation Mode Selection Cooling Operation Mode ( Heating Operation Mode ( ) ) Soft Dry Operation Mode ( Auto Operation Mode ( ) )

(Cooling (Heating model only) model only)

Fan Speed Selection

LO (Low)
Room Temperature Display : High:39°C ↔ LOW:11°C Temperature Setting Cooling Setting the Timer
Timer Cancel

MED (Med)

HI (High)

Down to 18°C Up to 30°C

Heating

Down to 16°C Up to 30°C

Weekly Program
Program Week Holiday

SET/CLR Hour Min

Fan Operation Mode

: Fan Operates without cooling & heating

Phase Control Setting
Timer

94 Multi type Air Conditioner

Operation

CST Type Remote Controller
Operation ON/OFF

Operation Mode Selection Cooling Operation Mode ( Heating Operation Mode ( ) ) Soft Dry Operation Mode ( Auto Operation Mode ( ) )

(Cooling (Heating model only) model only)

Fan Speed Selection

LO (Low)
Room Temperature Display : High:39°C ↔ LOW:11°C Temperature Setting Cooling

MED (Med)

HI (High)

JET

AUTO

Down to 18°C Up to 30°C

Heating

Down to 16°C Up to 30°C

Setting the Timer
Timer Cancel

Weekly Program
Program Week Holiday

: Fan Operates without cooling & heating
SET/CLR Hour Min

Fan Operation Mode

Service Manual 95

Operation

Convertible Type Remote Control
Operation ON/OFF

Operation Mode Selection Cooling Operation Mode.(
(Cooling (Heating model only) model only)

)

Auto Operation Mode.( ) Heating Operation Mode.(

) )

Healthy Dehumidification Operation Mode.(

Fan Speed Selection (Low) Room, Temperature Checking (Med) (High) (CHAOS)

: (High:39°C
Temperature Setting
TEMPERATURE LOW HIGH

Low:11°C) Down to 18°C Up to 30°C Down to 16°C Up to 30°C

Cooling
JET COOL

Heating

PLASMA(Optional)

Setting the Time or Timer

Timer Selection
ON OFF

: OFF, ON, OFF

ON

Timer Setting
SET

Timer Cancel
CANCEL

: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation

: 1, 2, 3, 4, 5, 6, 7, Off Timer
Airflow Direction Control

Air Circulation

: Fan Operates without cooling or heating.
Horizontal Airflow Direction Control Button(Optional)

2nd F Reset

96 Multi type Air Conditioner

Operation

Function of Outdoor Unit
Outdoor Unit
Two Comp algorithm • Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion. Operating Frequency • Inverter Frequency varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on. LEV Control • LEV pulse is modulated to keep constant superheat or subcooling. Out door Fan Control • Outdoor fan operates at High/Low or Off to respond to the load condition. R/Valve Control • Convert R/Valve to change cooling to heating, heating to cooling. Comp Pre-Heat Logic • Checking outdoor temp, D-Pipe temp,Heat Sink Temp, operate compressor at low frequency upto 5min to preheat oil. Defrost Function • After 35 min heating operation, check the defrost condition and if outdoor pipe temp is below -6°C and released from deice operation in case outdoor pipe temp is over 15°C or 7 min cooing mode. • To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to cooling, in this case, indoor and outdoor fan is off. Oil Return System • In heating operation, every 3 hours, changes from heating to cooling for 5 min to return the oil in piping to compressor. IPM Over Heat Protection • To protect IPM overheat, down comp Hz. Comp Overload Protection • To protect comp from being overload, down comp Hz. Low Pressure Protection • If cylce pressure is low (around 0.3kgf/cm2), turn off comp and outdoor fan.

Service Manual 97

Operation

Remote Control Operation
The Remote Controller transmits the signals to the system.

Signal transmitter

1

START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. OPERATION MODE SELECTION BUTTON Used to select the operation mode. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. INDOOR FAN SPEED SELECTOR Used to select fan speed in four steps low, medium, high and CHAOS. JET COOL Used to start or stop the speed cooling/heating. (Speed cooling/heating operates super high fan speed.) CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction. ON/OFF TIMER BUTTONS Used to set the time of starting and stopping operation. TIME SETTING BUTTONS Used to adjust the time. TIMER SET/CANCEL BUTTON Used to set the timer when the desired time is obtained and to cancel the Timer operation. Used to set Sleep Mode Auto operation. Used to circulate the room air without cooling or heating. Used to check the room temperature.

2 3

5 6

4
1 3

5

4 2 7 11 8 13
14 10
CANCEL ON OFF SET AUTO CLEAN

9 16

6

12 15

7

8
Flip-up door (opened)

9

Operation Mode
Cooling Operation Auto Operation

10 SLEEP MODE AUTO BUTTON 11 AIR CIRCULATION BUTTON

Healthy Dehumidification Operation Heating Operation

12 ROOM TEMPERATURE CHECKING BUTTON 13 PLASMA(OPTIONAL)
)

• Cooling Model(

), Heat Pump Model(

Used to start or stop the plasma-purification function. Initialize remote controller. Used prior to using modes printed in blue at the bottom of buttons.

14 RESET BUTTON 15 2nd F Button

16

AUTO CLEAN (Model Base) Used to set Auto Clean mode.

98 Multi type Air Conditioner

Operation

Duct Type Remote Controller
AUTO SWING OPERATION SET TEMP
Room Temp

FAN SPEED HI MED LO

SUB FUNCTION

Time Timer
Operation unit
03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4
17 19 21 23

1

Program set
09 11 13 15

On Off Set no. Time 01

3 Signal receiver 7 8 9 10 11 12 13
Timer Cancel

2 5
Holiday

Program

Week

6 4 14
RESET

SET/CLR Hour Min

15

1 2

Operation display Displays the operation conditions. On/Off Button Operation starts when this button is pressed, and stops when the button is pressed again. Set Temperature Button Used to set the temperature when the desired temperature is obtained. FAN Operation Button Used to circulate room air without cooling or heating. Fan Speed Button Used to set desired fan speed. Operation Mode Selection Button Used to select the operation mode. • Auto Operation Mode. • Cooling Operation Mode. • Soft Dry Operation Mode. • Heating Operation Mode.(except cooling model) Timer Cancel Button Used to cancel the timer.

8

Timer Set Button Used to set the timer when the desired time is obtained. Week Button Used to set a day of the week. Program Button Used to set the weekly timer. Holiday Button Used to set a holiday of the week. Time Set Button Used to set the time of the day and change the time in the weekly timer Function. Set and Clear Button Used to set and clear the weekly timer. Room Temperature Checking Button Used to check the room temperature. Reset Button Used to set the current time and clear the setting time.

9 10 11 12

3

4

5 6

13 14 15

7

Service Manual 99

Operation

CST Type Remote Controller
1Way
AUTO SWING OPERATION SET TEMP
Room Temp

FAN SPEED HI MED LO

SUB FUNCTION

Time Timer
Operation unit
03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4
17 19 21 23

1

Heat Pump Model

Program set
09 11 13 15

On Off Set no. Time 01

3 4Way 17 10 11 12 13 14 15 16 18
Timer Cancel

2 5
Holiday Plasma Set/Clr Hour Min RESET

6

Cooling Model

Program

Week

4 7 8 9

1 Operation display

9 Plasma Air Clean Button (optional) 10 Timer Cancel Button

Displays the operation conditions.
2 On/Off Button

Used to cancel the timer.
11 Timer Set Button

Used to set the timer when the desired time is obtained. Set Temperature Button 3 Used to set the temperature when the desired temper12 Week Button ature is obtained. Used to set a day of the week. 4 FAN Operation Button 13 Program Button Used to circulate room air without cooling or heating. Used to set the weekly timer. 5 Fan Speed (Jet Cool Button: 4 way) 14 Holiday Button Used to set the desired fan speed or select Jet cool Used to set a holiday of the week. mode. 15 Time Set Button 6 Operation Mode Selection Button Used to set the time of the day and change the time in Used to select the operation mode. the weekly timer Function. • Auto Operation Mode 16 Set and Clear Button • Cooling Operation Mode Used to set and clear the weekly timer. • Soft Dry Operation Mode • Heating Operation Mode(except cooling model) 17 Swirl Button (4 way) Used to select swirl mode. 7 Auto Swing Button Jet Cool Button (1 way) Used to swing up and down.
8 Room Temperature Checking Button 18 Reset Button

Operation starts when this button is pressed, and stops when the button is pressed again.

Used to check the room temperature.

Used to set the current time and clear the setting time.

❈ Display temperature can be different from actual room temperature if the remote controller is installed at the place where sun-rays are falling directly or the place nearby heat source.

100 Multi type Air Conditioner

Operation
1) Two Thermistor System (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. • Position 1: The room temperature is controlled by the thermistor of the main body. • Position 2: The room themperature is controlled by the thermistor of the wired remote-controller, control the temperature according to the position of wired remote-controller. • Position 3: The room temperature is controlled by lower temperature between the temperature of main body and of remote-controller sensor. (3) Move the slide switch to set position.

Room Temp. sensor Slide switch for 2 Thermistor
TH R13H R12H CO1H OP5R16H OP4 R14H OP3 SW TH OP2 OP1 R19H R11H R15H

Position 2 Position 1 Position 3

REMO MAIN 2TH
SW

REMO MAIN 2TH R17H

OP7 R18H OP6

LO STAND HI

C070 R03S R04S R02S R01S

HIGH

(4) Close the rear cover and check if it works normally.

CAUTION: • Select the position after counselling with a customer. • In case of cooling mode, room temperature is controlled by the main body sensor. • To control the room temperature by a wired remote controller, install controller(room temp. sensor) to sense the temperature more accurately. • Maunfactured in the position 1.

Service Manual 101

Operation
2) Group Control(Optional Wiring) • You can use a group control operation after connecting the brown and yellow wire of each air-conditioner. • Remove the resistor "OP 7" in remote controller. • It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent.

Wiring design
Indoor Unit 1
Terminal(Local Supply) Block Connector
RED(12V) YL(SIGNAL) BR(GND) RED(12V) YL(SIGNAL) BR(GND)

Main PCB
Indoor Unit 2
Terminal(Local Supply) Block Connector
YL(SIGNAL) BR(GND) YL(SIGNAL) BR(GND)

Indoor Unit 16
Terminal(Local Supply) Block Connector

Main PCB #1

Main PCB #2

....

YL(SIGNAL) BR(GND)

YL(SIGNAL) BR(GND)

Main PCB #16

....

Connecting Cable(Local Supply)

AUTO SWING

OPERATION

SET TEMP
Room Temp

FAN SPEED HI MED LO
ZONE

SUB FUNCTION

Time Timer
Operation unit
03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4
19 21 23

Slide Switch

Program set
09 11 13 15 17

On Off Set no. Time 01

Wired Remote Controller

OP7 Remote Controller PCB

Features
• Use Only One Wired Remote Controller with several air conditioners(max. 16 Units) • Random starting to prevent overcurrent.

CAUTION: • Be careful not to exchange the color of wires. • The maximum length of connecting wire should be below 200m(25Ω) on connecting each units. • Use a wire more than 0.5mm2

102 Multi type Air Conditioner

Operation
3) E.S.P.(External Static Pressure) Setting (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. s Without Zone System 1. Position V-H, F-H: • This position sets the maximum E.S.P as a default set. 2. Position V-L: • This position sets the minimum E.S.P as a default set. s With Zone System 1. Position V-H: • Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom. 2. Position F-H: • Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers. 3. Position V-L: • Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom. * Maximum : 8mmAq Minimum : 0mmAq (3) Move the slide switch to set position.

TH

R13H

R12H

CO1H

OP5R16H

OP4

R14H OP3 SW TH

OP2

OP1 R19H R11H

R15H

V-H F-H V-L

REMO MAIN 2TH R17H

OP7 R18H OP6

LO STAND HI

C070 R03S R04S R02S R01S

SW

HIGH

Slide switch for ceiling height

(4) Close the rear cover and check if it works normally.

Service Manual 103

Operation
4) How to Set E.S.P? Procedure of RPM change: Ex) External Static pressure is 4mmAq for Model 36K. • To protect the unit, compressor is designed to be off during E.S.P. setting.

1

Push the"On/Off"button. The unit will start.
AUTO SWING OPERATION SET TEMP
Room Temp

FAN SPEED HI MED LO
ZONE

SUB FUNCTION

AUTO Heater Preheat JET Defrost Humidify Filter Out door

Time
Operation unit
Set no. Time 01 03 05 07

Program set
09 11 13 15 17 19 21 23

2

Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
Timer
AUTO SWING OPERATION SET TEMP
Room Temp

FAN SPEED HI MED LO
ZONE

SUB FUNCTION

AUTO Heater Preheat JET Defrost Humidify Filter Out door

Time
Operation unit
Set no. Time 01 03 05 07

Program set
09 11 13 15 17 19 21 23

3

Push the "Up" of "Down" button for E.S.P adjustment. And, adjust the number which you want.(In this example, the number is "225". Refer to the table 1 on the next page.)
AUTO SWING OPERATION SET TEMP
Room Temp

FAN SPEED HI MED LO

SUB FUNCTION

Time
Operation unit
Set no. Time 01 03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 2
17 19 21 23

Program set
09 11 13 15

Note: The range of selection is from 1~254. Since, the display is two Digit only. If the range selection is above 100 then the third digit will appear in the screen as shown.

4

Shift the fan speed mode by pressing the fan speed button. And then, Adjust numbers of next steps by repeating the stage 3. (In this example, the numbers are "237" and "243" respectly)

5

Push the "Timer" and "Wind" button simultaneously for more than 3 seconds. Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWING OPERATION SET TEMP
Room Temp

FAN SPEED HI MED LO
ZONE

SUB FUNCTION

Timer
Time
Operation unit
Set no. Time 01 03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door

Program set
09 11 13 15 17 19 21 23

104 Multi type Air Conditioner

Operation

Duct ESP control table
Chassis Static Pressure(mmAq) 0 1 Setting Value 220 240 255 175 200 220 170 185 220 0 215 235 250 170 190 215 150 165 180 2 Setting Value 225 245 254 210 235 254 2 4 220 240 253 200 230 215 6 Setting Value 235 245 254 220 235 250 0 230 238 252 205 230 240 2 225 235 248 190 220 235 4 215 230 245 170 200 230 6 Setting Value 153 173 195 230 240 245 150 173 195 230 238 245 150 175 193 225 237 243 148 175 193 220 235 243 130 170 190 150 230 240 1 155 190 1 220 240 180 215 240 1 100 210 8 10 8 210 230 250 100 220 245 10 210 230 245 150 185 210 130 145 160 4 2

Ca(Btu/h)
9K

Step(Hi/Med/Lo)
8 CMM 7 CMM 6 CMM 10 CMM

BT

12K

9 CMM 8 CMM 14 CMM

18K

13 CMM 12 CMM

Chassis

Static Pressure(mmAq)

Ca(Btu/h)
9K

Step(Hi/Med/Lo)
10.5 CMM 9 CMM 8.5 CMM 11.5 CMM

BP
12K

10 CMM 8.5 CMM

Chassis

Static Pressure(mmAq)

0

Ca(Btu/h) Step(Hi/Med/Lo)
16.5 CMM 18K 14.5 CMM 13 CMM 18 CMM 24K 16.5 CMM 14 CMM Chassis Static Pressure(mmAq)

BH

Ca(Btu/h) Step(Hi/Med/Lo)
26.5 CMM 30K 23 CMM 20 CMM 32 CMM 36K 29 CMM 26.5 CMM

BG

Service Manual 105

Control Devices and Function

Control Devices and Function
Simple Central Control
Features
• Easy operation button. • Independent operation for 16 indoor units each. • Simultaneous turn ON/OFF for all of indoor units connected. • Easy change operation mode to cooling or heating • Set and clear lock-mode for each indoor unit • Simultaneously set and clear lock-mode for all of indoor units connected. • Display function for all of indoor units connected.

Term of Each part and Function
On/Off display LED (TOTAL 16EA)
• On pressing individual on/off button, display the present operation state. -Operation : green. -Stop : off -Error mode : blinking

Individual On/Off button
• Control ON/OFF of a unit.

Power display LED
• Indicate the state of DC Power supply in central control unit. - On : red(Heating), green(Cooling) - Off : no signal - Error mode : blinking with red color

TOTAL Off button
• Stop all linked units sequentially.

TOTAL On button
• Operate all linked units sequentially.

106 Multi type Air Conditioner

Control Devices and Function

Electrical wiring
s PICTORIAL VIEW OF THE CONNECTION

Outdoor Outdoor unit unit
PI485 MAIN PCB
L

: PNF-P14A0M

PI485

MAIN PCB
CN_CENTRAL

Control Box

MAIN PCB
CN_CENTRAL N L

PI485

10 G A B VCC GND C D

CN OUT

CENTRAL CONTROL UNIT

• Special purchase: Central control, PI485(PNF-P14A0M)

s ONE SIMPLE CENTRAL CONTROL CONNECTION
INDOOR UNIT 1 INDOOR UNIT 2

INDOOR UNIT
• SET The Address(Group No. & Indoor No.) * Refer to The Following sheet (1.3.5 Indoor unit Address setting method)
Vcc GND C D

OUTDOOR MAIN PCB

INDOOR UNIT 3 INDOOR UNIT 4 INDOOR UNIT 5 INDOOR UNIT 6
BUS B BUS A GND +10V

CN-POWER GND CN-COM B CN-POWER S1 LED2 LED3 IC1P + + LED5 + S9 S5 + S6 LED4 S2 L CN-COM A S4

+
LED7

+
LED8 S11

S3

D

C GND VCC

TX1 S12

+
LED10

S10

+
LED11

Outdoor Outdoor unit unit
Group Number 0 Master Mode

LED9

LED12 S15

+
LED13

+
LED14

S14

+
LED15

+
LED16

S16

PWB:6870A10001A ASM:6711A20005E

+
LED17 ON KSDO4H L1 2 3 4 S19

S15

S18

All the connections are to be done as shown above. A and B are the communication lines for the indoor and C and D are the communication lines for the Central Control. Use two shield lines for C/D connecting line.(Earth the shield line)

VCC CENTRAL GND CONTROL C UNIT D

Service Manual 107

Control Devices and Function s 2 OR MORE SIMPLE CENTRAL CONTROL CONNECTION
INDOOR UNIT 1 INDOOR UNIT 2

OUTDOOR MAIN PCB

INDOOR UNIT 3 INDOOR UNIT 4

<Group Number 0>
INDOOR UNIT 5 INDOOR UNIT 6
BUS B BUS A GND +10V
IC1P + LED5 + LED9 S9

Vcc

GND

C
CN-POWER GND

D

CN-COM B CN-POWER S1 LED2 LED3 S5 + S6 LED4 S2 L CN-COM A S4

Master

DIP SWITCH

+
LED7

+
LED8 S11

S3

TX1 S12

+
LED10

S10

+
LED11

LED12 S15

+
LED13

+
LED14

S14

+
LED15

+
LED16

S16

D

C GND VCC

PWB:6870A10001A ASM:6711A20005E

+
LED17 ON KSDO4H L1 2 3 S19 4

S15

S18

Outdoor unit 1
INDOOR UNIT 1 INDOOR UNIT 2

Master Mode

Group Number 0

1. Adhere the PI485 Module(For connecting central control) to the Control Box. 2. Connect the PI485 Module to central control. 3. In the case of connecting two more than central control, set the Master/Slave mode and then connect each communication lines(C,D) <Refer to above fig>. *Special purcharse: Central control(P/No.:4995A20105F), PI485 Module(PNF-P14A0M) * It can be added to 15 Central controls for the slave control.

OUTDOOR MAIN PCB

INDOOR UNIT 3 INDOOR UNIT 4 INDOOR UNIT 5 INDOOR UNIT 6
BUS B BUS A GND +10V
IC1P + LED5 + LED9 S9

Note
<Group Number 1>
Vcc GND C
CN-POWER GND CN-COM B CN-POWER S1 LED2 LED3 S5 + S6 LED4 S2 L CN-COM A S4

D

001
Slave
DIP SWITCH
Group No. Indoor No.
TX1

+
LED7

+
LED8 S11

S3

+
LED10

S10

+
LED11

S12

LED12 S15

+

+
LED14

S14

+
LED15

+
LED16

S16

D

C GND VCC

LED13

PWB:6870A10001A ASM:6711A20005E

+
LED17 ON KSDO4H L1 2 3 S19 4

S15

S18

Outdoor unit 2

Master Mode

Group Number 0

PI485 setting method(LG Aircon Network unit)

Selection of product unit type

Selection of network type

ON KS DO 4H L1 2 3 4

s Settings method of TPS Inverter Multi Type
ON KS DO 4H L1 2 3 4

1 ON + All OFF : Connection of "TPS Inverter Multi Connection + General Central Controller" Case.

ON KS DO 4H

1,4 ON + All OFF : Connection of
L1 2 3 4

"TPS Inverter Multi Connection +

Central Controller applied 「LGAP」" Case. * LGAP : LG Air conditioners Protocol

• Function of LG Network - It is possible to connect the network of LG air conditioners and to connect various contents of the network system, which is simple, deluxe and PC central control. - Please refer to "LG Control System Manual" about the detail functions and the products possible to network. - As the Interface for networking, PNF-P14A0M/R/C is applied.

108 Multi type Air Conditioner

Control Devices and Function Indoor Unit Address setting Method

Using Wired Remocon

1. Press 13(program) and 16(set and clear) key more than 3 second then "Address Setting Mode" starts. 2. Set the address of indoor unit by using "Temperature setting" key. s Range of address : 00 ~ FF
1

AUTO SWING

OPERATION

SET TEMP
Room Temp

FAN SPEED HI MED LO

SUB FUNCTION

Time Timer
Operation unit
03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4
17 19 21 23

Program set
09 11 13 15

On Off Set no. Time 01

3 17 10 11 12 13 14 15 16 18 Heat Pump Model
Timer Cancel

2 5
Holiday Plasma Set/Clr Hour Min RESET

Ex)

3

A

Program

Week

6 4 7 8 9

Group Room(Indoor Unit) No. No.
3. After setting address, press 13(program) and 16(set and clear) key more than 3 second then "Address Setting Mode" is finished.

Using Wireless Remocon
1. Address setting Method
Signal transmitter

1) Press 5(Jet Cool) & 13(Reset) key at the same time more than 3 seconds then "Address Setting Mode" starts. 2) Set the address of indoor unit by using "Temperature setting" key. s Range of address : 00 ~ FF

5 6

1 3

Ex)

3

A

4 2 7 11 8 13 14 10
CANCEL ON OFF SET AUTO CLEAN

9 16 12 15

Group Room(Indoor Unit) No. No.
3) After address setting, pressing 1(On/Off) key, address setting is finished. The address that is set is displayed on a display window of indoor unit. * notice : The mothod of display and time is different according to indoor unit type. 4) If the remote control is reset, normal mode starts.

Flip-up door (opened)

2.

2. Address Monitoring
1) Press 6(Chaos Swing) & 13(Reset) key at the same time then "Address Monitoring Mode" starts. 2) At the address monitoring mode, pressing 1(On/Off) key, The address that is set is displayed on a display window of indoor unit. * notice : The mothod of display and time is different according to indoor unit type. 3) If the remote control is reset, normal mode starts.

* Notice : Confirm that wired and wireless remote control are able to select the address or not.

Service Manual 109

Control Devices and Function

Test run method
1. Set the wiring of system and indoor unit. 2. Apply power to the setting. 3. Do auto addressing to the outdoor unit. 4. After addressing, initialize the central controller(Manual initialize: Total on + total off + 16 key). • Cooling: Setting basically(Total On + Total Off + 4 key) • Heating: Total On + Total Off + 8 key ➡ Red power lamp 'On' 6. Check up On/Off with a related indoor key pressing.

Installation
s CAUTIONS

Do not install in this area
• Don’t install near elevator, computer, automatic door. (High noise area).

Keep in mind
• Don’t operate with wet hands.

• Don’t install near high moisture & high oscillation area.

• Don’t pull the connected wire.

• Don ’ t install near direct sunlight or heat source.

110 Multi type Air Conditioner

Control Devices and Function s INSTALLATION ORDER 1. Remove upper & lower case. 2. Fixate screw in the holes of the
case bottom.

3. For Dip switch, and Rotary
switch setting, refer to the page “How to Install”.

4. For wiring connection, refer page
“Installation Procedure”

5. Adjust the upper case in accordance with back case while assembling as shown in the figure.

6. Check the operation by supplying the power.

s LINK OF CONNECTING WIRE 1. First, separate the front case from rear case of controller, connect terminal
C, D,Vcc, GND on PCB referring to the following table. Maximum length of connecting wire • Between controller and outdoor unit : 220m(25Ω • Between controllers : 220m(25Ω ) )
Vcc

GND D C

Out door unit Terminal Block GND Vcc C D

Wire Color BLUE Red Brown Yellow

Central Control Terminal GND Vcc C D

2. After attaching the supplied wire to terminal, link the connecting wire.
If necessary, Cut the indicated part of front case to draw the lead wire.

Service Manual 111

Control Devices and Function s. ROTARY SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)
The setting of Group Number in the Central Control is done by the rotary switch as shown in the figure below.

It is possible to set 0~15 Group(Total 16 Groups). All the numbers on the rotary switch represent the different Group Numbers. By changing the knob we can set rotary switch to the group number we want to control. The above fig. Shows the control of group number “0”. Similarly we can control all the 16 Groups.

s. DIP SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)
CAUTION Dip switch is now used only for the setting of master or slave mode.( In the case of two more than central controls.) Set one to Master, the others to slave.

Master Mode Rotary Switch
Dip Switch
ON OFF

Slave Mode

s. ACCEASSORY PARTS
Central control and sub (with wire ass'y) should be purchased as optional.

Central Control(1EA)

PI485(PQNFP14A0M)
Wire Assembly 1

Screw(4EA)

Wire Assembly 2

112 Multi type Air Conditioner

Control Devices and Function

Deluxe Central Control
2.1.1 Summary
Deluxe Central control is a product available for individual and integrated monitoring and control of maximum 256 of TPS Inverter Multi air conditioner systems. Specially, operation status of the individual air conditioner can be particularly checked. Individual or simultaneous operation of the air conditioner, operation mode, wind quantity, user locking and temperature setup are also available. Specially for this system, installation is simple and user's environment is excellent. Central control is available by a simple manipulation. In addition, this system have the self-battery built-in and can stably operate in spite of outside disturbance such as temporary power failure. This system has no need of additional peripheral equipment like UPS (Undisturbed Power System) and AVR to be purchased for stability when composing the existing PC central control system, and has so attractive advantage in installation costs. Using the Deluxe Central control enables the management room to setup lock of each air conditioner and prevent indoor control of the individual air conditioner and restrain the necessary use. In case of releasing the lock, you may control the system by using the wire/wireless remote control at the place where the individual air conditioner is installed. Setup of a weekly schedule is available and detailed schedule of the individual air conditioner can be easily setup through the GUI. Details of schedule setup can be immediately checked with a graph. This system is a product to meet energy saving and convenience at the same time at a place like a school by using this schedule function. Depending on installation environment, location and conditions of use, you can setup groups. With this setup, more efficient operation at the center is available. Setup without requiring other equipment is available by using the GUI and change by the consumer is also available after installation. You can reduce development time to configure special system upon the request by the consumer and conveniently this system by using the touch panel. Where needs from a new customer occur or where purchase of additional air conditioner is done, the Deluxe Central control can be smoothly installed.

Deluxe Central control

Outdoor Unit

CNU
PI485

Outdoor Unit

PI485

Service Manual 113

Control Devices and Function

Major Characteristics

Figure 2) Deluxe Central control

1. Individual/Integrated Operation/Monitoring
s You can identify operation status of the air conditioner, operation mode, wind quantity, wind direction, locking, temperature setting and error, etc by selecting the installed air conditioner through individual selection, group selection or all selection. Individual setup and operation of the detailed functions are available. Therefore, managing with Deluxe Central control installed at the control room at a building where a number of air conditioners are installed, is a convenient way.

2. Group Management
s Group management for the installed air conditioners is available. Group can be seperated by their nature, location and size of each air conditioner which enables convenient use. In addition, allotment of respective name to the setup group allows further intuitive management.

3. Self-diagnosis Function
s The air conditioner installed can self-diagnosed its error status and then transmits the result to the central control. Therefore, a rapid countermeasure against failure of the air conditioner allows easy management and increases the usage life of air conditioner.

4. Semi-permanent Life / Convenient Maintenance
s Since the Deluxe Central control is designed for the semi-permanent use, this system can be used semipermanently after installation, different from the existing PC or a large central control system requiring a continuous management due to the life of peripheral and other PC.

5. Management Costs Down
s In absence of the Central Control System, the manager controls a number of air conditioners. In addition, even if management was done at the center, there is only function of on/off management at best and thus 2 or 3 building managers were actually required. However, manipulation of all functions can be now done at a control room for the Deluxe Central control and so a manager can easily control all air conditioners. Automatic operation is also allowed without a manager, by using schedule function.

114 Multi type Air Conditioner

Control Devices and Function 6. Convenient GUI / Touch Screen
s Not requires special education for using the Deluxe Central control, conveniently used only by pressing the buttons on the screen, and its function can be understood with intuitive pictogram. Especially schedule setting is done by simply by dragging, different from the existing system requiring to press the button by more than average 30 times to enter a schedule.

7. Schedule Automatic Operation Management / Energy Saving
s For the Schedule Automatic Operation, weekly setting is available. Enlisting of the schedule exception processing schedule (national holiday) is done for a year prevents the air conditioner from an unnecessary operation of air conditioner, allowing the system to be controlled at the center so that it can be only used for a necessary case and enabling to obtain excellent energy saving effect. Fixed schedule places like elementary school, middle school, high school and college or university will get its excellent working effect.

8. Power Failure Backup Function / Powerful Stability
s For the existing Central Control System, additional purchase of expensive UPS equipment in provision for a temporary power failure must be done in the past but for the Deluxe Central control, since the self-power failure compensation battery is built-in, power is automatically converted by maximum 2 hours. Therefore, there is almost no malfunction due to a temporary power failure because stable operation is available.

9. Mobility
s A wireless radio system may be installed at the Deluxe Central control, it will control the Airconditioners directly while going around the building with the wireless radio system and its self-battery function (100 m where there is no obstacle).

10. Convenient Installation
s This system can be freely fixed to the wall surface because of its small size, light weight and thin thickness. It can also stood up on the desk by using, its dedicated cradle. It is not subjected to spatial restriction in installation space and location since this system communicates on the basis of the I-GW and the Ethernet.

11. Stable Date Storage/Backup
s Setup information is saved as it is, even if no power is supplied then also all data is saved in the built-in flash memory.

12. Scalability
s Scalability of the system is easy in case of additionally purchasing equipment since scalable slot such as USB, Serial (RS-232c), PCMCIA, CF Type is prepared. This system is designed considering sufficient scalability in provision for special request by the customer.

13. Upgrade
s Additional installation of a new program is available via the CF memory card and the existing program can be upgraded to a new program. Using such upgrade function always enables to construct a modern type of Central Control System.

Service Manual 115

Control Devices and Function

Figure 3) Deluxe Central control
Table 1) Comparison Between Central control Characteristics Internet Central control Dedicate PC Configuration Position of program Max. installation set numbers Remote control Control & monitoring Schedule management System setup System monitoring(overview) User ’s lock Upgrade Touch screen Built-in Flash DB (backup) Wireless LAN (movable) Non-interruption device Requirements Life Non-required User S/W Download to i-GW 256 sets (Less than 128 sets recommended) Available Available Available(Configure file modification) Available Available Browser supporting JAVA Semi-permanent PC Central control Required User S/W, Engine S/W Installation 256 sets1) Available Available Available Available Available Available Separately add 2) JVM (provided by MS) Peripheral devices & PC life Deluxe Central control Non-required Main Body of Web Pad Deluxe Central control Built-in 256 sets Available Available Available Available Available Available Built-in Built-in Available (option) Built-in Semi-permanent

1) For the PC central control, installation set numbers may respond up to 1024 sets upon user’s request. 2) JVM (Java Virtual Machine) is basically installed at the Windows but some versions of Window XP may be manually installed.

116 Multi type Air Conditioner

Control Devices and Function

Major Function of Deluxe Central Control
[ System Control ]
To check general monitor function of the air con central control system such as selection of group and air conditioner, air conditioner control monitor function etc.

PQCSW501A0, PQCSW502A0

[ System Monitor ]
To check the ctual time status of all air conditioners.

PQCSW501A0, PQCSW502A0

[ System Set-up ]
To manage the air conditioner through grouping and record setup of group and installation position, etc.

PQCSW501A0, PQCSW502A0

[ Time Schedule ]
Setup of a weekly schedule for all, group and individual air conditioner enabled operation of the system. Processing through enlist of extra schedule for a year is available.

PQCSW502A0

Service Manual 117

Control Devices and Function

System Configuration
Scenario 1 : In case of not using Internet access function

B part

A part

Product

Control System Interface

Delux Central Control

CNU PI485

PI485
Cross UTP Cable (Cross LAN Cable) RS-485 Cable

PI485

PI485

* CNU: Central control Network interface Unit PI485: Product Interface unit for IEEE485 transmission.

Main Specifications
1. Control System
- Centralized control of maximum 256 indoor units - Simple Touch PAD method - GUI setting considering convenience of use - Power failure compensation with independent Battery Built-in (Max. 2 hours)

2. CNU
- Combination of maximum 8 outdoor units - 485 to Ethernet Converter Built-in

3. PI485
- 1 pcs per outdoor units Note: - GUI(Graphic User Interface) may be changed without any notice, for improvement or options.

118 Multi type Air Conditioner

Disassembly of the parts

Disassembly of the parts (Indoor unit)
Indoor unit
1. Split Type Indoor unit CAUTION: Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.

To remove the Grille from the Chassis. • Set the up-and-down air discharge louver to open position (horizontally) by finger pressure. • Remove the securing screws • To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.

Screw

1) To remove the sensor, housing connect, earth conductor & step motor conductor with sensor holder, Motor, Evaporator & P.C.B.

Motor Conductor Power Conductor Sensor Conductor Step Motor Conductor

Earth Conductor

Service Manual 119

Disassembly of the parts
2) To remove the Control Box. • Remove securing screws. • Pull the control box out from the chassis carefully.

3) To remove the Discharge Grille. • Pull the discharge grille out from the chassis carefully.

4) To remove the Evaporator. • Remove screws securing the evaporator and the holder eva.

• Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.

5) To remove the Cross-Flow Fan • Loosen the screw securing the cross-flow fan to the fan motor (do not remove). • Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.

• Remove the left end of the cross-flow fan from the self-aligning bearing.

120 Multi type Air Conditioner

Disassembly of the parts 2. Art Cool Type Indoor Unit CAUTION: Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.

1. To remove the Grille from the Chassis. - Pull the grille bottom, the remove 2 securing screws. - Lift the both lower parts of panel front. - After pull down this panel a bit, separate connecting wire with product.

Panel Front Connector

2. To remove the Control Box. - Before removing the control box, be sure to disconnect the wires from PWB. - Pull the cover control out from the control box and disconnect other wires. - Remove securing screws. - Pull the control box out from the chassis carefully.

Step Motor Connectors Sensor Connector

4Way/Fan Connector Comp Connector Power Connector Power Connector Comp Connector Motor Connector

Service Manual 121

Disassembly of the parts
3) To remove the Evaporator. - Remove 4 screws securing the evaporator. - Pull the evaporator out from the chassis carefully.

4) Before removing the Turbo Fan. - Remove the securing screws from the chassis. - Pull the pipe cover, top cover and the air guide.

Top Cover

Air Guide

Pipe Cover

5) To remove the Motor. - Remove the securing bolt from the motor shaft. - Pull the fan out from the motor shaft. - Remove 4 screws securing motor mount from the chassis and lift up the motor mount and the bracket.

Bracket

Turbo Fan

Bolt

Motor Mount

122 Multi type Air Conditioner

Disassembly of the parts 3. Art Cool Deluxe Type Indoor Unit CAUTION: Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.

To remove the Grille from the Chassis. • Hold up Inlet Grille Horizentally. • To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward. • To seperate connecter assembly and than to remove Inlet Grille assembly.

1) Before removing the control box, be sure to take out the wire screwed at the other end.

Service Manual 123

Disassembly of the parts
2) To remove the Control Box. • Remove securing screws. • Pull the control box out from the chassis carefully.

3) To remove the Discharge Grille. • Unhook the discharge grille and pull the discharge grille out from the chassis carefully.

4) To remove the Evaporator. • Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).

124 Multi type Air Conditioner

Disassembly of the parts
• Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.

5) To remove the Motor Cover • Remove 2 securing screw. • Pull the motor cover out from the chassis carefully.

Motor cover 6) To remove the Cross-Flow Fan • Loosen the screw securing the cross-flow fan to the fan motor (do not remove). • Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.

• Remove the left end of the cross-flow fan from the self-aligning bearing.

Service Manual 125

Disassembly of the parts 3. CVT Type - VB chassis
Warning : Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.

1. Remove the air filter. • Pull the inlet grille slightly toward you. • Pull out the air filter. (2 pieces)

R

Inlet Grille

2. Remove the girlle from chassis • Remove the screws securing the side plate and push to the bottom-side. • Unhook the hanger from the hanger screw at the left and the right side. • Pick out the inlet grille.

R

1 4 Hanger Hanger Screw 2 3

3. Remove the lower air guide • Remove a screw of both side fixing "barrier airguide". • Remove the screws of both sides of the lower air-guide. • Remove the lower air-guide toward “arrow mark” by turning upwards as shown in figure.
Barrier Air guide Lower Air guide

R

126 Multi type Air Conditioner

Disassembly of the parts

VE chassis
Warning : Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.

To remove the Grille from the Chassis. • Set the up-and-down air discharge louver to open position (horizontally) by finger pressure. • Remove the securing screws. • To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.

1. Before removing the control box, be sure to take out the wire screwed at the other end.

Service Manual 127

Disassembly of the parts
2. To remove the Control Box. • Remove securing screws. • Pull the control box out from the chassis carefully.

3. To remove the Discharge Grille. • Unhook the discharge grille and pull the discharge grille out from the chassis carefully.

4. To remove the Evaporator. • Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).

Caution label When repair, do not damage the Caution label.

128 Multi type Air Conditioner

Disassembly of the parts
• Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.

5. To remove the Motor Cover • Remove 2 securing screw. • Pull the motor cover out from the chassis carefully.

6. To remove the Cross-Flow Fan • Loosen the screw securing the cross-flow fan to the fan motor (do not remove). • Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.

• Remove the left end of the cross-flow fan from the self-aligning bearing.

Service Manual 129

Disassembly of the parts
4. Remove air guide upper, crossflow fan and motor. • Remove the screws of both sides and center securing the upper air-guide. • Remove 2 screws fastening the bracket of door switch.

Door Switch
R

• Remove a bearing assembly by removing a screw and the bearing cover. • Remove 4 screws securing the motor cover. • Loosen the screw securing the crossflow fan to the fan motor shaft. (do not remove) • Remove the crossflow fan by sliding it out from the shaft of fan motor.
Motor Cover

Bearing Cover
R

Bearing

5. Remove the control box Assembly. • Disconnect the step motor connector, fan motor connector, display PCB connector, thermistor connector and door switch connector from the main PCB. • If necessary, disconnect power supply cord and connecting cable from the terminal block and remove the cord clamp screw. • Remove 2 screws securing the control box and pick out the control box carefully.

R

130 Multi type Air Conditioner

Disassembly of the parts
6. Remove the front panel. • Remove the screws of both sides fixing the front panel. • Push the upper side of front panel strongly to pull out the front panel from the inner hook of diffuser frame. • Pull down the front panel carefully not so as to harm the display PCB wires and thermistor wires.
Diffuser frame Diffuser frame Hook Front Panel Front Panel
R

7. Remove the diffuser assembly. • Remove the screws of both side of diffuser assembly. (4 pieces) • Push the upper side of cabinet strongly to pull out the inner hook of diffuser frame from the cabinet hole. • Take up the diffuser frame carefully not so as to harm the display PCB wires and the step motor wires.

Diffuser frame Hook Cabinet

R

8. Remove display PCB assembly. • Remove the screws at the both side of display cover. • If necessary, disconnect the display PCB connector from PCB assembly. • Remove 2 screws of PCB assembly.

Display Cover

Service Manual 131

Disassembly of the parts
9. Remove the vane-upper, vane-lower and step motor. • Remove 2 screws securing the step motor assembly and pull it out from the vanes carefully. • Unhook the vanes from the vane supporter and remove the upper vane and lower vane by pulling the center of vanes with care.

Step Motor Vane Supporter

Lower Vane

Upper Vane

10. Remove the drain pan assembly. • Remove the both side of screws. (4 pieces) • Pull out the drain pan assembly. • Be careful not to harm to the EPS packing of drain pan and the tubings of evaporator.

11. Remove the evaporator. • Remove the screws of both sides securing the EVA barrier-R/L on the side cabinet. • Remove the screws which fasten the barrier on the evaporator and take out the barrier assembly. • Remove the evaporator assembly by sliding toward arrow mark. (As shown in figure)

EVA. Barrier-L

Side Cabinet

EVA. Barrier-R

132 Multi type Air Conditioner

Schematic Diagram

5V
R04F,10K

R02F,10K

SLIDE S/W REMO

1
R03F,1K R01F,1K

2

3

4 MICOM GMS81516
5V
R02H 12.1K 1% 1% 6.2K 12.1K 12.1K 12.1K 12.1K 12.1K 12.1K R04H R16H R15H R14H R12H R11H R13H R16G,6.8K R15G,6.8K Q13G KTA1270Y

DISPLAY

DC 5V

1

1

7

7

GND

REMOCON

2 RD Wt R/W C SYNC R30 64 R31 63
C02F,0.01/50V C01F,0.01/50V R14G,6.8K

2

6

6

Vout

1
C01M

Vdd MP AVss AVref R67/AN7 R66/AN6 R65/AN5

3
R13G,6.8K Q12G

3

5

5

LED4

Vcc

2 3 4 5 6 7

4 R32 62 R33 61 R34 60 BRK R35 59 BRQ R36 58
KTA1270Y

4

4

4

LED3

0.01 50V

5
R12G,6.8K R11G,,6.8K Q11G KRA1270Y

5

3

3

LED2

PRE AMP ASSY TFMS2380B

C02L

6

6

2

2

LED1

7

7

1

1

CN-DISP1

220uF IC02M

CN-TH
PIPE-TH

10V

8 9 10
R03H,1K

R64/AN4 R63/AN3 R62/AN2
11

HALT R37 57 D0 D1 R61/AN1
12

KID65004AP

CN-DISP2

R06G,220

1 2 3
R01H,1K

1 2 3 4
C01H C02H

R00 56 R01 55 D2 R60/AN0
13 14 15

1 2

16 15

1 R02 54 D3 R57/PWM1 R56/PWM0 R55/BUZ
16 17 18 19 20 21 22 23 24
3 14

1

R01G,220

2
4 13

2

R07G,220

3 R03 53 D4 D5 D6 R54/WDTO R53/Srdy R52/Sclk R51/Sout R50/Sin R47/T30 R46/T10 R45/EC2 R44/EC0
TX RX
5 12

3

R02G,220

4
ROOM-TH

4 R04 52 R05 51 R06 50 D7 A0 A1 A2 A3 A4 A5 A6 A7
25 26 27
6 7 11 10

4

R04G,220

5

5

R05G,220

0.01 50V
CN-U/D

6 EEPROM R07 49 R10 48 R11 47 R12 46 R13 45 R14 44 R15 43 R16 42 R17 41 R43/INT3 R42/INT2 R41/INT1 A8 R20 40 A10 R21 39 A11 R22 38
DC 12V
8 9

6

R03G,220

7 S 1 C 2 D 3 Q 4 8 VCC 7 DU
R01T,10K R02T,10K R03T,10K

7

RD
1 1

DC 12V

OR
2 3 4 5 15 4 3 2 1 16 17 18 5 14 5 4 13 6 3 12 7 2 11 8

DC12V

10
OP6 XXXK OP5 XXXK OP4 XXXK OP3 XXXK OP2 XXXK

9

OP1 XXXK

DC 5V

8

8

DC 5V

YL PK BL
STEP MOTOR UP/DOWN

DC 12V

1 6 ORG 5 Vss

1

R04T,10K

R05T,10K

DC 5V

2

2

3

3

4

4

5

5

6

6

7

7

IC01M

8

8

Schematic Diagram

KID65084AP

9
SSR-MOTOR

9

CN-SUB
R02E,20
R02A,4.7K R01A,1K

28 R40/INT0
5V

A12 R23 37
29
R03A,100 KIA7036P C01A 0.01 50V

RESET'
30
BZ01E R01E,1K
IC01A C02A 10uF/50V
+

A13 R24 36 XIN
R01B,1M

Q01M KRC107M

Electronic Control Device

A14 R25 35
31 32
R02L,10K
OSC01B CST-8.00MTW

XOUT VSS

A15 R26 34 A16 R27 33

5V

IC01K(TLP621)

R01L,1K
REMOCON

D01K 1SR139-600

RX

C01L 680pF 50V
TX

C01K 0.001 25V

R02K,1K R01K 10K DC

3

2

5V

4

1 IC02K(TLP627) 2 3

R03K 1K

ZNR01K 14D271
NF01M

ZNR01M INR14D471K

CN-FAN

NF01M

3

3

R02C,4.7K

R01C,1K

1

4

SSR-MOTOR

2

2

INDOOR
5V
R04C,10K
FREQUENCY

R03C,20K R05C 4.7K M C02C 0.015 50V Q01C KTC3198Y C01C 0.01 25V
DC 5V
C06D 0.01 25V +

Q01K KRC102M

R04K 680

R05K 25K,3W,1%

R01M,120,1/2W

C01M,0.1,AC275V

1

1

FAN MOTOR

IC02D
O 7805 C05D 470uF 16V I D02K 1SR139-600

3

3

COM

C01J 0.1, AC275V

NF01J

FUSE 250V/T2A

FREQUENCY

2

2

LIVE

1. Indoor Unit

1) Split Type

IC01D
DC 12V
C04D 0.01 25V + O C03D 470uF 25V 7812 I + C02D 0.1 50V

D01D 1SR139-600

D02D-05D 1SR139-600

ZNR01J INR14D471K SVC561D-14A

1

1

NEUTRAL

CN-POWER

C01D 2200uF 35V

POWER TRANS
6171AQ3124C

Service Manual 133

Schematic Diagram 2) Art Cool Type

134 Multi type Air Conditioner

Schematic Diagram 3) Art Cool Deluxe Type

Service Manual 135

DC310V

C05D 681

CN-POWER

2
5V C10D 103 C11D 223/1KV C12D 103/1KV NF NTC01D 10D-9 ZD01D P6KE200A C06D 3 4,5 IC02D(TLP521) EN BP R03D 150 ZD02D 11V C04D 103/250VA C07D 330uF/35V
470uF/35V

2
D03D UF5402 3.3uH G C08D 104
R04D

LIVE
1 2

250V/ T3.15A,3A

ZNR01J INR14D561K

NF01J 22mH/3A
R01J D01D 1M,1/2W 1N4007

12V
L01D

1 6,7

S/Trans

IC03D KID78L05BP I O 7805

C09D 220uF/50V

IC11K(TLP621)

R11K 10K

C11K 102

M_RTX
R13K 1.5K

RX
2 1 3 4

Multi_RX

R12K,1K

DC 5V
M_RTX
D12K 1SR139-400 D11K 1SR139-400

DC 5V

1
AC_N C01D 10uF/ 400V IC01D TNY255P S 3,7,8
CN-OUT RY-OUTFAN 1 RY-4WAY 3 3 RY-4WAY 1 RY-OUTFAN

1

NEUTRAL
3 4

39

R16K 10K 3 4
R15K 82K/3W

3 3
M_RTX
RY-COMP

SIGNAL

C03J 10nF 275V C01J 100nF 275V D02D UF4005 D 5 4 TNY 255P 2 1 C03D 103 C02J 100nF 275V

2 1 IC12K(TLP627) R14K 1K

TX Multi_TX

DC 5V

Q11K

KRC104M

AC_L

DC 12V DC 12V STEP M
RY-HEATER

IC02M KID65004AF IC02M KID65004AF

L01K D01K DAN212K 100nH 5V

12V

DC 12V

CN-REMO
유선_TX

STEP M5

RY-HEATER 5 5

1
P76 P77 P00 P73 P72 P71 P70 VDD (AIN7)/P67 (AIN6)/P66 (AIN5)/P65 (AIN4)/P64 (AIN3)/P63 (AIN2)/P62 (AIN1)/P61 P14(PPG) (AIN0)/P60 P01 P02 P03 P04 P05 P06 P07 P10(INT0) P11(INT1) P12(INT2/TC1) P13(DVO) P74

P75

64 63 62 61 60 59 58 57 56 55 54 53 52 51 50
5V

HEATER 4WAY
Q01K

Q03K KRC104M

R02K

L03K

3

MED

4.7K

2 3 4 5 6 7 8 9 10 11 12 13 14 15
Q D
2 3

2 1

DC12V 3 Signal 2 GND 1

CN-D/PUMP
Drain Motor

D/PUMP OUTFAN A/C COMP
1 1

L02K

KRA104M

STEP M
RY-D/PUMP

STEP M2 STEP M3 LOUVER HIGH

C05K C04K C06K 104 103

3

3

CN-LOUVER
Louver Motor

STEP M

R07H 12.1K 1%

R05H 12.1K 1%

R03H 12.1K 1%

5V

12V
5V

R01K

1 3 RY-LOUV 3

1

STEP M4

STEP M

R08H 12.1K 1%

R06H 12.1K 1%

R04H 12.1K 1%

R02H 6.2K R01H 1% 12.1K 1%

1K
유선_RX

C03K 102

D02K

CN-MOTOR1 1 2 FAN RY-L 3 RY-M 4 RY-H CN-MOTOR2
SSR NF01M NF01M

1 2

LOW
IC01M KID65004AF

OPTION6 OPTION5 OPTION4 OPTION3
3 3

C01K 102

C02K 102

Q04K

DAN212K

KRA104M


DC 12V
MOTOR 3 4
REMO 50/60Hz

CN-PIPE
3 3

Q02K KRC104M

REMO
C02L 681

OPTION2 PIPE TH

1

1

FREQ

5V

5V

R03C 10K
AC_L
1

R06C 10K

1 FAN 2
ZNR01M

1 2 3

IC01C

BZ01E
R02E 20

R04C 4.7K

ROOM TH OPTION 1

1

50/60Hz

MOTOR 3

PHASE
EERROM 1 S

CN-ROOM CN_M C
AC_N

R02C 1K R01C 200K/2W

Q01C

R05C 1K

C01C 103

R02A 10K
5V
1

R01E 1K
5V
VCC 7 DU C 8

16 17
C

P15(TC2) P16

VARF VASS

49 48 18
P17 P54 SB3

5V
12V

KIA7036P
+ 2

3

R01A 1K

GND

C01U 103 OR6 OR5 OR4 OR3 OR2
D

1
OR1 C02H C01H 103 103
5V

1 2 2

12V 5V

IC01A 3.6V C01A
3.3uF /50V
5V
5 VSS

C02A 102

6 ORG

47
Q 4

S_B3

S
GND

19 20
NC

P20(INT5/STOP) TEST

P53 (PWM/PDO)/P52

46 45 21
P21(XTIN) (INT4/TC4)/P51

SB2 SB1

S_B2
5V

R01U 10K
S_B1

GND

3
C02U 103

3 4
SB0
Multi_TX

GND

4 5 5

PLC_SEL Multi_TX

DISPLAY
GND

1 2
LED1

1 2 3 4 5 6 7
5V

R01L 10K R02L 1K

44
REMO

S_B0

Vout

NC RESET XIN
R01B

Vcc

3
R04L 1K

23 24
1.0M

RESET XIN XOUT
OSC01B 8.00MHZ

(SO2)/P47 (SI2)/P46

42 41 25 26
LED1 XOUT VSS (SCK2)/P45 (SO1)/P44

CC TX

중앙_TX 유선_RX

GND 5V

1 2

1 2

GND 5V

PRE AMP TFMS-2380B LED3

LED2

4
R05L 1K

5 6 7

40 39 27
CN-DISP

유선_TX

12V

3
SO1/PLC P30 LED2 (SI1)/P43

3 4 4

12V SO1

Force SW

LED4

R06L 1K

38 28
5V

SI1/MULTI TX P31 LED3 (SCK)/P42 SCK1/MULTI RX

5

5

SI1

37 29
P32 NC

6

6

SCK1

36
R02F R01F

7
LED4
1K 1K

7

CS0

CN-LOUVER 1 3 3 1

30
LOUVER FLOAT

P33

NC

35 31 32
P34 P35
C02F 103 C01F 103

8
NC NC

8

CS1

Schematic Diagram

34 33
CSO

CN_ZONE

CN-FLOAT 1 2 1 2

CSI

136 Multi type Air Conditioner 4) Duct Type

R03L 1K

22

P22(XTOUT)

(INT3/TC3)/P50

43

CC RX

Multi_RX

6
중앙_RX

6

Multi_RX

1
LEV

CN-LEV 2
DC12V

SW-HIGH

6

6

3
5
3 A 5 4 5 3 E F 0 1 6 2 B C D 1 10K R16G 6 4

5 4 3

MN101C30A QFP64
12.1K, 1% R21H
9 8 7

MICOM
20K R14G 40K R15G

4 3

4

37 P60/AO 38 P61/A1 39 P62/A2
12.1K R12G

PA0/AN0

62
5V
12.1K, 1% R22H 12.1K, 1% R23H
80K R13G 2

PA1/AN1 PA2/AN2
5V

63 64
SW-LOW

WH YL OR BL BR RD
2 1 1 2

STEPPING MOTOR CN-U/D2 BL 5 5
R11G 1K 3 A B C 4 5 3 E F 0 1 6 2 D 5 10K R10G 6 9 8 7 4

(UP/DOWN)

40 P63/A3
12V
IC01M

9

8

61 Vref1 2
CN-TH2 5V
2 1 1
ROOM-TH
R05G 1K 80K R07G 2

OR1H F1
20K R08G 40K R09G

OR2H F2

OR3H F3

PK 4 3 2 2 3 4 YL OR

D/PUMP
3 2 3

7

PA3/AN3 PA4/AN4

41 P64/A4 42 P65/A5 43 P66/A6
OR5H
12.1K R06G

COMP FAN
5 4
R03H 6.2K 1% R01H R02H 6.2K 12.1K 1% 1%

6
OR4H
1

C02G 103

C01G 103

PIPE-OUT_TH

RD 1 1

CN-TH1
4 3 2 4 3 2 1 1
OR6H

STEPPING MOTOR

(UP/DOWN)

12V
1K R04H 1K R05H 1K R06H
5V
C03H C02H C01H

4WAY INDOOR FAN
3

44 P67/A7 47 P72/A10 48 P73/A11
PA7/AN7
R01P 10K
8
100nH L01K D03K DAN212K

CN-U/D1 BL 5 4 3 2 2
IC02M

5) Convertible Type

5 4 3 1

2

PA5/AN5 PA6/AN6

3 4 5
1 2
12V 5V
4.2K R09K

PIPE-TH

PK

49 P74/A12
103 103 103

YL

12V

9

8

OR

19 18
SDA SCL

MODE/WC

7 6 5
EEPROM IC 1
C11K 104 Q01K KRA104M Q03K KRC104M C12K 103

RD 1 1

R02E,20

3 4

12V
R01E 1K

BZ01E PKM13EPY-4002

SBT1/P05 SBI1/P04 20 BUZZER/P06 SBO1/P03

17
R01F,1K

CN-REMO
L03K

3 2 1
L02K

3 2 1
CN_INSTALL
1 3 1 3

DISPLAY
7

P54 36
Force
C01F 103

GND

1 2
RECEIVER
R04G,330,1/4W

1 2 3 4 5 6
R01G,330,1/4W R02G,330,1/4W R03G,330,1/4W

6

50 P75/A13 51 P76/A14
R02F 10K

5V
R08K 1K

12V
C10K 102

Vout

HVB OUT
4

5

52 P77/A15
TM3IO/P13
C08K 102

5V

Q02K KRC104M D02K DAN212K

Vcc

LED4 3 4 5 6
1 2 3

25 24
C09K 102 Q04K KRA104M

57 P83/D3 58 P82/D2 59 P81/D1 60 P80/D0
SEL

LED3 LED2

TM2IO/P12 IRQ3/P23 IRQ2/P22 IRQ1/P21 IRQ0/P20

R07F R05F 1K 1K

5V

1 2
R08F,1K

1 2 3
R06F,1K

PRE AMP ASSY TFMS2380B

30 29 28 27
C03F

3 4
5V
C04F

LED1 7
+

4

7

DC 5V
IC03M

12V

9

8

8
FORCE

8

16 P02/SBT0 15 P01/SBI0 14 P00/SBO0
D7/P87
R02A,4.7K

R07D 12K Q01C KTC3198-Y 2SC5343

CN-DOOR

C02L 4.7 50V

Rx

INT
R08D 56K

CN-CC

DC 5V DC 12V DC 5V
R01A 1K 1 3 3.6V 2

Tx

5V
R02L,1K R01L 5.1K R04F,1K C01L 680pF/50V

1 2
R06T,10K R05T,10K R04T,10K R03T,10K R02T,10K R01T,10K

1 2 3
C01A 10/ R03A 100

1 2 3 4
32 P50/NWE
50V

53
5V

receiver
3 3

1 3 4 5
33 P51/NRE
OSC1 NRST/P27

1
21
IC01A

Telecontrol
4 5 6
34 P52/NCS 35 P53/A16 22 P10/TMOIO 23 P11/TM1IO
Vss 10 XI 11 MMOD
C01Z 103

2

2

C02F,103

CN-FLOAT

R03F,10K

2

2

3

3

5V

1

1

5 6 7 8 9
NU 13
12,26,31,45,46 54~56

OSC2

8 9
1M R01B
5V
OSC01B

6 7 8 9

7 8 9
Vdd

Vref+

6 7

Option
CN-HVB

3 2 1 1 2

3

HVB

SEL
3
2 1

JP1 JP3

3 2

4WAY

2

1
HVB OUT
CN-CONT

1

INDOOR FAN INT
JP4 JP2 JP5 JP6

COMP 5V
12V

Tx FAN Rx D/PUMP

3
2 1

3 2 1
CN-12V

2 1

12V

DC PART
7 8 9 10

CN-ACDC

1

2

3

4

5

6

CN-ACDC

1

2

3

4

5

6

7

8

9

10
D/PUMP 12V
RY-FAN RY-4WAY RY-COMP

IC01J TLP762JF

12V

1 2 3

R03J 680 1/2W
6

NF02J

AC PART FOR NORMAL
12V 5V COMP
IC04D S78DL05L 1W C03D 681

T1

FAN 4WAY INDOOR FAN INT

FAN 4WAY COMP D/PUMP
1K/1W
SMPS D07D UG2D NTC SCK-102

INDOOR FAN

TR01J SM1L43
RY-D/PUMP CN-MOTOR 3 3

T2

R04J 560 1/4W 3216

4

ZNR02J TVR10561

INDOOR FAN MOTOR

SH-CAPACITOR

NF02J D05D 1N4007

R02J 100,1/2W

12V
5V
7805 O I

L1 ZBF503D

2 1

2 1

+

5V
C04D 470/35V/SD SD01D STO2D-200 + R04D 27k 1/8W 2012 R05D 300K 1/4W 3216

C07D 104 50V C06D 330 25V SD

R03D 39 1/8W 2012

BD01D DF08M

R01J 120, 1/2W
3 4

RY-D/PUMP G5N-1A(G5NB-1A)

1 3 C03J 100nF 275V/436D RY-FAN G5N-1A(G5NB-1A) T-BLOCK

1 3

Drain Motor

CN-D/PUMP

OUTDOOR

+ C09D 220 10V SD C08D 103 50V R02D 20K

1 2 ZD02D BZX55C11 DC LOW VOLTAGE GND

4 3

D 5 IC02D TLP181(V4 BL) EN 4 BP 1 C05D 472M DC HIGH VOLTAGE GND C02D 104

INT

3

4

5

5

C01D 15uF 450V/SG

4

1 2 3 IC03D TLP181(V4 BL) DC HIGH VOLTAGE GND DC LOW VOLTAGE GND IC01D TNY266P S 2,3,7,8 D08D LL4148 R06D 300K 1/4W 3216
NF01J 15mH/1A

3

4

RY-4WAY G5N-1A(G5NB-1A)

4 4 FUSE 250V/T2A 4 3

FAN MOTOR

4-WAY

2 1

2 1

RY-COMP G4A-1A-E-LG 4

2(N)

1

COMPRESSOR

DC HIGH VOLTAGE GND

3 ZNR01J TVR10561 C02J METAL FILM 47nM/275V/435D
C01J METAL FILM 100nM/275V/436D

1(L) L 1 CN-TAB1 1 N

CN-POWER
AC220~240V 50/60Hz

Service Manual 137

Schematic Diagram

1) A2UW186FA0, A3UW246FA0, A4UW306FA0, A2UW146FA0, A3UW186FA0, A4UW146FA0

+5V
5V
D06N 1N4148 D01N~D04N 1SR139-600
~ +

CT01N

CN_TH1
1
R11H R14H R15H R12H R13H

Discharge Suction
2 3 4 4
R01H~R05H 1K
~

1

CT_AD
R02N,1.65K,1% C01N 100UF
+

2 3
1UF/50V C11H~C15H

18K 6.2K 6.2K

6.2K

12.1K

C02N 103 D05N 1N4148 R01N 680, 1%

OUT_Air
CN_TH2
1 2 3 4 4 3 2 1

5V 5V
R16H R17H R18H R19H

OUT_Pipe
DISCHARGE
CN_TH3
2 1 1 2

IC01M GMS81516
1 P70(AIN10) 2 3 4 5 6

R20H

C17D 103

6.2K

12.1K

6.2K

6.2K

6.2K

VDD P71(AIN11) P72(AIN12) P73(AIN13) P74(AIN14) P75(AIN15) P67(AIN07) P66(AIN06) P65(AIN05) P64(AIN04) P63(AIN03)

64 63 62 61 60 59

+5V TSUP_E TSUP_D TSUP_C TSUP_B TSUP_A RX_F

Pipe F
OUT_AIR
+ + + + +

4

4

3

3

OUT_PIPE TSUP_F
C01H 104 C03H 104 C04H 104 C05H 104 C02H 104

2

2

CT_AD DC_LINK
D01M
EG01C

3

3

4

4

R10T~R15T, 270

7 P76(AIN16)

P62(AIN02)
H/Press INT
8 P77(AIN17)

58

Q01M KRC107M

P61(AIN01)
W2 V2 U2 W1
9 P00(W) 10 P01(V) 11 P02(U) 12 P03(W)

57

2

2

P60(AIN00) VREF VASS P54
V1 U1
13 P04(V) 14 P05(U)
P53(HPWM0)
P52(PWM4/PDO4)

56 55 54 53 52 51

RX_E +5V GND TX_E RX_D TX_D RX_C
5V
C06H 104 C07H 104 C08H 104 C09H 104 C10H 104

3

3

4

4

311V

+5V
R03T,1K
7 R02T 7

C31K 15uF,450V
18 U1 1

10K
Q01T

RY-PWR F0_IPM

107M
C04T 103 R04T

R01T 10k

15 P06(EMG1) 16 P07(CL1/PDW1)

P51(INT4/TC4) P50(INT3/TC3)

50 49

TX_C
IPM_5V_ENB
17 P10(INT0)
P47(SDA/SO)

R31K 1M,1/2W
48

RX_B
12V

BUS_COM

CN-IPM

U
+

V

W

U_

V_

W_

Fo

5V

C01T 103 C02T 103
C03T

1K

LED01T (RED)
+5V

RY-HEATER
TEST S/W R05T
17 U1 16 2

18 P11(INT1)

P46(SCL/SI)

47

TX_B
RY-4WAY
U1 3

C13K 471,250V
19 P12(INT2/TC1)

P45(SCK)
RY-SV
1K
15 U1 4

46 20 P13

RX_A P44(TxD)
RY-FAN_1H
45

1 1
1 2 3
IC10S
4 3

2 8 8
1 2 3 4
R08T

3 9 9
10K 47uF/50V

4 6 6 7 7 4 5

5

TX_A
R07T

5V

BUS_ADDR_LEV

2

3

1K

R06T

14

IC01S
3 2

4
IC06S IC05S IC07S IC09S IC02S IC08S IC03S IC04S

56K
13

U1

5

RY-FAN_1L
LED02T (YELLOW)
U1 6

22 P15(DVO/TC2)

P42
RY-FAN_2H
23 P16(PDV1)

43

LEV_CTL_B P41
42

RC01M

21 P14(PPG)

P43(RxD)

44

LEV_CTL_C LEV_CTL_A

RY-SV

TLP559*6 TLP521*4
1 5 6 8 2

+5V

R02A,4.7K IC01A KIA7036P C04A 102 R03A,100
+

R01A,1K

12

CN_Test 2

+5V
C01A 102
11 10

U1

7

RY-FAN_2L
U1 8 9

24 P17(PDU1)

P40
RY-START
+5V
R30M

41 25 P20(INT5/STOP)
IC04M KIA65084 4.7K
D09D 1SR139-400

LEV_ENABLE P37
26 TEST 40
LEV_B_1

Q01Z KRA107M

R12M~R22M 4.7K

CN-SV

C07S 104 R01S 20K C08S 104 R02S 20K R03S 20K C09S 104 C10S R04S 104 20K C11S R05S 104 20K

C12S R06S 104 20K

C03A 10uF/50V

P36
+5V +12V
IC04D

39 27 P21
C04M 104

LEV_B_2

RY-4WAY

RC02M

S-TRANS CN-GATE2
D10D
17
+

P35
7805

38 28 P22
R08D 1.2K
+ + +

LEV_B_3

D08D RU2YX

P34
29 RESET 30 XIN

37

LEV_B_4

CN-4WAY

9

6 5 4 3 2 1

6 5 4 3 2 1

15 V

P33 P32
16

36 35
C03D 2200UF 35V
C04D 680UF C15D C16D 103 104 C05D 220UF 16V

LEV_A_1 LEV_A_2

RY-HEATER

C06D 220UF 35V
15 V
+

C04S 10UF C05S 10UF
+ +

C06S 10UF

D11D C07D 220UF 35V

15 8

C14D 473

R09D 1K

OSC01B 16MHz

31 XOUT
R01B,1M

P31
32 VSS
DC LINK
IC03D,SE012N
14 1

34

LEV_A_3

P30
LED01Y(GREEN)
R03D 47K 3W

33
R05Y 15K R03Y 82K 1/4W R02Y 70K,3W

LEV_A_4

RY-FAN2_L

CN-HEATER

CN_TH5

TX_F

+

+

+

+

+

1

1

CN_TH4

1

1

CN_TH3

SUCTION

R06H~R10H 1K

C16H~C20H

1UF/50V

1 2 2 3 4 5 6 8 9 3 4 5 6 8 9

1

+

D13K 100D-9 NTC01K 1SR139-600

2

2

1

1

2

2

1

1

2

2

1

1

G/Y

3

3

+

7

7

MOTOR
7 6 5 4 3 2 1
15 V

2

2

7 6 5 4 3 2 1

13
+

D05D EG01C

R07Y,1K
C08D 220UF 35V
12 2

C12D,100P,1KV R04D 10,1/4W
3

Q01Y C3198

D06D 1N4937 C02D 47UF 50V
+

ZD01Y 20V 1W

R01Y 70K,3W

RC03M

D12D

C11D,473,630V

+5V 1/4W

+5V
Q02Y C3198

H/Press INT

RY-FAN2_H
IC01V TLP621-BL
FB01D FBA04HA900
IC02D TLP621-BL

FAN2
RY-DISC
R06Y,10K IC01Y TLP621 R04Y 2.2K 1/4W C01Y 222

1

1

+12V

R01V 62K,3W R02V 1K
1
15 V
+

D01V 1SR139-600

R03V 33K

R04V 10K Q01V C3198
4
R11Y,R12Y 56K,3W RY-DISC

R06V 1K

R04M~R20M 68K

RY-FAN1_L
C01V 102
1/4W
D13D
11

CN-FAN2

G/Y

3

3

C01S 10UF
+ + +

C02S 10UF

C03S 10UF

IC01D
FB02D R05D 5.6K 1/4W

R05V 10K
D01D~D04D 1SR139-600 R01D 27,5W NF01J

MOTOR
RC05M

2

2

9 8

9 8

Vupc Up Vup1 Vvpc Vp Vvp1 Vwpc Wp Vwp1 1 2 3 4 5 6 7 8 9 10 11 12 Vfo Ufo Wfo Un 16 Vn1 14 Vn 17

Br Wn F0 Vnc 13 18 15 19

RY-FAN1_H
C09D 330UF 35V
10

2
5 R06D 680,1/4W 3 C13D 680P D07D 1N4937 50V

G6551

ZNR01D ZNR561D14

RC04M
R07D 1 ,1W
+

CN-FAN1
CN-GATE1
4

GND In Vcc Fo GND Vcc In GND TEMP Out Si Out Si GND Out Si GND GND Out Si GND Out Si GND In GND Vcc Vcc

GND In Vcc Fo In Fo

Fo

Fo

Vcc

In

Fo
GND

Vcc

In

Fo
GND

RY-START
Out Si GND Out Si GND

C01D 68UF 400V

R02D 82K,1W

R00D 1M,1/2W

C02J 104,275V

C01J 104,275V

RY-PWR CN-DC CN-PWR

1 1 -

2 2

PTC

4

3

2

1
CN-AC

CN-POWER

IPM
PM50CSD120

+
W N B
NC

4
HIGH PRESS Comp OLP
REACTOR 28A 0.68mH
RM20TPM-2H AC440V/DC1600V, 40A

3

2

1

1 1

1 1

2 2

P

U

V

RED

DSA-362MA

561

WHITE

Schematic Diagram

L2:1.5mH

L1:2.0mH

Power Relay
1uF

BLACK

472 332

1W/1M 2.0uF

GND

1uF

N
COMP

400V 2200uF
800V,0.27uF

+

100K,2W
CT01N/30A 1:3000

472 332

1W/1M 2.0uF

821 (102)

500V,25A

1uF

1uF

T

400V 2200uF

+

100K,2W

MAGNETIC S/W 480V /40A

472 332

1uF

1uF

1W/1M 2.0uF

821 (102)

500V,25A 561

S

821 (102)

R

472 332

500V,25A

3 ,380V,60Hz CN-INPUT

138 Multi type Air Conditioner

FUSE 250V/5A

FAN1
+

1

1

2. Outdoor Unit

~

Schematic Diagram

DISCHARGE2 CN-TH4

1 1 2 2
+5V

3
R16H DISCHARGE1 CN-TH3 R08H R07H R06H R05H R04H R03H PIPE CN-TH2 4.7K 2012 6.2K,1% 2012 12.1K,1% 2012 6.2K,1% 2012 18K,1% 2012 18K,1% 2012 12.1K,1% 2012 1.5K,1% 2012 R15H R12H R11H R14H R13H R10H R09H

3

1 2 3 4 4 2 3

1

C06M~C11M 104 R09M 10K IC04M 74HC245AF
QE +5V
C07H C08H C11H C09H C10H C12H

CN_LEV1

+15V

1

1

+5V

SUCTION

2

2

C03M 104
1

3

3

1 2 3
SW1 OR1 LONG C06H 10uF 50V 50V
LOW-V

1 2 3 4
+
C05H 10uF 50V 50V 50V 50V JIG POINT R14T 1K 2012 10uF 10uF 10uF 10uF R03N 20K 2012 C02N 102K 2012 C04H C02H C01H C03H C.T NORMAL R01H R01H~R08H 1K 2012 C07H~C12H C102*7 R04T 4.7K
INPUT VOLT

R02H

20

VCC A0 A1 A2

IC07M KIA65084
2 3

4

4

LEV1

19

CS

5

5

CS-1

OUT AIR

4
+ + + + +

1 2 3

18

B0

1

18

6
4

6

HEAT SINK

1
PIPE LENGTH

1 2
R01P~R04P 470K 1/2W 1% R05P~R10P
2012

C02T 102K 2012

17

B1 A3

2

17

CN_LEV2
ER_CODE, INDICATOR
5

16

B2

3 A4

16

1
LED01G : RED_10자리 LED02G : GREEN_1자리
6

1

2
C05P 102 +5V C09D 104 L03D 12uH R01L 4.7K R02L 4.7K +5V +5V 20K
2012

CN-TH1 5V : NORMAL GND : LONG C01L 103 2012 R15P~R17P 4.7K 1/4W(or 2012) G

+15V +5V

15

B3 A5
TX_JIG_S RX_JIG_S
7

4

15

2

2

14

B4

5

14

3

3

W V U
R05P

9 8 14

3 1 8
100 99 98 97 96 95 94 93 92 89 88 90 91
2012 2012

IC01M KID65004AP
LED0 1 18 R01G 1.5K

A6 +15V LED01G A7

8 9

13

B5

6

13

4
85 84 83 82 81

4

LEV2

R06P A2 R07P R18P R08P

Vcc

12

B6

7

12

5
87 86
GND
10
P03/AN03 P05/AN05 P07/AN07 P02/AN02 P04/AN04 P06/AN06

5
R02G 17 1.5K LED02G

5 4 2
R19P
P96 P95 P94 P93 P92 P91 P90 BYTE CNVss P87 P86 RESET Xout Vss Xin Vcc1

2
AVcc P10/AN0 P101/AN1 P103/HEAT_SINK P105/PIPE P107/DISCHARGE1 P97 Vref AVss P102/AN2 P104/OUT_AIR P106/SUCTION

7 6
1 2
SCL SDA

WP
P01/AN01 P00/DISCHARGE2

11

B7

8

11

6
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51
LED0 LED1 PCB Auto Check

6
LED1 2 3 4
IPM Fault Signal
P14 INT3 INT4 INT5 P20/AN20 P21/AN21 P22/AN22 P23/AN23

A1

N
C07Z,09Z,11Z : 104K 2012
R09P

3 4
3
EEPROM M24C08

9 16 15 5
INT_HP PSC F/Signal Phase Control DC Fan On/off
RY-PWR RY-C/COMP

10 RY-PWR RY-C/COMP RY-OIL/S 14 6 7 8 13 12 11 10
RY-OIL/S

CN_LEV3
R10M 10K IC05M 74HC245AF
RY-P/ICE RY-HEATER QE A0 A1 C01M 104
2012

7 1

SPM2 FairChild FSAM30SM60A FSAM20SM60A
4
R21P R10P

C08Z,10Z,12Z : 47uF 50V
6 12
+5V

R20P R18P~R20P 1K 2012

A0

5

+15V

1

1

+5V

R13Z~R15Z : 20 1/4W
5

2

2

D01Z~D03Z : 1N4937
6
+15V D01Z R13Z R11P~R13P 15K 1/4W 1% C04P 104 CN-WRITER IC01P KIA339A

7.5K 1/2W 1% C06P~C08P 102M

RX_JIG_PC

1 2
TX_JIG_PC

C04M 104
1 2 3

3

3

FAN FG

3

32
VCC VCC(WH)

P
VB

VB(W)

R07F 1K C03F 102

20

VCC

22

2012

IC08M KIA65084

4

4

LEV3

21

OUT COM C07Z IN(WH)
2012

+
C08Z
TXD-6

C01P~C03P 331
2012

31
VS(W)

W
VS IN

R14P 7.5K 1/4W 1%
RXD-6

+5V R02A IC01A 100 2012 KIA7036P 3 C01A 3.3UF,50V RESET OSC01B 4MHz R01B 0 2
+

R01A 4.7K R03A 1K 2012 C02A 102 2012 R18T 4.7K

19

CS

5

5

CS-2

18

B0

1

18

6

6

20

1
C03A 104

23
D02Z R14Z

VB

VB(V)

18 17

YL
1 1

WCN-W YL
VCC VCC(VH)

OUT
COM COM(H) C09Z C10Z +5V +5V

+
R01T 4.7K

MITSUBISHI M16C/62P Group IC02A
P85/NMI P84/INT2 P83/INT1 P82/INT0 P81/U P80/U

P24/AN24 P25/AN25 P26/AN26 P27/A7 Vss P30/A8 Vcc2 P31/A9 P32/A10 P33/A11 P34/A12

RY-P/ICE RY-HEATER RY-HOT GAS RY-4WAY

IC02M KID65004AP
1 2 3
RY-FAN(B)_H

A2 A3 16 15 14 4 13 RY-HOT GAS A4 RY-4WAY A5 RY-FAN(B)_H A6 RY-FAN(B)_L

4 5 6 7 8

17

B1

2

17

16

B2

3

16

CN_LEV4

15

B3

4

15

1

1

14

B4

5

14

2

2

BL
2 2

WCN-V BL VS
30

16 15 19
D03Z R15Z R07Z R08Z 4.7K 2K R02Z R09Z 2K R10Z 4.7K R11Z 2K R12Z 4.7K R01Z

V
IN VS(V) IN(VH)

+5V
RY-FAN(B)_L PSC(On/off) RY-FAN(A)_H RY-FAN(A)_L

A7 5 6 7 12 11 10 PSC (On/off) RY-FAN(A)_H RY-FAN(A)_L GND

9 10

B5 13 +5V B6

6

13

3

3

LEV4

12

7

12

4

4

RD
3
VB VCC VCC(UH) VB(U)

3

WCN-U RD
13 12

11

B7

8

11

5

5

9

10

OUT
COM C11Z IN(UH) C12Z R16Z 20A :47,1/4W,1% 30A :56,1/4W,1% R04Z R05Z R06Z R01Z~R06Z 100 2012 R20Z 390, 2012 3.9K,1/4W,1% C13Z 102K,2012 R17Z R03Z IN

+
PWM

ENABLE1

29

U VS
VS(U)

P35/A13

CS-1 P75/W P74/W P73/V P72/V
RXD0/P62 TXD0/P63 CLK1/P65 RXD1/P66 TXD1/P67 RST1/P64 EPM/P24 CE/P50
ENABLE2

8
P36/A14 P37/A15 P40/A16 P41/A17 P42/A18

9
CS-2
ENABLE3

11 14

R11M 10K
CS-3

CN_LEV5
C02M 104
2012

+5V

C19Z 400VAC 1.5uF
RSC

+15V

1
IC06M 74HC245AF
QE +5V RX-CC TX-CC R02T 4.7K
P43/A19 P26 39 P25 40 P23 42 P22 43 P21 44 P51 45 P46 48 P45 49 P44 P47 47 P60 P61 37

1

C05M 104
1

2

2

OUT(WL)
28

10 9 8
C14Z 104,2012

Nw C(SC) C(FOD) OUT(VL) VFO
COM(L) VFO CFOD

CSC

20

VCC A0 A1

IC09M KIA65084
2

3

3

LEV5

19

CS

4
50 35 38 36 46 32 33 34 41 31
3

4

CS-3

18

B0 A2
RXD-5 TXD-5 RXD-4 TXD-4 RXD-3 TXD-3 RXD-2 TXD-2 RXD-1 TXD-1

1

18

5
4

5

7 6
C01Z 471 C02Z 122 C03Z 471 C04Z 122 C05Z C06Z 122 471

27
IN(WL)

Nv

17

B1 A3
RX_Flash TX_Flash

2

17

5

16

B2 R17T 4.7K R16T R15T 4.7K 4.7K A4 A5 +5V A6 A7
6 7 8 9
+5V

3

16

CN_LEV6

Inv._COMP_BLDC Nu IN(UL)
25 NC
IN(UL)

IN(WL) OUT(UL) IN(VL)
3
+5V IN(VL)

5 4

15

B3

4

15

1

1

14

B4

5

14

2

2

26

13

B5

6

13

3
IC01K TLP421(Dip)
1 4

3

LEV6

COM(L) VCC
R18Z 4.7k
2012 2012

COM(L) 2
VCC(L)

12

B6 GND R06K
AC_COM

7

12

4
10

4

24 NC 1

11

B7
680

8

11

5
+5V R01C 12K,1% C06K 102K
2012 2012
2 3

5
ZD03K 68V
+5V

9

10

+

R19Z 20K IPM Fault Sig.

C15Z 104Z 25V
2012 2012 2012

C16Z 47uF 50V C17Z 102 C18Z 102

IC02K TLP421(Dip)
4 1

+5V
R12K 1.5K 1/4W 1% Phase Freq R03C 10K,1% C07K 102K Q01C KTC3198Y (DIP) TRANS1 50Hz,DC12V R04C 4.7K,1/4 1% R02C 47K,1/4 1% C01C 103K 50V
2012

R08K 1K 2012 R10K 10K
+5V

R14K 30K 1W
3 2

D03K~D08K 1N4007 R15K 30K 1W IC03K TLP421(Dip)
1 4

R06T 1K
D03K

R05T 4.7K
R01M~R08M 68K
R07K
680
2012
2 3

RX_JIG_PC

RX

CN_JIG_PC

1

1

VDC

TX_JIG_PC
AC_COM

TX

2 2 3 3
ZD04K 68V 3 AC(L) BD01C DF08M 5
~

+5V
C08K 102K +5V D02C 1N4148 D01C 1N4007
+

CN-COIL2

4
2012

4
+5V

2) A6UW406FA0/A7UW486FA0/A8UW566FA0

IC04K TLP421(Dip)
4 1

~

BD01S RBV2506 RBV1506 C01S 680UF 400WV C02S 680UF 400WV

+

+

+

+

D2 C03S 680UF 400WV C04S 680UF 400WV

D1

R07C 1K,1/4 5% INPUT VOLT 7 1
~

R09K 1K 2012 C09K 102K C03C 25V,47uF AC(N) C10K 102K
2012

R13K 1.5K 1/4W 1%
3 2

R16K 30K 1W

R07T 1K

RX_JIG_S
D04K R11K 10K R05C 12K,1% R06C 2.7K,1% C02C 102
+

2012

RX

1
R17K 30K 1W
2012

1

CN_JIG_S

CN-COIL1 AC (L1) D4
~

-

+

+5V

IC05K TLP421(Dip)
1 4

C03T 102K 2012
R38K
680
2012
2 3

R08T 10K

TX_JIG_S

TX

2012
AC_COM

2 2 3 3
ZD05K 68V
+5V

+5V

D3

4
IC06K TLP421(Dip)
4 1

4

REACTOR 26.8mH/ 9A 11mH/ 14A AC (N)

R10T 1K
R26K 1.5K 1/4W 1% R18K 1K 2012
3 2

R09T 4.7K
R30K 30K 1W

RX_FLASH

RX

1

1

CN_FLASH

+5V

TX_FLASH

TX

+15V +15V IC01S TLP251 IGBT GT50J102
7 2 6 3 4
2012

C11K 102K R03S 1.2K 1/4W AC (L1) 4 PSC On/Off
+

R22K 10K
2012

+5V
+5V

IC07K TLP421(Dip)
1 4

R31K 30K 1W
AC_COM

D05K

R11T 1K 2012 RX-CC
R39K CT01N Current Trans 3
~

R12T 4.7K

2 2 3 3

+5V

4

4

C05S 104

8 1

680

BD02S RBV1506
~

G D1 C09S 152J
5

BD01N DF08M

D2

R01S 10k 1/4W

R02S 220 1/4W

R02N 1.65K 1% 1/6W +5V AC (L) 6 1
~

D02N 1N4148

2012

2

3

ZD06K 68V C12K 102K
2012

+5V

IC08K TLP421(Dip)
4 1

C01T 102K 2012

RX

1
R27K 1.5K 1/4W 1% R32K 30K 1W

1

CN_CENTRAL

TX-CC

TX

2
C.T
R19K 1K 2012

2

Q01T KRA105
R06S 4.7K
2012

3
R01N 1K 1% 1/6W R07S 20K
2012

3

-

+

+
D01N 1N4148
1 4

3

2

C01N 220uF 10V(RN) PSC F/Signal

4
C13K 102K
2012

4
R23K 10K
+5V

D4 C09S 0.1uF +120 R04S 0.05 R05S 71.5k C06S 152J D01S 1N4007

~ D3

IC09K TLP421(Dip)
1 4

R33K 30K 1W
AC_COM

D06K

+5V

CN-COM
R40K 680 C07S
2 3

1
C08S 102K IC02S TLP421 +5V +5V D01Y 1N4148 IC01V TLP421_BL D01V 1N4007 R02V~R05V 47K,1/4W,5%
2012 2012
2 3

1
ZD07K 68V 102
2012

C14K 102K
2012

+5V

IC10K TLP421(Dip)
4 1

R20K 1K 2012 C15K 102K
2012

R28K 1.5K 1/4W 1%
3 2

R34K 30K 1W

2 2 3 3

TB2

R01Y R02Y 1% 270K 1/2W 1% 270K 1/2W

R24K 10K
+5V
4 1

IC11K TLP421(Dip) LOW-V C01Y 103K 50V,2012 R03Y 4.7K,1%
INT_HP
1 4

R35K 30K 1W
AC_COM

D07K

4 5

4 5

C4

C4

G

G

6
R41K R08V 1K
680
TXD-6
3 2
2012
2 3

6
ZD08K 68V R06V 1K,1/4 5% D01D 1N4937 C04D 470UF 35V L02D 12uH C08D 103 50V +15V C01V 102K
2012

N

N

L

L

AC_COM

C3
R01V 47K,1W,5% R07V 10K
2012

C3
C16K 102K
2012

+5V

IC12K TLP421(Dip)
4 1

RXD-6

3

2

C17K 102K
2012

R25K 10K

PTC

R37K 30K 1W

D08K

D02K 1N4007

R05K 50.5K/1W

+
IN GND

R02D

+
2K 1/2W
R102

C05D 220uF 35V

40 OHM +15V +5V

1
R101

13
C101

FAN ON/OFF Q01F
D101

Q03F

R06F 4.7K
1/4W

NF02J AC (L)
FAN FG

ZNR01J,02J SVC561

C01K 102/100V

NF01J J51~J56

J21~J26
OUT NC +15V +5V R01F RY-PWR G4A-1A-PE C07J 472M

C05J 332M L01D 12uH

3
D
D201

12
OUT

IC04D

1K

2012

C09J

R04J R03F 4.7K R05F 10K AC (L1) 1uF/ 275VAC C04J 1M 1UF 1/2W

9
NC

7805

RY-FAN(A)-H JQ1A-12V

R202

RY-FAN(A)-L JQ1A-12V

C06D 103
PC201

C07D 103
BP
C102

RY-FAN(B)-L JQ1A-12V

R02F PWM
S
PC201

RY-FAN(B)-H JQ1A-12V

5 6

FB

TNY 268

Q02F
R201

2012

2012

+

+

+
50V
D202

50V

C03D 220uF 10V

Q04F 1K
2012

C08J 472M

C06J 332M

275VAC

R04F 5.1K 1/4W

C02F 10UF /10V

6.8V ZD01F

RY-P/ICE G5NB-1A

RY-4WAY G5NB-1A

RY-HEATER G5NB-1A

RY-OIL/S G5NB-1A

RY-HOT GAS G5NB-1A

AC (N)

7
GND u-POWER MODULE uRM1515-2B C10D 102M GND C01D 1000UF 35V C02D 470uF 25V

Q01F,02F KRC104S(Chip)

Q03F,04F KRA106S(Chip)

C01F 103k 630V

RY-C/COMP G4A-1A-E CN-PRESS Vs CN-MOTOR1 7 7 YL 6 6 BL FG 5 5 WH Vcc 4 4 BK GND 3 3 2 2 1 1 RD CN-FAN(A) CN-FAN(B) CN-P/ICE CN-4WAY CN-HEATER CN-OIL/S CN-HOT GAS

R03J 20 1/4W,5%

J27~J32

R02J 20 1/4W,5%

J57~J62

R01J

20

1/4W,5%

SURGE DA-38-302MT-A21

2 2

1 1

4 4

3 3

2 2

1 1

3 3

2 2

1 1

2 2

1 1

2 2

1 1

2 2

1 1

2 2

1 1

2 2

1 1

BK

WCN_GND2

BK

WCN_GND1

H/P

L/P

DC FAN MOTOR

FAN MOTOR(L)

FAN MOTOR(R)

COMP (single)

COMP_AC_IM

+

R21K 1K 2012

R29K 1.5K 1/4W 1%

R36K 30K 1W

D01K 1N4007 R01K~R04K 11K/3W*4

ZD01K,02K 36V,1W

C2

C2

G

G

C02K 150uF/100V

CN-CP(L)

N

N

1

1

L

L

CN-CP(N)

1

1

C1

C1

20A/250V

FUSE

WCN_P(L) BR

C02J

222M

C01J 1uF/

275VAC

C03J

GR/YL

222M

GND GND

N

N

WH

WCN_P(N) BL

L

L

BK

TB1

AC-POWER AC220~240V/50,60Hz

Service Manual 139

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

VDC

BUS_ADDR_LEV

R01M 10K
5V
C01M 104

12V

1
IC05M KIA65084 IC01M QE A0

1

CN_LEV 5

2

2

BUS_COM 5V
DC310V R01K 1.5K
ERA15-06

IC02K(TLP627)

1 VCC

18

3 1 2
A1 245

3 20 19 3
A2 A3

2 CS_LEV12

17

4

4

3 B0

16

TX_D0
IC01K(TLP621)
D01K D07K ERA15-06

5 18 4 5
A4 A5

5

LEV5

4 B1

15

6 17 16 6 15 7 14

6

RX_D0

R07K,IK

R19K 1K

R25K 82K/3W

CN-DATA
1 2 3 4 2 3 4 5 6 5 6 1

C07B 103
B2 B3 B4 A6 A7 GND

1

1

CN_LEV 6

C02K 102 25V R13K 10K IC04K(TLP627) R02K 1.5K
ERA15-06

2
B5

2

5

14

3 8 9 10 13 12 11
B6 B7

3

6

13

4

4

TX_D1
IC03K(TLP621)
D02K D08K ERA15-06

7

12

5

5

LEV6

8

11

6

6

9

10

C08B 103

RX_D1
C04K 102 25V R14K 10K IC06K(TLP627) R03K 1.5K
ERA15-06

R08K,IK

R20K 1K

R26K 82K/3W

R02M 10K
5V
C002M 104

12V

1
IC06M KIA65084 IC02M

1

CN_LEV 3

2

2

TX_D2
IC05K(TLP621)
D03K

1 QE VCC

18

3 1
A0 A1 A2 A3

3 20 2
245

2 CS_LEV12

17

4 19 3 4 5
A4

4

3 B0

16

RX_D2
C06K 102 25V R15K 10K IC08K(TLP627) R04K 1.5K
ERA15-06

R09K,IK

R21K 1K

R27K 82K/3W

D09K ERA15-06

5 18 17 16 6
A5 A6

5

LEV3

4 B1 B2

15

6

6

C09B 103

1 15 7 14 8 13
B3 B4 B5

1

CN_LEV 4

TX_D3
IC07K(TLP621)

2

2

5

14

3
D04K

3
A7
R28K 82K/3W D10K ERA15-06

6

13

4 9
GND

4 12 10 11
B6 B7

7

12

RX_D3
C08K 102 25V R16K 10K IC10K(TLP627) R05K 1.5K

R10K,IK

R22K 1K

5

5

LEV4

8

11

6

6

9

10

C10B 103

TX_D4

ERA15-06

R03M 10K

IC09K(TLP621)
D05K D11K ERA15-06

5V
C003M 104

12V

1
R29K 82K/3W

1
IC07M KIA65084

CN_LEV 1
R23K 1K

2
IC03M QE

2

1 VCC

18

RX_D4
C10K 102 25V R17K 10K

2

17

4
IC12K(TLP627) R06K 1.5K
ERA15-06

4 1
A0 A1 A2

20 2
245

3

16

19 3 4
IC11K(TLP621)
A3
D06K

CS_LEV12

5 18 17 5
A4 B0 B1

5

LEV5

4

15

6

6

TX_D5

C11B 103

16 6
R12K,IK R24K 1K
R30K 82K/3W D12K ERA15-06

B2

1 15
A5 A6 B3 B4

1

CN_LEV 2
7 14

2
B5

2

5

14

RX_D5
C12K 102 25V

3
R18K 10K

3 8
A7 GND

13 9 10 12 11

6 B6 B7

13

4

4

7

12

5

5

LEV6

8

11

6

6

9

10

C12B 103

140 Multi type Air Conditioner

R11K,IK

3

3

Schematic Diagram

Schematic Diagram

13
C101 R101

GND
R102

IN

1

+12V
D101

IC04D
7805
9
D201 R201 R202 PC201

L1 12uH
12
OUT
D

OUT

3 NC
TNY 267
FB

NTC D05D SCK102 1N4007
(DIP)
+ C01D 4.7uF 450V

BD01D DF08M

N/F01N 11mH/1.5A

ZNR01N SVC561D-14A

FUSE_1 250V/T3.15A

C05D 220uF 10V
+ +

C04D 103 50V C08D 103 50V R01D 1/2W
BP
PC201

+
1/4W
S
C102

5 NC 6

R02D 300K C01N 104 275VAC

L

1K
7
D202

N

C07D 220uF 25V C06D 470UF 25V
GND GND

CN_PWR

u-POWER MODULE uPM1512-C2
C09D 102M

D05D 1N4007

D05D 1N4007

D05D 1N4007

5V_EXT

5V 5V
C09Y 104 U05Y MAX253 Trans01Y D01Y SS12 G C04Y 22uF/35V IC03D KID78L05BP I O 7805 C02Y 104 C03Y 22uF/35V C05Y

R13K 1K/0.62K
1 2 3 4

6N137

8

4.7K R14K

1

4 5 6
D02Y SS12

7

1 2 3 4
2 3
U02Y 6N137

8 7 6 5

6

104 C01K

5
IC02K(6N137)

TXD1

CN_OUT
5V

TXD0 SEL RXD0
R01Y 0.62K U03Y 6N137 C08Y 104 R03Y 4.7K ZNR01Y SVC220D-07B LED1 R04Y 5.1K R09Y 1K R07Y 0.33K U01Y SN65LBC176 R08Y 1K

1 2 3 4
C07Y 104 R02Y 5.1K 104

8 7 6 5

CN-COMM
1 2 3 4 4 3 2 1

TXD1

15pF C03K

1

1

RX

1 2 3 4

8 7 6 5 1 2 3 4 8 7 6 5

SEL
R12K 1K/4.7k
5

2

2

TX

R05Y 4.7K C06Y 104 U04Y 6N137

TXD0

3. Central control unit Schematic diagram

SEL SCK
5V

2012

2012

IC01K(6N137)

5V

5V_EXT
BR1
1 o o 2 3 o o 4 5 o o 6 7 o o 8

C10D 220uF 10V
RXD1 GND TXD1 VCC

+

CON5*2

RXD0
44

43 MOSI 1 MISO 2

42

41

40

39

38

37

36

35

34 33 32 SCK 3 RESET 4 31 PA4 PA5 PA6

SEL

9 o o 10

TXD0

R01G 470 R02G 470 R03G 470 R03T 1K

LED01G
5V 5V

LED02G LED03G

R02A 4.7K
5V
1

C03A 102 KIA7036P
2

3

R03A 120

R01A 1K

IC01A 3.6V
4.7uF

C01A C02A 104

ATMEGA162
RXD0 5
5V

30 29 AVCC 6 TXD0 7 28 27 PD2 PD3 8 9 26 25

PA7

R04T 10K
2012

AGND

SWITCH

V5

R02M 1K OMRON_B3WN

OUT
8 7 6 2 3 4

IN SW4 SW3 SW2 SW1
S10R S20R S30R S40R

PD5

11 12
4*K1 W8/1

23 13 14 Xtal1 15 Xtal2 16 GND 17 VCC 18 RXD2 19 TXD2 20 21 22

ON

5 1

SW DIP-4

V5

PD4

10

24

R05T 10K
R08S R07S R06S R05S

C05H

C04H

C03H

C02H

4*K01 W8/1

4*301

V5

R06T 10K
R01B

C03X 104,2012
1M

C02X 102K
12uH L01D 12uH L02D

R03X 1K
2012
OSC01B 14.7456

2012

5V

1

6N137

8

C01X 102K

R01X 1K

104 C02K

2

7

RXD0

RXD1

4

3

6

5 6 7 8

4 3 2 1

R06Y 0.62K

15pF C04K

RXD1

3

3

GND

4

4

5V_EXT

5

5

12V_EXT

R15K 1K/0.62K

5V_EXT

IC05D

7805

CN_JIG

TXD2

1

1

RX

RXD2

2

2

TX

3

3

GND

5V

C04X 104

4

4

5V

Service Manual 141

5V

Schematic Diagram

Wiring Diagram
1. Room Type Indoor Unit
AC PCB ASM
CN-MOTOR

2. Art Cool Type Indoor Unit
CN-HVB(BL) CN-LR2(WH) CN-LR1(WH) CN-UD(BL) CN-TH1CN-TH2

DC PCB ASM
CN-U/D CN-TH1 CN-TH2 THERMISTOR(OUT-PIPE) THERMISTOR(IN-PIPE) THERMISTOR(ROOM)
FAN MOTOR
WH BK YL RD

AC PWB ASM
CN-MOTOR1 CN-GND1

DC PWB ASM

THERMISTOR(OUT-PIPE) THERMISTOR(IN-PIPE) THERMISTOR(ROOM)

STEP MOTOR

CN-ACDC1

CN-ACDC2

STEP MOTOR STEP MOTOR
RD

ZNR
ZNR
Z

CN-POWER

GN/YL

BR

BL

RD

FUSE 250V 2A

FUSE 250V 3.15A

H.V. ASM BK

PLASMA AIR CLEAN

1(L) 2(N)

3

4

CN-D1(WH) CN-D2(WH)

CN-POWER

TO OUTDOOR UNIT

SAFETY S/W SAFETY S/W

CONNECT PCB ASM

DISPLAY PCB ASM

3854A20135Y
3854A20135W

STEP MOTOR

FORCE S/W

3. Art Cool Deluxe Type Indoor Unit

4. Duct Type Indoor Unit - BT chassis

CN-MOTOR

CN-L/R

MAIN PCB ASM
TRIAC

WIRING DIAGRAM
STEP MOTOR
ROOM. IN-PIPE. OUT-PIPE. CENTRAL CONTROL REMOTE TELE CONTROL THERMISTOR CONTROL THERMISTOR THERMISTOR DRY CONTACT A/CL UNIT PTC HEATER

OR

MOTOR
SH-CAPA

CN-U/D

BK

BR YL GN/YL

CN-CC ZONE CONTROL

CN-PIPE1

CN-REMO CN-PIPE2

CN-ROOM

CN-AIRC

CN-PTC

CN-OUT

STEP MOTOR

ZNR CN-HVB

VENTILATION E/HEATER

RD
H.V.B

RD
A/CL

CN-ZONE

4

BK

BK

5

CN-TH2

FLOAT S/W

THERMISTOR(OUT-PIPE)

CN-PIPE1

GN/YL BR
FUSE
CN-DISP CN-MOTOR CN-DPUMP CN-POWER

CN-TH1

THERMISTOR(IN-PIPE) THERMISTOR(ROOM)

CN-POWER

FUSE 250V 2A

BR BL GN/YL RD

CN-VFD

DISPLAY
RF-REMOTE CONTROL

OPTION

1(L) 2(N)

3 4

3854A20419A
TO OUTDOOR UNIT

FORCED OPERATION S/W

CN-MAIN CN-SW/1
CONNECTOR PCB ASM

CN-SW/2 CN-SW/3

LIMIT S/W-1 LIMIT S/W-2

CN-STEP1

CN-STEP2

INDOOR WIRING DIAGRAM
3854A20135X

SUC STEP MOTOR-1

SUC STEP MOTOR-2

142 Multi type Air Conditioner

1(L) 2(N)

BL

3

RD

TO OUTDOOR UNIT

Schematic Diagram

5. Duct Type Indoor Unit - BH/BP chassis 6. CVT Type Indoor Unit - VE chassis
WIRING DIAGRAM
ROOM. IN-PIPE. OUT-PIPE. CENTRAL CONTROL REMOTE TELE CONTROL THERMISTOR CONTROL THERMISTOR THERMISTOR DRY CONTACT

WIRING DIAGRAM
A/CL UNIT PTC HEATER
CN-DOOR

STEP MOTOR

S/W2

CN-UD1

CN-OUT

CN-CC ZONE CONTROL CN-ZONE

CN-PIPE1

CN-REMO CN-PIPE2

CN-ROOM

CN-AIRC

CN-PTC

VENTILATION E/HEATER

S/W1

DC PCB ASSY

CENTRAL CONTROL

CN-CC

AC PCB ASSY
4 RD GN/YL 1(L) 2(N) BL BR TO OUTDOOR UNIT

A/CL UNIT

5

CN-ACDC

3

RD
FLOAT S/W CN-PIPE1

TO OUTDOOR UNIT

HVB CN-HVB

GN/YL 1(L) 2(N) BL BR
FUSE
CN-DISP CN-MOTOR CN-DPUMP CN-POWER

CN-ACDC

4

GN/YL

FUSE
CN-TH1 CN-TH2 CN-FLOAT CN-DISP CNMOTOR CNDPUMP

IN-PIPE. THERMISTOR ROOM OUT-PIPE. THERMISTOR THERMISTOR FLOAT S/W

DISPLAY PCB ASSY

OPTION

OPTION
RF-REMOTE CONTROL

3854A20419D

3854A20419B

7. CVT Type Indoor Unit - VB chassis

8. CST Type Indoor Unit - TE/TF/TD chassis
WIRING DIAGRAM

CENTRAL CONTROL

CN-DOOR

OUT-PIPE. ROOM. IN-PIPE. THERMISTOR THERMISTOR THERMISTOR
CN-UD1

DOOR S/W

A/CL UNIT

WIRING DIAGRAM

HVB

STEP MOTOR

S/W2 S/W1

CN-CC

STEP STEP MOTOR MOTOR

STEP MOTOR

STEP MOTOR

CN-PIPE2 CN-ROOM CN-PIPE1
4
A/CL UNIT

CN-HVB

CN-UD1 CN-UD2 CN-LR1 CN-LR2

3

RD GN/YL BL BR

TO OUTDOOR UNIT

CN-ACDC

CN-ACDC

FUSE
CN-TH1 CN-TH2 CN-FLOAT CN-DISP CNMOTOR CNDPUMP

GN/YL BL BR FUSE CN-PTC PTC HEATER CN-FLOAT CN-DISP CN-MOTOR CN-DPUMP

CN-HVB

IN-PIPE. THERMISTOR ROOM OUT-PIPE. THERMISTOR THERMISTOR FLOAT S/W

DISPLAY PCB ASSY

OPTION

CN-REMO

3854A20419E

DISPLAY PCB ASSY FLOAT S/W

OPTION

REMOTE CONTROL

3854A20419C

9. CST Type Indoor Unit - TC chassis
INDOOR WIRING DIAGRAM
TEMP. PIPE IN THERMISTOR THERMISTOR FLOAT S/W

CAPACITOR BR YL BK GN/YL
INDOOR MOTOR CN-ROOM CN-MOTOR CN-PIPE1 CN-FLOAT PIPE OUT THERMISTOR CN-PIPE2

MAIN PCB ASSY

OR

CN-DPUMP

CN-STEP

GN/YL

DRAIN PUMP

STEP MOTOR REMOTE CONTROL

CN-POWER FUSE T3.15A

CN-REMO

CN-AIRC

BR BL
1(L) 2(N)

RD
WH RD
BK

TO OUTDOOR UNIT

H.V.B

RD BK

P/N:3854A20405A

AIR CLEANER

3

4

DOOR S/W

(OPTION)

DISPLAY PCB ASSY

CN-DISP

Service Manual 143

1(L) 2(N)

3

HVB

TO OUTDOOR UNIT

GN/YL 1(L) 2(N)

CENTRAL CONTROL TELE CONTROL

CN-CC

3

Schematic Diagram

5. Outdoor Unit 1. A2UW186FA0
INVERTER COMPRESSOR

2. A3UW246FA0
OUTDOOR WIRING DIAGRAM
INVERTER COMPRESSOR REACTOR RD BL YL
OR

OUTDOOR WIRING DIAGRAM
REACTOR

RD BL YL

RD

BL

YL

BK

BK

CN-FAN(A)

BL BK BR YL

OR

FAN

RD

BL

YL

BK

BK

CN-FAN(A)

CN-LEV2 CN-LEV1

U

V

W

CN-COIL1 CN-COIL2

BL BK BR YL

FAN

LEV

MAIN PCB
4WAY VALVE

LEV

CN-LEV2 CN-LEV1

LEV

U

V

W

CN-COIL1 CN-COIL2

LEV CN-4WAY
4WV

CN-4WAY CN-LEV3

4WV 4WAY VALVE

LEV

MAIN PCB
CN-HEATER
CN-TH2 CN-TH1 CN-TH3 CN-TH4

CN-JIG-PC CN-CENTRAL

CN-JIG-PC CN-CENTRAL

CRANKCASE HEATER OPTION

CN-WRITER

CN-TH2

CN-TH3

CN-WRITER

CN-TH1

CN-P/ICE
(H/SINK) (AIR/PIPE) (DISP-I/SUG) (DISP-C)

SV (HEATING)

DEFROST

(AIR/PIPE)

(H/SINK) (DISP-I/SUG) LOW PRESS SWITCH CN-PRESS

CN-PRESS CN-OIL/S WH RD

LOW PRESS SWITCH
SV OIL SEPERATOR
OLP COMPRESSOR
C R S

CN-COM L N CN-GND1 CN-GND2 BR BL WH BK

CN-COM L N

BK

RY-C/COMP

CONSTANT

BR BL RD

GND-1 GND-2 BR BR BL BK BK BL

BR

BL

BL BR

BL BR

1(L) 2(N) 1(L) 2(N) 3(A) 3(B) 1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) GN/YL

POWER SUPPLY

A ROOM B ROOM

TO INDOOR UNIT

POWER SUPPLY

A ROOM B ROOM C ROOM

3854A20354A

TO INDOOR UNIT

3854A20354B

3. A4UW306FA0
INVERTER COMPRESSOR

4. A6UW406FA0
INV-COMP

OUTDOOR WIRING DIAGRAM
RD BL YL REACTOR

WIRING DIAGRAM

RD BL YL

REACTOR
OR

RD
OR
CN-LEV1

BL

YL

BK

BK
CN-FAN(A)

BL BK
BR

FAN (A) FAN (B)

RD

BL

YL

BK

BK

CN-FAN(A)

CN-LEV4 CN-LEV2 CN-LEV1

FAN(B)

LEV

CN-CENTRAL

CN-FAN(B)

CN-WRITER

U

V

W

CN-COIL1 CN-COIL2

BL BK BR YL OR BL BK BR YL

FAN(A)

LEV

U

V

W

CN-COIL1 CN-COIL2

YL OR BL BK
BR

MAIN PCB
TH2 TH1 TH3 TH4

CN-FAN(B)

YL

CN-4WAY
YL

4WV

4WAY VALVE OPTION CRANKCASE HEATER

LEV LEV LEV

CN-4WAY
CN-LEV3

4WV 4WAY VALVE

CN-JIG-PC

MAIN PCB
CN-COM

CN-HEATER
(H/SINK) (AIR/PIPE) (I/SUC-DISP) (DISP-C)

CN-HEATER
CN-TH2 CN-WRITER CN-TH1 CN-TH3 CN-TH4

CN-CENTRAL

CRANKCASE HEATER OPTION

CN-OIL/S
WH BK NOISE FILTER RELAY WH

SV OIL SEPERATOR(INV)
LOW PRESSURE SWITCH CONS-COMP
BL RD BR R S C

CN-PRESS

CN-P/ICE
(H/SINK) (AIR/PIPE) (DISP-I/SUG) (DISP-C)

SV

DEFROST (HEATING) LOW PRESS SWITCH

FUSE 250V,20A

CN-JIG-PC

L

N

CN-PRESS CN-OIL/S RY-C/COMP BR

GND-2

GND-1
BR

BR

BL

SV OIL SEPERATOR

BL BR BR

BL

GN/YL BL BR

CONSTANT COMPRESSOR
BR BL RD C R S

GN/YL BR

T/B

CN-COM L N WH RD BK BR BL BL

1(L) 2(N)

1(L) 2(N)

3(A) 3(B)

GND-1 GND-2

Power Supply
LEV A LEV B LEV C LEV D LEV E LEV F

BR

BL

BR

BL

BL BR

CN-LEV-A
LED1

CN-LEV-B
LED2

CN-LEV-C
LED3

CN-LEV-A
LED1

CN-LEV-B
LED2

CN-LEV-C
LED3

1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) 5(D)

BRANCH DISTRIBUTOR-(A)
CN-ROOM-A CN-ROOM-B CN-ROOM-C L N S L N S L N S L N S CN-PWR

BRANCH DISTRIBUTOR-(B)
CN-ROOM-A CN-ROOM-B CN-ROOM-C L N S L N S L N S L N S CN-PWR

POWER SUPPLY

A ROOM B ROOM C ROOM D ROOM

TO INDOOR UNIT

3854A20354C

A

B

C

D

E

F

TO INDOOR UNIT

TO INDOOR UNIT

3854A20354G

144 Multi type Air Conditioner

Schematic Diagram

5. A2UW146FA0
INVERTER COMPRESSOR

6. A3UW186FA0
OUTDOOR WIRING DIAGRAM
INVERTER COMPRESSOR

OUTDOOR WIRING DIAGRAM
REACTOR

RD BL YL

REACTOR
RD BL YL
OR

RD

BL

YL

BK

BK

CN-FAN(A)

BL BK BR YL

OR

FAN

RD

BL

YL

BK

BK

CN_FAN(A)

CN-LEV2 CN-LEV1

U

V

W

CN-COIL1 CN-COIL2

BL BK BR YL

FAN

LEV

MAIN PCB

LEV

CN-4WAY

4WV

4WAY VALVE

CN_LEV2 CN_LEV1

LEV

U

V

W

CN_COIL1 CN_COIL2

LEV LEV

CN_4WAY CN_LEV3

4WV 4WAY VALVE

MAIN PCB
CN_TH2 CN_TH1 CN_TH3

CN-JIG-PC CN-CENTRAL

CN-PRESS
CN_JIG_PC CN_CENTRAL

CN-WRITER

CN-TH2

CN-TH3

CN_WRITER

CN-TH1

(H/SINK) (AIR/PIPE) (DISP_I/SUG)

CN_PRESS

LOW PRESSURE SWITCH

(H/SINK) (DISP-I/SUG) (AIR/PIPE)

CN_COM

L

N CN-GND1 CN-GND2
L N GND_1 GND_2

BR

BL

WH

BK

BK
BR BL

BR

BL

BK

BL BR

WH

BK

BL BR

1(L) 2(N) 1(L) 2(N) 3(A) 3(B)
1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C)

GN/YL

POWER SUPPLY

A ROOM B ROOM

TO INDOOR UNIT

POWER SUPPLY

A ROOM B ROOM C ROOM

RD

CN-COM

3854A20354L

TO INDOOR UNIT

3854A20354J

7. A4UW246FA0
INVERTER COMPRESSOR

8. A7UW486FA0, A8UW586FA0
INV-COMP(A)

OUTDOOR WIRING DIAGRAM
RD BL YL REACTOR

WIRING DIAGRAM

RD BL YL

REACTOR
RD
OR
CN-LEV1

OR

BL

YL

BK

BK

CN-FAN(A)

BL BK
BR

YL

FAN (A)
4WAY 4WV VALVE CONS-COMP(C)
BR C BL R S
RD

RD

BL

YL

BK

BK

CN-FAN(A)

BL BK BR YL

FAN

LEV

U

V

W

CN-COIL1 CN-COIL2

CN-4WAY

CN-WRITER

CN-LEV2 CN-LEV1

U

V

W

CN-COIL1 CN-COIL2

CN-CENTRAL

MAIN PCB
TH2 TH1 TH3 TH4

CN-C/COMP2

PTCR OPTION CRANKCASE HEATER OPTION CRANKCASE HEATER_2

LEV

CN-HEATER

BR

BL

LEV LEV

CN-LEV3

MAIN PCB
CN-HEATER
CN-TH2 CN-TH1 CN-TH3 CN-TH4
CN-COM

CN-JIG-PC

CN-4WAY

4WV 4WAY VALVE

(H/SINK) (AIR/PIPE) (SUC/DISP_I) (DISP-C)

CN-HEATER2 CN-C/FAN

CN-JIG-PC CN-CENTRAL

CRANKCASE HEATER OPTION

FM COOLING FAN
OIL

NOISE FILTER

CN-OIL/S

SV SEPERATOR
LOW PRESSURE SWITCH CONS-COMP(B)
WH BL BL BL C R S
RD

CN-WRITER

CN-P/ICE
(AIR/PIPE) (H/SINK) (DISP-I/SUG) (DISP-C)

DEFROST SV (HEATING) LOW PRESS SWITCH

FUSE 250V,20A

CN-PRESS

L

N

GND-2
BK

GND-1
BK

RY-C/COMP BR

CN-PRESS CN-OIL/S RD WH

BR

SV OIL SEPERATOR
OLP COMPRESSOR
C R S

GN/YL BL BR GN/YL

BL

T/B
BR

CN-COM L N

BK

RY-C/COMP

CONSTANT

T/B

BR BL RD

1(L) 2(N)

1(L) 2(N)

3(A) 3(B)

GND-1 GND-2 BR BR BL BL
LEV A

Power Supply
LEV B LEV C LEV D LEV E LEV F LEV G LEV H

BL BR

BL BR

CN-LEV-A
LED-1

CN-LEV-B
LED-2

CN-LEV-C
LED-3

CN-LEV-D
LED-4

CN-LEV-A
LED-1

CN-LEV-B
LED-2

CN-LEV-C
LED-3

CN-LEV-C
LED-4

1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) 5(D)

BRANCH DISTRIBUTOR-(A)
CN-ROOM-A CN-ROOM-B CN-ROOM-C CN-ROOM-D L N S L N S L N S L N S L N S CN-PWR

BRANCH DISTRIBUTOR-(B)
CN-ROOM-A CN-ROOM-B CN-ROOM-C CN-ROOM-D L N S L N S L N S L N S L N S CN-PWR

Only 8Rooms Model

A

B

C

D

E

F

G

H

POWER SUPPLY

A ROOM B ROOM C ROOM D ROOM

TO INDOOR UNIT

TO INDOOR UNIT

TO INDOOR UNIT

3854A20354M

3854A20354K

Service Manual 145

Schematic Diagram

Components Locations
1. Indoor Unit
MAIN P.C.B ASM 1) Split Type • DC part

• AC part

146 Multi type Air Conditioner

Schematic Diagram 2) Art Cool Type
TOP VIEW BOTTOM VIEW

Service Manual 147

Schematic Diagram 3) Art Cool Deluxe Type
TOP VIEW

C03J C04J CN_MOTOR CN_TH2 JP33

JP32

CN_L/R(BL) JP1 JP34
4

CN

_U

R01J CN_CC FUSE
250V/T2A

/D

(W

CN_POWER

JP28

D07D

EARTH C05J JP29 C06J

JP40

JP39

JP45

NF02J R05K

C01J JP35

JP44

JP58

ZNR01J C04D

D02K

SD01D JP30 C01E NTC C01D C09D IC04D

D01K

NF01J ZNR02J

PCB : 6870A90120C

ASM : 6871A10111

JP47 CN_CON(BL)

BZ01E JP42 JP41

R03J

R02J

D05D

JP31

IC01D Q01V

~
D02D

OSC01B IC01A

~
C05D ZD02D

C02A IC1

JP49

TR01J

JP56

JP38

JP51

JP52

IC01K

IC02K BD01D IC02D IC01J

JP19

+

-

JP50 Q01C

IC03D

BOTTOM VIEW

JP32 CN-L/R(BL)

R04H C03H R03H

JP20

CN-MOTOR

CN-CH2

JP1 JP5 JP34 IC01M IC04M

JP27

CN

-U

/D

(W

H)

JP33

C03J

JP53

JP54

CN-CC R24G R23G R22G R21G

R01J

JP57

CN
C01F

JP43 D07D SMPS C05J

EARTH C06J

JP4

C

N-T

H1
L1 R02F R01F C06D

JP29 C10D ZNR01J

JP40

JP45

C07D

CN
JP3

JP39

-V

F

JP44

D(W

JP58

H)

JP35

C01J

C04V

R04V

C04D

NF02J D02K

MICOM
50

SD01D C01E JP30

C03V R03V

R02H R01H R05H

JP16

C08D IC04D C01D C09D R03E Q02E NTC
40

ZNR02J

JP48

JP46 JP47

JP25 JP9 R02L JP2 Q03E C01L R01E R02E Q01E

C02H R06H C01H CN-CON(BL) R21H R23H R22H

55

TR01J R03J

JP49

30

JP24 R04E JP26

R01B

C02D

D05D

R02J

R02G OR1H OR3H

JP8 R01L

IC01D

JP18 R05V R06V JP15

20

JP31

25

JP41

R05D

JP42

OR2H

JP10

R01A C01A

R05K

Q01V

JP17

BC01D C05D

IC02K

D01K

R04J

C01G R01G

C01X

JP19

Q02V

R08D

JP37

L01X

L02X

JP12

JP56

JP55

R03D R02D

JP38

JP21

JP36

JP54

JP53

JP52

JP51

JP23

JP22

IC1

ZD02D

Q01C

R07D

R04D

JP13

JP7 JP6

C01K

R01K

148 Multi type Air Conditioner

R04K R02K

R02A JP50

R06D

IC01A JP14

IC02D

R01P

D02D

IC01J

IC03D

Q01K

R03K

NF01J

CN-POWER

IC02M

JP28

-H

VB

(B

L)

CN

-S

UC

(W

H)

FUSE 250V/T2A

JP55

C04J

IC01K

JP12

JP48

3

1

7

H) CN

SMPS

_S

UC

(W

H) CN _H

JP43 L1 C06D

VB

(B

L) CN _T H1

CN

_V

FD

(W

H)

JP11 JP46

45

1 10 15

Schematic Diagram 4) Duct Type • High static (BH/BG chassis) • Built in type (BP chassis)

Service Manual 149

Schematic Diagram • Low static (BT, BT1 chassis)

150 Multi type Air Conditioner

Schematic Diagram 5) Casset Type • 1 way(TC chasis)

Service Manual 151

Schematic Diagram • 4 way(TE, TF, TD chasis)

58 B

152 Multi type Air Conditioner

Schematic Diagram 6) Convertible type • VE chassis AC part

TOP VIEW

BOTTOM VIEW

DC part

TOP VIEW

BOTTOM VIEW

Service Manual 153

Schematic Diagram • VB chassis

154 Multi type Air Conditioner

Schematic Diagram 2. Display ASSEMBLY 1) Split Type

2) Convertible Type VE chassis TOP VIEW

PWB ASM:6871A20390

PCB:6870A90065K

BOTTOM VIEW

VB chassis

3) Art Cool Type

TOP VIEW

BOTTOM VIEW

Service Manual 155

Schematic Diagram 4) Art Cool Deluxe Type
TOP VIEW
SEJIN ELECTRON INC. SVM-GP1119AI P/N 3210018043 REV1
Q2 R9 R18 C19 Q1 R19 C7 R10 C9 R13 R3 R4 R6 R2 R17 D1 C21 R5
M43

BOTTOM VIEW

156 Multi type Air Conditioner

TP4 TP3

TP2

TP2

TP7

TP8

TP4

TP6

TP5

TP3

TP1

TP1

C18

C8

C14

C15

C13

M42

R8 R7
M45 M44

1
C20

Schematic Diagram

3. Outdoor Unit
1) Component side

Service Manual 157

Schematic Diagram 2) Solder side

158 Multi type Air Conditioner

Schematic Diagram 3) Central control PCB 1) Top View

2) Bottom View

Service Manual 159

Schematic Diagram

4. SUB P.W.B ASSEMBLY
1) Art Cool Type
TOP VIEW

BOTTOM VIEW

160 Multi type Air Conditioner

OUTDOOR UNIT

3 rooms model Reversing Valve

Room C

Field Piping Gas

Room B

Room A Header Th2 Th3 Th1

Refrigeration Cycle Diagram

Low Pressure S/W

Troubleshooting Guide

Accumulator

1. A2UW186FA0, A2UW146FA0, A3UW186FA0
Exchanger Heat

3 rooms model LEV-C Compressor

Room C LEV-B

Field Piping Liquid LEV-A

Room B

Room A

Service Manual 161

Troubleshooting Guide

Refrigerant Flow Cooling Heating

Drier

4 room model Room D Room C Room B Room A Header Reversing Valve

OUTDOOR UNIT

Troubleshooting Guide

Room D Room C Room B Room A LEV-A LEV-B LEV-C

Th3 Low Pressure S/W

Field Piping Liquid

Cooling
Drier

Heating

Valve(2) Solenoid

Refrigerant Flow

Valve(1) Solenoid

162 Multi type Air Conditioner
Check Valve(1) Oil Seperator Th2 Th1 Check Valve(2) Accumulator Heat Exchanger Constant Compressor 4 room model LEV-D Inverter Compressor

2. A3UW246FA0, A4UW246FA0

Field Piping Gas

OUTDOOR UNIT
Reversing Valve

Room D

3. A4UW306FA0

Room C

Field Piping Gas

Room B

Room A Header Check Valve(2) Oil Seperator Th2 Accumulator Th1 Heat Exchanger Check Valve(1)

Constant Compressor LEV-D LEV-C LEV-B LEV-A Low Pressure S/W

Inverter Compressor Th3

Field Piping

Room C

Liquid

Room B

Room A

Cooling
Drier

Service Manual 163

Troubleshooting Guide

Heating

Valve(2) Solenoid

Refrigerant Flow

Valve(1) Solenoid

Room D

Troubleshooting Guide

4. A6UW406FA0
OUTDOOR UNIT
Refrigerant Flow Cooling Heating
Reversing Valve

Check Valve(2 ) Accumulator Th2

Check Valve(1 ) Oil Seperator Th1

Solenoid Valve(1)

Heat Exchanger

Constant Compressor

Inverter Compressor Th3

Field Piping Gas(Ø 19.05) Drier Field Piping Liquid (Ø 9.52)

Low Pressure S/W

L.E.V.

Receiver

Notes: • Th: Thermistor • L.E.V: Linear Expansion Valve

164 Multi type Air Conditioner

Troubleshooting Guide

5. BD Unit
Refrigerant Flow Cooling Heating Main Liquid Main Gas Piping ( Ø 9.52) Piping ( Ø 19.05)

D Liquid(Ø9.52) C Liquid(Ø9.52 or Ø12.7) B Liquid(Ø9.52 or Ø12.7) A Liquid(Ø9.52 or Ø12.7) LEV-B LEV-A

D Liquid(Ø6.35) C Liquid(Ø6.35) B Liquid(Ø6.35) A Liquid(Ø6.35)

[Indoor Unit]

LEV-D

LEV-C

Service Manual 165

Outdoor Unit

Troubleshooting Guide

Self-diagnosis Function
s Error Indicator • The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. • Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table. • If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed. • After error occurrence, if error is released, error LED is also released simultaneously. • To operate again on the occurrence of error code, be sure to turn off the power and then turn on. • Having or not of error code is different from Model.

Indoor Error
Error code 00 01 02 03 04 05 06 07 No Error Indoor Room themistor error Indoor in-piping sensor error Remote controller error Drain Pump error Communcation error between in and out Indoor Out-Piping sensor error Differnt mode operation 1time 2times 3times 4times 5times 6times 7times Description INV TPS LED 1 (Red) LED 2 (Green) Indoor Status ON OFF OFF OFF OFF OFF OFF OFF

Outdoor Error
Error Code
21 22 23 24 25 26 27 28 32 33 40 41 44 45 46 47 51 53 60 61 62 63 65 CT 2(Max CT) DC Link Low Volt. L_P/Heater Sink Low voltage / Over voltage DC Comp Position Error PSC Fault Error DC Link High Volt D-Pipe High (INV) D-Pipe High (Normal) CT Sensor (Open/Short) INV. D-PipeTh Error(Open/Short) Outdoor air Th Error(Open/Short) Cond. Pipe Th Error(Open/Short) Suction Pipe Error(Open/Short) Const D-pipe Th Error(Open/Short) Capacity over Signal error (Indoor ↔ Outdoor) EEPROM Check Sum Error Cond. Pipe High Heatsink High Cond. Pipe Low Heatsoml Th error (Open/Short)

Description
DC Peak (IPM Fault)

INV TPS

LED 1 (Red)
2times 2times 2times 2times 2times 2times 2times 2times 3times 3times 4times 4times 4times 4times 4times 4times 5times 5times 6times 6times 6times 6times 6times

LED 2 (Green)
1time 2times 3times 4times 5times 6times 7times 8times 2times 3times O 1time 4times 5times 6times 7times 1time 3times O 1time 2times 3times 5times

Indoor Status
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

166 Multi type Air Conditioner

Troubleshooting Guide

Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current. Temp. difference Current : approx. 0°C : less than 80% of rated current All amount of refrigerant leaked out. Check refrigeration cycle.

Temp. Difference Temp. difference Current Operating Current Temp. difference Current : less than 8°C : near the rated current Excessive amount of refrigerant : approx. 8°C : less than 80% of rated current Refrigerant leakage Clog of refrigeration cycle Defective compressor

Temp. difference

: over 8°C

Normal

Notice: Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Temperature (Compared with the normal value) High Higher Normal Excessive amount of refrigerant Insufficient amount of refrigerant(Leakage) Clogging High pressure does not quickly rise at the beginning of operation. Current is low.

Cause of Trouble Defective compressor

Description Current is low.

Lower

Higher

Notice: 1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
2

Service Manual 167

Troubleshooting Guide

Electronic Parts Troubleshooting Guide
1. A2UW186FA0, A2UW146FA0, A3UW186FA0
❇ Refer to electronic contorol device drawing & schematic diagram.

Trouble 1

The Product doesn’t operate at all.

Turn off the main power and wait until LED on outdoor PCB is off.

Turn on the main power again.

Does "Beeping" sound is made from the indoor unit? NO Check the voltage of power(AC220V/AC240V, 50Hz). • The voltage of main power. • The voltage applied to the unit. • The connecting method of Indoor/Outdoor connecting cable (each color) • The P.W.B. Ass'y (Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.) YES • Primarily, the operating condition of Micom is O.K.

• Check CN-DISP1

The operation check of the P.C.B. Ass'y Procedure 1) The input voltage of power transformer. 2) The output voltage of power transformer. 3) IC01D(7812) 4) IC02D(7805) 5) IC01A(KIA7036) Specification 1) AC230V ± 30V : Check the rated voltage 2) 14V ± 3V 3) DC12V 4) DC5V 5) The voltage of micom pin 29 : DC4.5V↑ Remedy 1) Replace power transfomer. 2) Replace power transfomer. 3) Replace IC01D. 4) Replace IC02D. 5) Replace IC01A.

168 Multi type Air Conditioner

Troubleshooting Guide

Trouble 2

Product doesn't operate with the remote controller.
Turn on main power.

While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)

Caused by the remote controller.

Caused by other parts except the remote controller

When the mark ( ) is displayed in LCD screen, replace battery.

Check the contact of CN-DISP 1 connector

When the detect switch (double key) inside the remote controller door is fault, it is impossible to operate temperature regulating(v / w) and wind speed selecting.

Check DISP PWB Ass'y -Voltage between CN1 ➀ - ➆ : DC +5V

Check the Display PWB Ass'y

• Check receiver ass'y

Service Manual 169

Troubleshooting Guide

Trouble 3

The Compressor/Outdoor Fan don't operate

Turn on the main power.

Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1°C at least.

When in air circulation mode, compressor/outdoor fan is stopped.

Check the sensor for Indoor temperature is attatched as close as to be effected by the themperature of Heat Exchange (EVA.)

When the sensor circuit for Indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor fan is stopped. • Check the related circuit of R02H(12.1K), R01H(1K), R04H(6.2K), R03H(1K), C01H(102), C02H(102), Micom(pin No. , ). • Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).

Check the Relay(RY-PWR, RY-START) for driving Compressor. • Check the voltage between brown and blue cable of terminal to connect the Outdoor (About AC220V / 240V). • Check the related circuit of relay in Outdoor PCB Ass'y. Check Point Between Micom(No. 19) and GND Between IC01M(No. 10) and GND Comp. ON DC 5V DC 1V↓ Comp. OFF DC 0V DC 12V

Turn off main power.

Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor.

170 Multi type Air Conditioner

Troubleshooting Guide

Trouble 4

When indoor Fan does not operate.
Turn off main power.

Check the connection of CN-FAN.

Check the Fan Motor.

Check the Fuse(AC250V, T2A).

Check the related circuit of indoor Fan Motor. • The pin No. 38 of micom and the part for driving SSR.(Q01M) • Check the related pattern. • Check the SSR. - SSR Open: Indoor Fan Motor never operate. - SSR short: Indoor Fan Motor always operates in case of ON or OFF.

Turn on the main power

Check the SSR high speed operation by remote control. (the Indoor Fan Motor is connected) The voltage of Pin No 1(orange) and 3(black) of CN-FAN.

About AC 160V over

About AC 50V over

SSR is not damaged

Check SSR

Service Manual 171

Troubleshooting Guide

Trouble 5

When the louver does not operate.

• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the vertical louver with hands ⇒ Normal

• Check the connecting condition of CN-U/D or CN0L/R Connector • Check the soldering condition(on PCB) of CN-U/D or CN0L/R Connector

Check the operating circuit of the vertical louver • Confirm that there is DC +12V between pin ➀ of CN-U/D, CN0L/R and GND. • Confirm that there is a soldering short at following terminals. - Between 17 , 18 , 19 and 20 of MICOM - Between 1 , 2 , 3 and 4 of MICOM - Between 4 , 5 , 6 and 7 of IC01M - Between 5 , 6 , 7 and 8 of IC01M

If there are no problems after above checks. • Confirm the assembly condition that are catching and interfering parts in the link of the vertical louver

172 Multi type Air Conditioner

Troubleshooting Guide

General Information
s Error Indicator (Indoor) • The function is to self-diagnosis air conditioner and express the troubles if there is any trouble. • Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit control board. • If more than two troubles occur simultaneously, lower number of error code is first displayed. • After error occurs, if error is released, error LED is also released simultaneously.

1 digit
s Indoor Error Error code 01 02 03 04 05 06 07 Contents Air sensor (open/short) Inlet pipe sensor

10 digit

Case of error Open / Short Open / Short Communication Poorly Float switch Open Communication Poorly Open / Short Different operation mode

Indoor Status Off Off Off Off Off Off Off

Communication(Indoor ↔ Wired R/Control) Drain pump/ Float switch Communication(Indoor ↔ Outdoor) Outlet pipe sensor Different operation mode

Service Manual 173

Troubleshooting Guide
s Error Indicator (Outdoor) Outdoor Error Ex) Error 21 (DC Peack)
2 Times 2 Times 2 Times

LED01G (RED)
1 Sec. 1 Time 1 Sec. 1 Time 1 Sec. 1 Time

LED02G (GREEN)
2 Sec. 2 Sec.

Error code
21 22 23 24 25 26 27 28 32 33

Contents
IPM Fault (Compressor Over current) CT 2(Max. Current) DC Link Low Volt. Low / High press AC Low / AC High Volt. DC Compressor Position PSC Fault DC Link High Volt Discharge Pipe Temp. High (INV) Discharge Pipe Temp. High (Cons.)

LED01G LED02G (Green) (Red)
2 times 2 times 2 times 2 times 2 times 2 times 2 times 2 times 3 times 3 times 1 time 2 times 3 times 4 times 5 times 6 times 7 times 8 times 2 times 3 times Off Off Off

Case of error
Compressor malfunction,IPM Fault Current is 14A DC Link volt. Is 140V Low / High press switch OPEN Abnormal AC volt. Input.

Outdoor Status
Off Off Off Off Off Off Off Off Off Off

174 Multi type Air Conditioner

Troubleshooting Guide
s Error Indicator (Outdoor) Outdoor Error

Error code
40 41 44 45 46 47 51 53 60 61 62 65 CT Circuit

Contents

LED01G LED02G (Green) (Red)
4 times 4 times 4 times 4 times 4 times 4 times 5 times 1 time 4 times 5 times 6 times 7 times 1 time 3 times

Case of error
CT Circuit malfunction Open / Short Open / Short Open / Short Open / Short Open / Short Over load combination Communication Poorly Check sum mismatching

Outdoor Status
Off Off Off Off Off Off Off Off Off Off Off Off

D-pipe sensor INV. (open/ short) Air sensor (open/ short) Cond. Pipe sensor (open/ short) Suction pipe sensor (open/ short) D-pipe sensor Cons. (open/ short) Over capacity Communication (Indoor EEPROM check sum Cond. Pipe sensor temp. high Heat sink sensor temp. high Heat sink sensor (open/ short) Outdoor)

5 times 6 times 6 times 6 times 6 times

1 time 2 times 5 times

Cond. Temp. high Heat sink temp. high Open / Short

Service Manual 175

Troubleshooting Guide 1) Troubleshooting CH01, CH02, CH06
Display code 01 Title Cause of error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error Check point & Normal condition Normal resistor : 10KΩ/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged) Normal resistor : 5KΩ/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged) Normal resistor : 5KΩ/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged)

Indoor air sensor

02

Indoor inlet pipe sensor

06

Indoor outlet pipe sensor

10kΩ


2.5Vdc
V

Check the resistance

Check the voltage

Check Point
1. Unplug the sensor on Indoor unit PCB. 2. Estimate the resistance of each sensor. 3. If the resistance of the sensor is 10KΩ/ 5KΩ at 25°C, then sensor is normal. 4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. ¡ Change the sensor. 5. Plug the sensor on Indoor unit PCB and Power ON. 6. Estimate the voltage of each sensor. 7. If the voltage of the sensor is 2.5Vdc at 25°C, then sensor is normal. 8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ¡ Repair or Change the PCB.

176 Multi type Air Conditioner

Troubleshooting Guide 2) Troubleshooting CH03
Display code 03 Title Communication Wired R/C Cause of error • Open / Short • Wrong connection Check point & Normal condition • Connection of wire • Main PCB Volt. DC12V • Noise interference

Wired R/C 12V S GND 12V

Indoor Unit S GND

CN-REMO

12Vdc
V

12Vdc
V

Check the Volt.

Check the Volt.

Check Point
1. Check the wire connection. (Open / Short) ¡ Repair the connection 2. Check the soldering state of connector. (Soldered poorly) ¡ Repair or Change the PCB. 3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) ¡ Repair or Change the main PCB. 4. Check the installation of wired remote controller. (Noise interference) ¡ Adjust the state of installation

Service Manual 177

Troubleshooting Guide 3) Troubleshooting CH04
Display code Title Cause of error Check point & Normal condition • The connection of wire(Drain pump/ Float switch) • Drain pump power input. (220V) • Drain tube installation. • Indoor unit installation. (Inclination)

04

Drain pump / Float switch

• Float switch Open. (Normal : short)

CN Float

CN-D/PUMP CN-Float

0Ω


Check the resistance

Check Point
1. Check the wire connection. (Open, Soldered poorly) ¡ Repair the connection or change the PCB. 2. Check the resistance of float switch (Abnormal : Open, Normal : short) ¡ Check the float switch. 3. Check the level of water 4. Check the volt. Of Drain pump power supply. (AC 230V) ¡ Repair or Change the main PCB.

178 Multi type Air Conditioner

Troubleshooting Guide 4) Troubleshooting CH05, CH53
Display code Title Cause of error Check point & Normal condition • Power input AC 220V. (Outdoor, Indoor) • The connector for transmission is disconnected. • The connecting wires are misconnected. • The GND1,2 is not connected at main GND. • The communication line is shorted at GND. • Transmission circuit of outdoor PCB is abnormal. • Transmission circuit of indoor PCB is abnormal.

04 / 53

Communication (Indoor ¡ Outdoor)

• Communication poorly

Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit) 2. Check the communication wires are correctly connected. ¡ Adjust the connection of wire ¡ Confirm the wire of “Live”, “Neutral” 3. Check the resistance between communication line and GND. (Normal : Over 2MΩ) 4. Check the connector for communication is correctly connected. 5. Check the connection of GND1, GND2, and main GND. 6. If one indoor unit is operated normally, outdoor PCB is no problem. ¡ Check the another indoor unit. * CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

Service Manual 179

Troubleshooting Guide 5) Troubleshooting CH21
Display code Title Cause of error Check point & Normal condition • An instant over current in the U,V,W phase - Comp lock - The abnormal connection of U,V,W • Over load condition - Overcharging of refrigerant - Pipe length. • Poor insulation of compressor

21

DC Peak

• Instant over current • Over Rated current • Poor insulation of IPM

Comp U Ω V W

Resistance(Ω) at 20°C Terminal U-V V-W W-U Copper pipe Inverter Constant comp. comp. 0.64 0.64 0.64 0.8 0.8 0.8

Comp

Resistance(Ω) at 20°C Ω Terminal U-GND V-GND W-GND Inverter Constant comp. comp. 2MΩ 2MΩ 2MΩ 2MΩ 2MΩ 2MΩ

Check Point
1. Check the wire connection. (U,V,W) 2. Check the load condition. (Refrigerant, Pipe length, …) ¡ Adjust the load condition 3. Check the electricity leakage of the compressor. ¡ Normal : Over 2MΩ. 4. Check the resistance of compressor. ¡ Normal : 0.65Ω(INV), 0.8Ω(Cons.) ¡ No difference at each terminal. 5. Check the insulation from water at IPM part. ¡ Check the trace of water. 6. Check the IPM circuit.

180 Multi type Air Conditioner

Troubleshooting Guide 6) Troubleshooting CH22
Display code 21 Title Cause of error Check point & Normal condition Malfunction of compressor Blocking of pipe Low voltage input Refrigerant, pipe length, blocked, … Malfunction of current detection circuit. (Open / Short) The voltage of “C01N” Is 4.0Vdc(25A) .

Max. C/T

Over current (14A )

22

C/T Internal circuit

Initial current error

V

Check Point
1. Check the power source. 2. Check the fan operation is right. 3. Check the current. 4. Check the install condition. 5. Check the internal circuit. (C/T, Diode, Resistor)

+ + -

+

Service Manual 181

Troubleshooting Guide 7) Troubleshooting CH23, CH28
Display code 23 Title DC Link Low voltage. Cause of error Check point & Normal condition

• DC link volt. is 140Vdc .

• Check the power source. • Check the components.

28

DC Link High voltage

• DC link volt. is 420Vdc .

• Check the power source. • Check the components.

Check Point
1. Check the power source. 2. Check the components (B/Diode, Reactor, PSC Parts )

V

182 Multi type Air Conditioner

Troubleshooting Guide 8) Troubleshooting CH24, CH25
Display code 24 Title Cause of error Check point & Normal condition

Press S/W Open

• Low / High press S/W open.

• Check the connection of “CN_Press”. • Check the components.

25

Input voltage

• Abnormal Input voltage (140Vac , 300Vac .

• Check the power source. • Check the components.

TRANS1 50Hz, DC12V

CN PRESS

CN TRNAS1

Check Point
• CH 24 1. Check the connection of “CN_PRESS” 2. Check the install condition for over load. 3. Check the SVC V/V open. 4. Check the leakage of refrigerant. • CH 25 1. Check the power source. 2. Check the components (Trans1, B/Diode, Diode, Resistance)

Service Manual 183

Troubleshooting Guide 9) Troubleshooting CH26, CH27
Display code 26 Title DC Compressor Position Cause of error Check point & Normal condition • Check the connection of comp wire “U,V,W” • Malfunction of compressor • Check the component of “IPM”, detection parts.

• Compressor position detect error

27

PSC Fault

• Over current at “IGBT”

• Check the component of “IGBT” . • Check the components.

E C B

C

B E

Check Point
• CH 26 1. Check the connection of “U,V,W” 2. Check the insulation of IPM part. 3. Check the compressor. (same with CH21) • CH 27 1. Check the component of “IGBT” 2. Check the components (IGBT, R04S, NF1, BD02S)

184 Multi type Air Conditioner

Troubleshooting Guide 10) Troubleshooting CH32, CH33
Display code 32 Title D-pipe (Inverter) temp. high (105°C ) D-pipe (Constant) temp. high (105°C ) Cause of error Check point & Normal condition • Check the discharge pipe sensor for INV. • Check the install condition for over load. • Check the leakage of refrigerant. • Check the SVC V/V open. • Check the discharge pipe sensor for Cons. • Check the install condition for over load. • Check the leakage of refrigerant. • Check the SVC V/V open.

• Discharge sensor (Inverter) temp. high

33

• Discharge sensor (Cons.) temp. high

D-Pipe temp. Toff(105) °C T2(95) °C T1(90) °C

COMP Frequency Normal (Hz) LEV Openness (Pulse) Normal

Normal Normal

OFF OFF Control

Check Point
• CH 32 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. • CH 33 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. 4. Check the constant compressor. (same with CH21)

Service Manual 185

Troubleshooting Guide 11) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65
Display code 41 Title Cause of error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error • Open / Short • Soldered poorly • Internal circuit error Check point & Normal condition • Normal resistor : 200KΩ / at 25°C (Unplugged) • Normal voltage : 4.5Vdc / at 25°C (plugged) • Normal resistor : 10KΩ / at 25°C (Unplugged) • Normal voltage : 2.5Vdc / at 25°C (plugged) • Normal resistor : 5KΩ / at 25°C (Unplugged) • Normal voltage : 2.5Vdc / at 25°C (plugged) • Normal resistor : 5KΩ / at 25°C (Unplugged) • Normal voltage : 2.5Vdc / at 25°C (plugged) • Normal resistor : 200KΩ / at 25°C (Unplugged) • Normal voltage : 4.5Vdc / at 25°C (plugged) • Normal resistor : 10KΩ / at 25°C (Unplugged) • Normal voltage : 2.5Vdc / at 25°C (plugged)

D-pipe sensor (Inverter)

44

Air sensor

45

Condenser Pipe sensor

46

Suction Pipe sensor

47

D-pipe sensor (Constant)

65

Heat sink sensor

Check Point
1. Estimate the resistance of each sensor.(Unplugged) 2. Estimate the voltage of each sensor.(Plugged) 3. If the resistance of the sensor is 0 kΩ or ∞, then sensor is abnormal.



If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.

186 Multi type Air Conditioner

Troubleshooting Guide 12) Troubleshooting CH51, CH60
Display code 51 Title Cause of error Check point & Normal condition

Over capacity

• Over capacity Combination

• Check the indoor unit capacity. • Check the combination table.

60

EEPROM Check sum

• Check sum error

• Check the PCB ASM P/No. • Check the poor soldering.

Model A2UW146FA0 A2UW186FA0 A3UW186FA0 A3UW246FA0 A4UW246FA0 A4UW306FA0 A6UW406FA0

Gross max. capacity 21k 24k 33k 39k 52k

Max. single indoor unit capacity 12k 12K 18K 18K 24K

Check Point
• CH 51 1. Check the indoor unit capacity. • CH 60 1. Check the insertion condition of EEPROM. 2. Check the poor soldering

Service Manual 187

Troubleshooting Guide 13) Troubleshooting CH61, CH62
Display code 61 Title Condenser pipe sensor temp. high Cause of error • Condenser pipe sensor detected high temp.(65°C) • Heat sink sensor detected high temp.(85°C) Check point & Normal condition

• Check the load condition. • Check the sensor of Condenser pipe sensor.

62

Heat sink sensor temp. high

• Check the fan is locked. • Check the sensor of heat sink.

Heat Sink temp. Toff °C T2 °C T1 °C

COMP Frequency Normal (Hz)

Normal

OFF

Normal

Check Point
• CH 61 1. Check the install condition for over load. (Refrigerant, Pipe length, Blocked, …) • CH 62 1. Check the fan is locked. 2. Check the Outdoor temp. is very high.

188 Multi type Air Conditioner

(3-way) Valve

(3-way) Valve
3-way Valve (Liguid Side) 3-way Valve (Gas Side) Valve cap Open position Closed position Pin To piping connection

Valve cap Open position Closed position Pin To piping connection

Service Service port cap port

Service Service port cap port

To outdoor unit

To outdoor unit

Works Shipping

Shaft position Closed (with valve cap)

Service port Closed (with cap)

Shaft position Closed (with valve cap) Closed (clockwise)

Service port Closed (with cap) Open (push-pin or with vacuum pump) Closed (with cap) Open (connected manifold gauge) Open (connected manifold gauge) Open (with charging cylinder) Open (connected manifold gauge) Open (connected manifold gauge)

1.

Air purging (Installation)

Open Open (counter-clockwise) (push-pin or with vacuum pump) Open (with valve cap) Closed (clockwise) Closed (with cap) Closed (with cap)

Operation

Open (with valve cap) Open (counter-clockwise)

2.

Pumping down (Transfering)

3.

Evacuation (Servicing)

Open

Open (connected manifold gauge) Closed (with cap)

Open

4.

Gas charging (Servicing)

Open

Open

5.

Pressure check (Servicing)

Open

Open (connected manifold gauge) Open (connected manifold gauge)

Open

6.

Gas releasing (Servicing)

Open

Open

Service Manual 189

(3-way) Valve

(1) Pumping down

Indoor unit

Liquid side 2-Way valve Close Outdoor unit

Gas side 3-Way valve Open

Indoor unit

Liquid side 2-Way valve Close

Gas side 3-Way valve manifold gauge Open

Lowhandle (CLOSE)

Hi- handle (CLOSE)

• Procedure 1. Confirm that both the gas side and liquid side valves are set to the open position. - Remove the valve stem caps and confirm that the valve stems are in the raised position. - Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the manifold gauge to the service port of the gas side valve. - Connect the hose of the gauge with the push pin to the service port. 4. Air purging of the charge hose. - Open the Low-handle valve on the gauge slightly to air purge from the hose. 5. Set the liquid side valve to the closed position. • Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm g.
2

7. Immediately set the gas side valve to the closed position. - Do this quickly so that the gauge ends up indicating 1kg/ g. 8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m) - Be sure to check for gas leakage.

190 Multi type Air Conditioner

(3-way) Valve

(2) Evacuation
(All amount of refrigerant leaked)

Indoor unit

Liquid side 2-Way valve Open Outdoor unit

Gas side 3-Way valve Open

Indoor unit

Liquid side 2-Way valve Open

Gas side 3-Way valve manifold gauge Vacuum pump Lowhandle (OPEN) Hi- handle (OPEN) Open

• Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position. 2. Connect the vaccum pump to the center hose of the manifold gauge. 3. Connect the service port of the gas side valve to the low side of the gauge. 4. Evacuation for approximately one hour. - Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less). 5. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge needle does not move(approximately 5 minutes after turning off the vacuum pump). 6. Disconnect the charge hose from the vacuum pump. - Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted,replenish as needed. 7. Mount the valve caps and the service port caps.

Service Manual 191

(3-way) Valve

(3) Gas Charging
(After Evacuation)

Indoor unit

Liquid side 2-Way valve Open Outdoor unit

Gas side 3-Way valve Open

Indoor unit

Liquid side 2-Way valve Open

Gas side 3-Way valve Charging cylinder manifold gauge Open

Low-handle Check valve (OPEN)

Hi- handle (OPEN)

• Procedure
1. Connect the gauge to the charging cylinder. - Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. - If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid. 2. Purge the air from the charge hose. - Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder. 3. Open the low handle on the gauge and charge the system with liquid refrigerant. - If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure(pumping down-pin). 4. Immediately disconnect the charge hose from the gas side valve's service port. This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner. - Stopping partway will allow the gas to be discharged. - If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose. 5. Mount the valve stem nuts and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.) - Be sure to check for gas leakage.

192 Multi type Air Conditioner

Exploded View & Replacement Parts List

Exploded View & Replacement Parts List
Indoor Unit
SQ/SR chassis
135316

135314

152313

152302 131410 359011 733010

342800 159830

354210

135316 352115 352116

159901 268712

35211B 263230-2 352150 146811

346810 135516 263230-1

135311

266090 267110 249951

268716 268715 W0CZZ

Service Manual 193

Exploded View & Replacement Parts List Parts List (SQ, SR chassis)
LOCATION No. DESCRIPTION PART No. AMNH076LQL0 3141A20006A 3531A10127A 3531A20100B 3531A20187M 3551A20050P 4681A20055A 5230A10005A 5231A20032C 5983A10009V 5990A10005A 6323AQ3226T 6323A20004A 6609A10003J 6711A20067J 6871A20194A 6871A20267B 6871A20440A 4280A20004A 4681A20062A 5211AR7066P 5211A20470J 5211A20471D 5251AR2575F 5421A10024A 5901A20007B 3301A10003A 3H01487A AMNH096LQL0 3141A20006A 3531A10127A 3531A20100B 3531A20187M 3551A20050P 4681A20055A 5230A10005A 5231A20032C 5983A10009V 5990A10005A 4995A20361B 6323AQ3226T 6323A20004A 6609A10003J 6711A20067J 6871A20194A 6871A20267B 6871A20440B 4280A20004A 4681A20062A 5211AR7066P 5211A20470J 5211A20471D 5251AR2575F 5421A10024A 5901A20007B 3301A10003A 3H01487A AMNH096LRL0 3141A20005A 3531A10230A 3531A10117C 3531A10208N 3551A20099A 4681A20055A 5230A20014A 5231A20032C 5983A10006T 5990A20007A 4995A20361C 3623AQ3226T 6323A20004A 6609A10003H 6711A20067J 6871A20390A 6871A20267B 6871A20440C 4280A20004A 4681A20048A 5211AR7066L 5211A20388H 5211A20389F 5251AR2575F 5421A20087W 5901A20007A 1H00843A 3H1487A AMNH126LRL0 3141A20005A 3531A10230A 3531A10117C 3531A10208N 3551A20099A 4681A20055A 5230A20014A 5231A20032C 5983A10006T 5990A20007A 4995A20361D 3623AQ3226T 6323A20004A 6609A10003H 6711A20067J 6871A20390A 6871A20267B 6871A20440D 4280A20004A 4681A20048A 5211AR7066L 5211A20388H 5211A20389F 5251AR2575F 5421A20087W 5901A20007A 1H00843A 3H1487A SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R

131410 CHASSIS ASSEMBLY 135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 135314 GRILLE ASSEMBLY,INLET SUB 135316 GRILLE ASSEMBLY,FRONT(INDOOR) 135516 COVER ASSEMBLY,MOTOR 146811 MOTOR ASSEMBLY,STEP 152302 FILTER(MECH),A/C 152313 FILTER ASSEMBLY,DEODORIZER 159830 AIR CLEANER ASSEMBLY 159901 VANE,HORIZONTAL 263230-1 THERMISTOR ASSEMBLY 263230-2 THERMISTOR ASSEMBLY 266090 H.V ASSEMBLY 267110 REMOTE CONTROLLER ASSEMBLY 268712 PWB(PCB) ASSEMBLY,DISPLAY 268715 PWB(PCB) ASSEMBLY,MAIN(AC) 268716 PWB(PCB) ASSEMBLY,MAIN(DC) 342800 BEARING 346810 MOTOR ASSEMBLY,INDOOR 35211B TUBE ASSEMBLY,TUBING 352115 TUBE ASSEMBLY,EVAPORATOR IN 352116 TUBE ASSEMBLY,EVAPORATOR OUT 352150 HOSE ASSEMBLY,DRAIN 354210 EVAPORATOR ASSEMBLY, FIRST 359011 FAN ASSEMBLY,CROSS FLOW 733010 PLATE ASSEMBLY,INSTALL W0CZZ CAPACITOR,DRAWING

249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20361A

194 Multi type Air Conditioner

Exploded View & Replacement Parts List ST chassis

135316

267110

135314

152313

152302 131410 359011 733010

342800

159830 135311 352111

135316 159901-1 159901-2 268712

352115 352116 35211B 263230-2 352150 146811 346810 135516 263230-1 268715

249951 266090 268716

W0CZZ

Service Manual 195

Exploded View & Replacement Parts List Parts List (ST chassis)
LOCATION No. DESCRIPTION PART No. AMNH186LTL0 3141A10002A 3531A10116A 3531A20107W 3531A20207E 3551A20099C 4681A20055A 5230A20001A 5983A10006T 5990A20008A 5990A20009A 4995A20361E 6323AQ3226T 6323A20004A 6609A10003L 6711A20067J 6871A20194B 6871A20267B 6871A20440E 4280A20004A 4681A20003D 5211A20514G 5211A30058H 5211A30057D 5251AR2575F 5901A20008A 3301A10002A 5211A30439E 3H01487G AMNH246LTL0 3141A10002A 3531A10116A 3531A20107W 3531A20207E 3551A20099C 4681A20055A 5230A20001A 5983A10006T 5990A20008A 5990A20009A 4995A20361F 6323AQ3226T 6323A20004A 6609A10003L 6711A20067J 6871A20194B 6871A20267B 6871A20440F 4280A20004A 4681A20067A 5211A20514G 5211A30097J 5211A30098G 5251AR2575F 5901A20008A 3301A10002A 5211A30439J 3H01487G SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R

131410 CHASSIS ASSEMBLY 135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 135314 GRILLE ASSEMBLY,INLET SUB 135316 GRILLE ASSEMBLY,FRONT(INDOOR) 135516 COVER ASSEMBLY,MOTOR 146811 MOTOR ASSEMBLY,STEP 152302 FILTER(MECH),A/C 159830 AIR CLEANER ASSEMBLY 159901-1 VANE,HORIZONTAL 159901-2 VANE,HORIZONTAL 249951 CONTROL BOX ASSEMBLY,INDOOR 263230-1 THERMISTOR ASSEMBLY 263230-2 THERMISTOR ASSEMBLY 266090 H.V ASSEMBLY 267110 REMOTE CONTROLLER ASSEMBLY 268712 PWB(PCB) ASSEMBLY,DISPLAY 268715 PWB(PCB) ASSEMBLY,MAIN(AC) 268716 PWB(PCB) ASSEMBLY,MAIN(DC) 342800 BEARING 346810 MOTOR ASSEMBLY,INDOOR 352111* TUBE ASSEMBLY,CONNECTOR 352115 TUBE ASSEMBLY,EVAPORATOR IN 352116 TUBE ASSEMBLY,EVAPORATOR OUT 352150 HOSE ASSEMBLY,DRAIN 359011 FAN ASSEMBLY,CROSS FLOW 733010 PLATE ASSEMBLY,INSTALL 35211B TUBE ASSEMBLY,TUBING W0CZZ CAPACITOR,DRAWING NOTE) 35211* is for pipe fitting to SVC valve.

196 Multi type Air Conditioner

135515

249951 354210

266090 268714-2 267110 330870 352116 268714-1 352115

SP1 chassis(Art cool type)

144710-1 268717 146811 352150 35211B

135316 152302 144710-2 146811-2 147581 135500-3 352380 131410

263230-2

263230-1

135311-2 146811

135500-2

147581

135311-1 346810 159830 349600

135314 146811-3

268712

135311-3 359012

147581 135500-1

Exploded View & Replacement Parts List

Service Manual 197

146811-2

Exploded View & Replacement Parts List Parts List (SP1 chassis)
LOCATION No. DESCRIPTION PART No. AMNH096AP*1 AMNC096AP*1 AMNH126AP*1 AMNC126AP*1 3141A20004N 3550A20123A 3550A20124A 3550A20060A 3531A20069G 3531A20069H 3531A20069J 3531A20212K 3531A20212L 3531A20212M 3551A20031B 3531A20213N 3531A20213P 3531A20213Q 4758A20014B 4681A20055C 4681A20055A 5230A20032A 5983A20007F 4994A10046A 6871A20380D 6871A20381D 6609A10003S 6323AQ6226T 6323A20004N 6871A20388A 6711A20073D 3087A30004A 4681A20091A 4960A20016A 5211A20301J 5211A20302J 5211AR7066F 5251AR1222R 5238A20020A 5421A20072A 5900A00003A 3141A20004N 3550A20123A 3550A20124A 3550A20060A 3531A20069G 3531A20069H 3531A20069J 3531A20212K 3531A20212L 3531A20212M 3551A20031B 3531A20213R 3531A20213S 3531A20213T 4758A20014B 4681A20055C 4681A20055A 5230A20032A 5983A20007F 4995A20372N 4994A10046A 6871A20380D 6871A20381G 6609A10003S 6323AQ6226T 6323A20004N 6871A20363D 6711A20073E 3087A30004A 4681A20091A 4960A20016A 5211A20301J 5211A20302J 5211AR7066F 5251AR1222R 5238A20020A 5421A20072A 5900A00003A 3141A20004N 3550A20123A 3550A20124A 3550A20060A 3531A20069G 3531A20069H 3531A20069J 3531A20212K 3531A20212L 3531A20212M 3551A20031B 3531A20213N 3531A20213P 3531A20213Q 4758A20014B 4681A20055C 4681A20055A 5230A20032A 5983A20007F 4995A20372J 4994A10046A 6871A20380D 6871A20381F 6609A10003S 6323AQ6226T 6323A20004N 6871A20388A 6711A20073D 3087A30004A 4681A20091A 4960A20016A 5211A20301J 5211A20302J 5211AR7066F 5251AR1222R 5238A20020A 5421A20072A 5900A00003A 3141A20004N 3550A20123A 3550A20124A 3550A20060A 3531A20069G 3531A20069H 3531A20069J 3531A20212K 3531A20212L 3531A20212M 3551A20031B 3531A20213R 3531A20213S 3531A20213T 4758A20014B 4681A20055C 4681A20055A 5230A20032A 5983A20007F 4995A20372P 4994A10046A 6871A20380D 6871A20381G 6609A10003S 6323AQ6226T 6323A20004N 6871A20363D 6711A20073E 3087A30004A 4681A20091A 4960A20016A 5211A20301J 5211A20302J 5211AR7066F 5251AR1222R 5238A20020A 5421A20072A 5900A00003A SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

131410 CHASSIS ASSEMBLY 135500-1 COVER 135500-2 COVER 135500-3 COVER 135311-1 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 135311-2 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 135311-3 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 135314 GRILLE ASSEMBLY, INLET M: Matal B: Blue D: Wood 135515 COVER ASSEMBLY,TOP(INDOOR) 135316 GRILLE ASSEMBLY, FRONT(INDOOR) 147581 LOUVER,HORIZONTAL 146811-1 MOTOR ASSEMBLY,STEP 146811-2 MOTOR ASSEMBLY,STEP 152302 FILTER(MECH),A/C 159830 AIR CLEANER ASSEMBLY 249941 CONTROL BOX,INDOOR 268715 PWB(PCB) ASSEMBLY,MAIN(AC) 268716 PWB(PCB) ASSEMBLY,MAIN(DC) 266090 H.V ASSEMBLY 263230-1 THERMISTOR ASSEMBLY 263230-2 THERMISTOR ASSEMBLY 268712 PWB(PCB) ASSEMBLY,DISPLAY 267110 REMOTE CONTROLLER ASSEMBLY 330870 DRAIN PAN ASSEMBLY 346810 MOTOR ASSEMBLY,INDOOR 349600 MOUNT,MOTOR 352116 TUBE ASSEMBLY,EVAPORATOR OUT 352115 TUBE ASSEMBLY,EVAPORATOR IN 35211B TUBE ASSY,TUBING 352150 HOSE ASSEMBLY,DRAIN 352380 AIR GUIDE 354210 EVAPORATOR ASSEMBLY,FIRST 359012 FAN,TURBO M: Matal B: Blue D: Wood

249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20372H

198 Multi type Air Conditioner

Exploded View & Replacement Parts List Art Cool Deluxe Type(SU, SZ chassis)
146811 135316

152302

668713-1 146811-1

145200

668713-2

135313

135080-1 263020 135080-2

135511

263230-2

263230-1

733010

267110 159830 266090 352111

359011

342800

131410 346810 352150 352114 352118 W0CZZ 35211B 266090 249951

146811 159901 135311 268714 249941

Service Manual 199

Exploded View & Replacement Parts List Parts List(Art cool Deluxe Type)
LOCATION No. PART No. DESCRIPTION AMNH076DZ*0 3141A20009B 3508A20055B 3508A20056B 3531A20184C 3531A20196J 3531A20196E 3531A20195B 3531A20196F 3531A10214K 3531A10214H 3531A10214J 3531A10214Q 4681A20055A 4681A20055B 5983A10009V 5230A20033A 5990A20022B 4995A20323K 4994A20067A 6302A90003A 6323AQ2226T 6323A20004A 6609A10005B 6711A20073P 6871A10111E 4280A20004A 4681A20103C 5211A202569D 5211A20605B 5211A30596A 5251AR1222R 5421A20149E 5901A20016E 6871A20258B 6871A20259A 3301A10005A 3H01487A W: White M: Metal R: Mirror B: Blue 135316 GRILLE ASSEMBLY, FRONT W: White M: Metal R: Mirror B: Blue 146811 MOTOR ASSEMBLY, STEP (Vane) 146811-1 MOTOR ASSEMBLY, STEP (Door) 159830 AIR CLEANER ASSEMBLY 152302 FILTER (MECH), A/C 159901 VANE HORIZONTAL 249951 CONTROL BOX ASSEMBLY 249941 CONTROL BOX, INDOOR 263020 DIGITRON 263230-1 THERMISTOR ASSEMBLY(Out) 263230-2 THERMISTOR ASSEMBLY(Room, In) 266090 HUB ASSEMBLY 267110 REMOTE CONTROLLER ASSEMBLY 268714 PWB(PCB) ASSEMBLY, MAIN 342800 BEARING 346810 MOTOR ASSEMBLY, INDOOR 352114 TUBE ASSEMBLY DISTRIBUTOR 352118 TUBE ASSEMBLY MANIFOLD 35211B TUBE ASSEMBLY, TUBING 352150 HOSE ASSEMBLY, DRAIN 354212 EVAPORATOR ASSEMBLY, FINAL 359011 FAN ASSEMBLY, CROSS FLOW 668713 PWB ASSEMBLY, SUB 668713 PWB ASSEMBLY, SUB 733010 PLATE W0CZZ CAPACITOR,DRAWING AMNH096DU*0 3141A20007B 3508A20034E 3508A20034F 3531A10137B 3531A20118Z 3531A20118Y 3531A20118X 3531A20118W 3531A21026C 3531A21026B 3531A21026A 3531A21026D 4681A20055A 4681A20055B 5983A10006T 5230A20022A 5990A20015B 4995A20323L 4994A20067A 6302A90003A 6323AQ2226T 6323A20004A 6609A10005A 6711A20073C 6871A10111F 4280A20004A 4681A20048A 5211A202569D 5211A20605B 5211AR7066L 5251AR1222R 5421A20105H 5901A20016A 6871A20258B 6871A20259A 1H00843A 3H01487A AMNH126DU*0 3141A20007B 3508A20034E 3508A20034F 3531A10137B 3531A20118Z 3531A20118Y 3531A20118X 3531A20118W 3531A21026C 3531A21026B 3531A21026A 3531A21026D 4681A20055A 4681A20055B 5983A10006T 5230A20022A 5990A20015B 4995A20232M 4994A20067A 6302A90003A 6323AQ2226T 6323A20004A 6609A10005A 6711A20073C 6871A10111G 4280A20004A 4681A20048A 5211A202569D 5211A20605B 5211AR7066L 5251AR1222R 5421A20105H 5901A20016A 6871A20258B 6871A20259A 1H00843A 3H01487A R R R R R R R R R R R R R R R R R R R R R R SVC CODE R R R R R R R R R R R R R R

131410 CHASSIS ASSEMBLY 135080-1 DECORATION (TOP) 135080-2 DECORATION (BOTTOM) 135311 GRILLE ASSEMBLY, DISCHARGE 135313 GRILLE ASSEMBLY, INLET

200 Multi type Air Conditioner

Exploded View & Replacement Parts List Duct Type - High Static(BH, BG chassis)

359012 237210

346810

359012 336610-1 336610-2

W0CZZ

249951 354210 152302 268714

352111

263230-1 263230-2 552111 352118 330860 263230-3 267110

Service Manual 201

Exploded View & Replacement Parts List Parts List(Duct - High static)
LOCATION No. 152302 237210 249951 DESCRIPTION FILTER (MECH), A/C PANEL ASSEMBLY, UPPER CONTROL BOX ASSEMBLY(INDOOR) PART No. AMNH186BHA0 5230A30001M 3721A20177A 4995A14002A 6323AQ3226G 6323AQ3214E 6323AQ3226V 6711A10008X 6871A10140E 3087A10008B 3660A20017A 3660A20018A 4681A10013C 5211A20514G 5211A20465G 5421A20100A 5901A10026A 5901A10028B 5211A20466K 2A00986D AMNH246BHA0 AMNH306BGA0 AMNH366BGA0 5230A30001M 3721A20177A 4995A14002B 6323AQ3226G 6323AQ3214E 6323AQ3226V 6711A10008X 6871A10140F 3087A10008B 3660A20017A 3660A20018A 4681A10013C 5211A20514G 5211A20465G 5421A20100B 5901A10026A 5901A10028B 5211A20466L 2A00986D 5230A30001L 3721A20180A 4995A14002C 6323AQ3226G 6323AQ3214E 6323AQ3226V 6711A10008X 6871A10131H 3087A10008A 3660A20019A 3660A20020A 4681A10013J 5211A20514J 5211A20416J 5421A10027A 5901A10026A 5901A10028J 5211A20693D 2A00986D 5230A30001L 3721A20180A 4995A14002D 6323AQ3226G 6323AQ3214E 6323AQ3226V 6711A10008X 6871A10131J 3087A10008A 3660A20019A 3660A20020A 4681A10013A 5211A20514J 5211A20416J 5421A10027A 5901A10026A 5901A10028A 5211A20693D 2A00986D SVC CODE R R R R R R R R R R R R R R R R R R R

263230-1 THERMISTOR ASSEMBLY(IN) 263230-2 THERMISTOR ASSEMBLY(ROOM) 263230-3 THERMISTOR ASSEMBLY (OUT) 267110 268714 330860 REMOTE CONTROLLER ASSEMBLY PWB(PCB) ASSEMBLY, MAIN DRAIN PAN ASSEMBLY

336610-1 HOUSING(MECH), WRAPPER 336610-2 HOUSING(MECH), WRAPPER 346810 352118 354210 359012 552111 MOTOR ASSEMBLY, INDOOR TUBE ASSEMBLY, MENIFOLD(INDOOR) EVAPORATOR ASSEMBLY, FIRST FAN ASSEMBLY, BLOWER(Motor) TUBE ASSEMBLY, CAPILLARY 352111* TUBE ASSEMLBY, CONNECTOR

359012-1 FAN ASSEMBLY, BLOWER(Single)

WOCZZ CAPACITOR, DRAWING

NOTE) *5211A20514G is for connecting service valve pipe fitting.

202 Multi type Air Conditioner

Exploded View & Replacement Parts List Duct Type - Low Static (BT, BT1 chassis)

152302

346810 336610 359012-2

W0CZZ 359012-1

354210

267110

249951 268714 552111 352118 330860 352111

263230-1

263230-2

263230-3

Service Manual 203

Exploded View & Replacement Parts List Parts List (Duct Type - Low Static)
LOCATION No. DESCRIPTION PART No. AMNH096BTG0 5230A30001Q 3721A20150B 4995A20338F 6323AQ3226G 6323AQ3214E 6323A20025D 6711A10008U 6871A10131A 3087A10015C 3660A20033A 4681A10022B 5211A10418B 5421A20153B 5901A20030A 5211A10417B 3828A20403E 3828A20395B 3A02157K AMNH126BTG0 5230A30001Q 3721A20150B 4995A20338E 6323AQ3226G 6323AQ3214E 6323A20025D 6711A10008U 6871A10131B 3087A10015C 3660A20033A 4681A10022B 5211A25011B 5421A21002A 5901A20030A 5211A25010A 3828A20403E 3828A20395B 3A02157K AMNH186BTG0 5230A30001P 3721A20150A 4995A20338J 6323AQ3226G 6323AQ3214E 6323A20025D 6711A10008U 6871A10131G 3087A10015B 3660A20033A 4681A10022A 5211A10418C 5421A20153A 5901A20030A 5901A20030B 5211A20514G 5211A10417B 3828A20403E 3828A20395B 3A02157H SVC CODE R R R R R R R R R R R R R R R R R R R R

152302 FILTER(MECH), A/C 237203 PANEL ASSEMBLY, UPPER 249951 CONTROL BOX ASSEMBLY(INDOOR) 263230-1 THERMISTOR ASSEMBLY (IN) 263230-2 THERMISTOR ASSEMBLY (ROOM) 263230-3 THERMISTOR ASSEMBLY (OUT) 267110 REMOTE CONTROLLER ASSEMBLY 268714 PWB(PCB) ASSEMBLY, MAIN 330860 DRAIN PAN ASSEMBLY 336610 HOUSING(MECH), WRAPPER 346810 MOTOR ASSEMBLY, INDOOR 352118 TUBE ASSEMBLY, MENIFOLD(INDOOR) 354210 EVAPORATOR ASSEMBLY, FIRST 359012-1 FAN ASSEMBLY, BLOWER(Single) 359012-2 FAN ASSEMBLY, BLOWER(Single) 352111 TUBE ASSEMBLY, CONNECTOR 552111 TUBE ASSEMBLY, EVAPORATOR IN 738282 MANUAL, INSTALLATION 738290 MANUAL, OWNER'S WOCZZ CAPACITOR, DRAWING

204 Multi type Air Conditioner

Exploded View & Replacement Parts List Built in Duct type (BP chassis)

137214

267110-2

249951 267110-1

263230-1

263230-2 336610-1 359012 263230-3 268714 137210

158591 346810

352118

359012-1 336610-2

352111 354210

330860

152302

137202

Service Manual 205

Exploded View & Replacement Parts List Parts List(Built in Duct Type-BP chassis)
Location No. 237202 137210 137214 152302 158591 249951 PANLE, FRONT PANEL ASSEMBLY, FRONT (SINGLE) PANEL, UPPER FILTER (MECH), A/C PUMP ASSEMBLY, WATER CONTROL BOX ASSEMBLY(INDOOR) Part No. Description AMNH096BPA0 3720A20260B 3721A20168A 3721A20188A 5230A30001R 5859A20002A 4995A20355C 6323AQ3226G 6323AQ3214E 6323AQ3226V 6711A10008U 6871A10140G 3086A10036A 3660A20017A 3660A20018A 4681A10031A 5211A21171A 5211A21172A 5421A20178E 5901A10049A 5901A10026A 2A00986D AMNH126BPA0 3720A20260B 3721A20168A 3721A20188A 5230A30001R 5859A20002A 4995A20355B 6323AQ3226G 6323AQ3214E 6323AQ3226V 6711A10008U 6871A10140H 3086A10036A 3660A20017A 3660A20018A 4681A10031A 5211A21171A 5211A21172A 5421A20178E 5901A10049A 5901A10026A 2A00986D R R SVC CODE R R R R R R R R R R R R R R R R R R

263230-1 THERMISTOR ASSEMBLY (IN) 263230-2 THERMISTOR ASSEMBLY (ROOM) 263230-3 THERMISTOR ASSEMBLY (OUT) 267110 268714 330860 REMOTE CONTROLLER ASSEMBLY PWB(PCB) ASSEMBLY, MAIN DRAIN PAN ASSEMBLY

336610-1 HOUSING(MECH), WRAPPER 336610-2 HOUSING(MECH), WRAPPER 346811 MOTOR ASSEMBLY, INDOOR 352118-1 TUBE ASSEMBLY, MENIFOLD(OUT) 352118-2 TUBE ASSEMBLY, MANIFOLD (IN) 354210 359012 WOCZZ EVAPORATOR ASSEMBLY, FIRST FAN ASSEMBLY, BLOWE CAPACITOR, DRAWING

359012-1 FAN ASSEMBLY, BLOWER(SINGLE)

206 Multi type Air Conditioner

267110-2 346810 130911 W1SZ

267110-1

354212 158591

266012 359011

137211 352116

Cassette Type - 1 way (TC chassis)

330860

352115

268712 354210

135802

146811 152302 266090 140570 W0CZZ 249951 152312 159830 135312 268714

Exploded View & Replacement Parts List

Service Manual 207

263230-1

263230-2

263230-3

Exploded View & Replacement Parts List Parts List(Cassette Type - 1 way)
LOCATION No. DESCRIPTION PART No. AMNH096TCC0 3531A10062D 3721A10123F 3580A20005A 6871A10140A 3091A10024A 4681AR2727G 5990A20004A 5859A10001A 5231A10003A 5983A10006A 4995A10114B 6323AQ3226E 6323AQ3226V 6323AQ3214P 6601A20001E 6690A20005C 6711A10008V 6711A20096B 6871A20096B 3087A10005A 5211A20229E 5211A20230E 5421A10011A 5251A20001A 5901AR2441A 4681A20003Y 3H00671E 5239A10004A AMNH126TCC0 3531A10062D 3721A10123F 3580A20005A 6871A10140B 3091A10024A 4681AR2727G 5990A20004A 5859A10001A 5231A10003A 5983A10006A 4995A10114A 6323AQ3226E 6323AQ3226V 6323AQ3214P 6601A20001E 6690A20005C 6711A10008V 6711A20096B 6871A20096B 3087A10005A 5211A20229E 5211A20230E 5421A10011A 5251A20001A 5901AR2441A 4681A20003Y 3H00671E 5239A10004A SVC CODE R R R R R R R R R R R R R R R R R Option R R R R R R R R R R

135312 GRILLE ASSEMBLY,INLET 137211 INLET GRILE ASSEMBLY 135802 DOOR LOCK 268714 PWB(PCB) ASSEMBLY,MAIN 139011 CABINET ASSEMBLY,INDOOR 146811 MOTOR ASSEMBLY,STEP 152302 VANE HORIZONTAL 158580 PUMP ASSEMBLY,WATER 152312 FILTER ASSEMBLY,AIR CLEANER 159830 AIR CLEANER ASSEMBLY 249951 CONTROL BOX ASSEMBLY,INDOOR 263230-1 THERMISTOR ASSEMBLY (IN) 263230-2 THERMISTOR ASSEMBLY (OUT) 263230-3 THERMISTOR ASSEMBLY (ROOM) 266012 SWITCH ASSEMBLY,FLOAT 266090 HVB ASSEMBLY 267110-1 REMOTE CONTROLLER ASSEMBLY 267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS) 268712 PWB(PCB) ASSEMBLY, DISPLAY 330870 DRAIN PAN ASSEMBLY 352115 TUBE ASSEMBLY,EVAPORATOR IN 352116 TUBE ASSEMBLY, EVAPORATOR OUT 354210 EVAPORATOR ASSEMBLY,FIRST 354212 DRAIN ASSEMBLY,TUBE 359011 FAN ASSEMBLY,CROSS FLOW 346810 MOTOR ASSEMBLY,INDOOR W0CZZ CAPACITOR, DRAWING W1SZ AIR GUIDE ASSEMBLY

208 Multi type Air Conditioner

Exploded View & Replacement Parts List Cassette Type - 4 way(TE chassis)

266090 249951

263230-3

263230-2

263230-1

268714

159830

354211

352118

35211A

158591 266012 352111 330870

Service Manual 209

Exploded View & Replacement Parts List

137211 130411

W0CZZ

346811

359011 146811 W4056 268712

152312

130911-1

135312-2

135802

130911-2 267110-2 267110-1 352150

210 Multi type Air Conditioner

Exploded View & Replacement Parts List Parts List(Cassette Type - 4 way - TE 12K, 18K)
LOCATION No. 130411 DESCRIPTION BASE ASSEMBLY,WELD[INDOOR] PART No. AMNH126TEC0 AMNC126TEC0 AMNH186TEC0 AMNC186TEC0 3041A10013A 3091A10023C 3091A10023D 3721A10105B 3531A10059A 3580A20005A 4681A20055A 5231A10005A 5859A20001M 5983A10002A 4995A14001D 6323AQ3226T 6323AQ3226F 6323A10002A 6601A20001G 6609A20005C 6871A20096J 6871A10158D 6711A20076N 6711A20096B 3087A10002A 4681AC2026E 5211A20241S 5211A20243M 5251A20002A 5421A10006M 5900A10004A 3H00660N 4056A20001A 3041A10013A 3091A10023C 3091A10023D 3721A10105D 3531A10059A 3580A20005A 4681A20055A 5231A10005A 5859A20001M 5983A10002A 4995A14001R 6323AQ3226T 6323AQ3226F 6323A10002A 6601A20001G 6609A20005C 6871A20096J 6871A10338U 6711A20076K 6711A20096B 3087A10002A 4681AC2026C 5211A20241R 5211A20243M 5251A20002A 5421A10006A 5900A10004A 3H00660N 4056A20001A 3041A10013A 3091A10023C 3091A10023D 3721A10105B 3531A10059A 3580A20005A 4681A20055A 5231A10005A 5983A10002A 4995A14001C 3041A10013A 3091A10023C 3091A10023D 3721A10105D 3531A10059A 3580A20005A 4681A20055A 5231A10005A 5983A10002A 4995A14001S SVC CODE R R R R R R R R R R R R R R R R R R R option R R R R R R R R R R

130911-1 CABINET ASSEMBLY,INDOOR 130911-2 CABINET ASSEMBLY,INDOOR 137211 135312 135802 146811 152312 158591 159830 249951 PANEL ASSEMBLY,FRONT(INDOOR) GRILLE ASSEMBLY,FRONT(INDOOR) DOOR ROCK MOTOR ASSEMBLY,STEP FILTER ASSEMBLY, AIR CLEANER PUMP ASSEMBLY,WATER AIR CLEANER ASSEMBLY CONTROL BOX ASSEMBLY,INDOOR

5859A20001M 5859A20001M

263230-1 THERMISTOR ASSEMBLY (OUT) 263230-2 THERMISTOR ASSEMBLY (IN) 263230-3 THERMISTOR ASSEMBLY (ROOM) 266012 266090 268712 268714 SWITCH ASSEMBLY,FLOAT H.V ASSEMBLY PWB(PCB) ASSEMBLY,DISPLAY PWB(PCB) ASSEMBLY,MAIN

6323AQ3226T 6323AQ3226T 6323AQ3226F 6323AQ3226F 6323A10002A 6609A20005C 6871A20096J 6871A10158C 6711A20076N 6711A20096B 3087A10002A 6323A10002A 6609A20005C 6871A20096J 6871A10338V 6711A20076K 6711A20096B 3087A10002A 6601A20001G 6601A20001G

267110-1 REMOTE CONTROLLER ASSEMBLY 267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS) 330870 346810 352118 35211A 352150 354211 359011 W0CZZ W4056 DRAIN PAN ASSEMBLY MOTOR ASSEMBLY,INDOOR TUBE ASSEMBLY,MENIFOLD(INDOOR) TUBE ASSEMBLY, SUCTION (INDOOR) DRAIN ASSEMBLY, TUBE EVAPORATOR ASSEMBLY,BENDING FAN,TURBO CAPACITOR,DRAWING LOCKER

4681AC2026C 4681AC2026C 5211A20514G 5162A20011C 5211A20241R 5251A20002A 5900A10004A 3H00660N 4056A20001A 5211A20241R 5251A20002A 5900A10004A 3H00660N 4056A20001A 5211A20243M 5211A20243M 5421A10006M 5421A10006A

352111* SOKET (MECH) FLAKE

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 211

Exploded View & Replacement Parts List Cassette Type - 4 way(TF chassis)

266090

249951

268714

354211-2 354211-1

159830

263230-1 352118-2 263230-2 552111 352118-1

158591

266012

330870

212 Multi type Air Conditioner

Exploded View & Replacement Parts List

130411

268712 W0CZZ 146811 346810

359012

152312

130911-2

135314

137211

267110-2

267110-1

130911-1

Service Manual 213

Exploded View & Replacement Parts List Parts List(Cassette Type - 4 way - TF 24K, 30K)
LOCATION No. DESCRIPTION PART No. AMNH246TFC0 3041A10030B 3091A10051A 3091A10051B 3721A10072E 3531A10211C 4681A20055A 5231A10012A 5859A20001K 5983A10002A 4995A10093K 6323AQ3226Y 6323AQ3226E 6323A10002A 6601A20001H 6609A20005E 6871A20096J 6871A10158B 6711A20076N 6711A20096B 3087A10010B 4681A20051Z 5211A20011C 5211A20251Q 5211A20251K 5211A21137B 5251A20002B 5421A10016G 5421A10016H 5901A10036A 3H00660M 4056A20001B AMNC246TFC0 3041A10030B 3091A10051A 3091A10051B 3721A10072G 3531A10211C 4681A20055A 5231A10012A 5859A20001K 5983A10002A 4995A10131B 6323AQ3226Y 6323AQ3226E 6323A10002A 6601A20001H 6609A20005E 6871A20096J 6871A10209M 6711A20076K 6711A20096B 3087A10010B 4681A20051W 5211A20514J 5211A20251Q 5211A20251K 5211A21137B 5251A20002B 5421A10016G 5421A10016H 5901A10036A 3H00660M 4056A20001B AMNH306TFC0 3041A10030B 3091A10051A 3091A10051B 3721A10072E 3531A10211C 4681A20055A 5231A10012A 5859A20001K 5983A10002A 4995A10093N 6323AQ3226Y 6323AQ3226E 6323A10002A 6601A20001H 6609A20005E 6871A20096J 6871A10158R 6711A20076N 6711A20096B 3087A10010B 4681A20051W 5211A20514J 5211A20251Q 5211A20251K 5211A21137B 5251A20002B 5421A10016G 5421A10016H 5901A10036A 3H00660M 4056A20001B SVC CODE R R R R R R R R R R R R R R R R R R option R R R R R R R R R R R R

130411 BASE ASSEMBLY,WELD[INDOOR] 130911-1 CABINET ASSEMBLY,INDOOR 130911-2 CABINET ASSEMBLY,INDOOR 137211 PANEL ASSEMBLY,FRONT(INDOOR) 135314 GRILLE ASSEMBLY,FRONT(INDOOR) 146811 MOTOR ASSEMBLY,STEP 152312 FILTER ASSEMBLY, AIR CLEANER 158591 PUMP ASSEMBLY,WATER 159830 AIR CLEANER ASSEMBLY 249951 CONTROL BOX ASSEMBLY,INDOOR 263230-1 THERMISTOR ASSEMBLY (OUT) 263230-2 THERMISTOR ASSEMBLY (IN) 263230-3 THERMISTOR ASSEMBLY (ROOM) 266012 SWITCH ASSEMBLY,FLOAT 266090 H.V ASSEMBLY 268712 PWB(PCB) ASSEMBLY,DISPLAY 268714 PWB(PCB) ASSEMBLY,MAIN 267110-1 REMOTE CONTROLLER ASSEMBLY 267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS) 330870 DRAIN PAN ASSEMBLY 346810 MOTOR ASSEMBLY,INDOOR 352111* SOCKET (MECH), FLAKE 352118-1 TUBE ASSEMBLY,MENIFOLD(INDOOR) 352118-2 TUBE ASSEMBLY, MANIFOLD (INDOOR) 552111 TUBE ASSEMBLY, CAPILLARY (INDOOR) 352150 DRAIN ASSEMBLY, TUBE 354211-1 EVAPORATOR ASSEMBLY,BENDING 354211-2 EVAPORATOR ASSEMBLY, BENDING 359012 FAN,TURBO W0CZZ CAPACITOR,DRAWING W4056 LOCKER

NOTE) 35211* is for pipe fitting the SVC valve.

214 Multi type Air Conditioner

Exploded View & Replacement Parts List Cassette Type - 4 way(TD chassis)

249951 266090

159830

268714

263230-1 263230-2

130411

263230-3

354211

352118-1

552111 330870 352118-2

158591

266012

Service Manual 215

Exploded View & Replacement Parts List

130411

W0CZZ

146811

268712

346810 152312 359012

140570 130911-2 130912-1 135313

135802 267110-1 137211 130912-2

130911-1 267110-2 352150-2

216 Multi type Air Conditioner

Exploded View & Replacement Parts List Parts List(Cassette Type - 4 way - TD 36K)
LOCATION No. 130411 130911-1 130911-2 130912-1 130912-2 137211 135314 135802 146811 152312 158591 159830 249951 263230-1 263230-2 263230-3 266012 266090 268712 268714 267110-1 267110-2 330870 346810 352111* 352118-1 352118-2 552111 354211-1 354211-2 359011 W0CZZ W4056 DESCRIPTION BASE ASSEMBLY,WELD[INDOOR] CABINET ASSEMBLY, INDOOR CABINET ASSEMBLY, INDOOR CABINET ASSEMBLY, INDOOR CABINET ASSEMBLY, INDOOR PANEL ASSEMBLY,FRONT(INDOOR) GRILLE ASSEMBLY,FRONT(INDOOR) DOOR ROCK MOTOR ASSEMBLY,STEP FILTER ASSEMBLY, AIR CLEANER PUMP ASSEMBLY,WATER AIR CLEANER ASSEMBLY CONTROL BOX ASSEMBLY,INDOOR THERMISTOR ASSEMBLY (OUT) THERMISTOR ASSEMBLY (IN) THERMISTOR ASSEMBLY (ROOM) SWITCH ASSEMBLY,FLOAT H.V ASSEMBLY PWB(PCB) ASSEMBLY,DISPLAY PWB(PCB) ASSEMBLY,MAIN REMOTE CONTROLLER ASSEMBLY REMOTE CONTROLLER ASSEMBLY (WIRELESS) DRAIN PAN ASSEMBLY MOTOR ASSEMBLY,INDOOR TUBE ASSEMBLY, CONNECTOR TUBE ASSEMBLY,MENIFOLD(INDOOR) TUBE ASSEMBLY, MANIFOLD (INDOOR) TUBE ASSEMBLY, CAPILLARY (INDOOR) EVAPORATOR ASSEMBLY,BENDING EVAPORATOR ASSEMBLY, BENDING FAN,TURBO CAPACITOR,DRAWING LOCKER PART No. AMNH366TDC0 3041A10016A 3091A10030A 3091A10030B 3091A10031A 3091A10031B 3721A10106B 3531A10066A 3580A20005A 4681A20055A 5231A10004A 5859A20001D 5983A10003D 4995A22004L 6323AQ3226V 6323AQ3226A 6323A10002B 6601A20001F 6609A20005D 6871A20096J 6871A10158S 6711A20076N 6711A20096B 3087A10006A 4681A20006J 5211A20154J 5211A20251R 5211A20251B 5211A20316M 5421A10016A 5421A10016B 5900A10003B 3H00660M 4056A20001B SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 217

Exploded View & Replacement Parts List Convertible Type (VE chassis)

137211 268712 147581

135310

152302 135313 146811

733010 131410

267110 W0CZZ 266000 330870

135500 346810 263230-1 354212 35211B 352150 268716 W4810 359011 342800 330780 159830 266090 266000 249951 263230-2 268715 131410

218 Multi type Air Conditioner

Exploded View & Replacement Parts List Parts List(Convertible Type-VE chassis)
PART No. AMNH096VEA0 AMNH096VEL0 AMNH126VEA0 AMNH126VEL0 3721A10092A 4681A20055A 4758A10006A 5230A10009A 4995A20356F 6323A20004T 6323AQ3226V 6600AP2059B 6711A20096A 6871A20390D 6871A20359B 6871A20358E 3078A20001A 3087A10018A 4280A20004A 4681A20131B 5211A21217B 5211A25012B 5211A22007B 5251AR2575Q 5421A30019B 5901A20008E 3301A10002A 3H00671A 4810A21019A 3141A10009A 3550A30201A 3531A10248A 3531A10247A 3721A10092A 4681A20055A 4758A10006A 5230A10009A 5983A20007F 4995A20356 6323A20004T 6323AQ3226V 6600AP2059B 6609A10003S 6711A20096A 6871A20390D 6871A20359B 6871A20358 3078A20001A 3087A10018A 4280A20004A 4681A20131B 5211A21217B 5211A25012B 5211A22007B 5251AR2575Q 5421A30019B 5901A20008E 3301A10002A 3H00671A 4810A21019A 3141A10009A 3550A30201A 3531A10248A 3531A10247A 3721A10092A 4681A20055A 4758A10006A 5230A10009A 4995A20356E 6323A20004T 6323AQ3226V 6600AP2059B 6711A20096A 6871A20390D 6871A20359B 6871A20358F 3078A20001A 3087A10018A 4280A20004A 4681A20131A 5211A21217B 5211A25012B 5211A22007B 5251AR2575Q 5421A30019B 5901A20008E 3301A10002A 3H00671A 4810A21019A 3141A10009A 3550A30201A 3531A10248A 3531A10247A 3721A10092A 4681A20055A 4758A10006A 5230A10009A 5983A20007F 4995A20356 6323A20004T 6323AQ3226V 6600AP2059B 6609A10003S 6711A20096A 6871A20390D 6871A20359B 6871A20358 3078A20001A 3087A10018A 4280A20004A 4681A20131A 5211A21217B 5211A25012B 5211A22007B 5251AR2575Q 5421A30019B 5901A20008E 3301A10002A 3H00671A 4810A21019A 3141A10009A 3550A30201A 3531A10248A 3531A10247A

LOCATION No. 137211 146811 147581 152302 159830 249951

DESCRIPTION PANEL ASSEMBLY,FRONT(INDOOR) MOTOR ASSEMBLY,STEP LOUVER,HORIZONTAL FILTER(MECH),A/C AIR CLEANER ASSEMBLY CONTROL BOX ASSEMBLY,INDOOR

SVC CORD R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

263230-1 THERMISTOR ASSEMBLY (IN, ROOM) 263230-2 THERMISTOR ASSEMBLY (OUT) 266000 266090 267110 268712 268715 268716 330780 330870 342800 346810 35211B 352115 352116 352150 354211 359011 733010 W0CZZ W4810 131410 135500 135310 135313 SWITCH,PUSH H.V ASSEMBLY REMOTE CONTROLLER ASSEMBLY PWB(PCB) ASSEMBLY,DISPLAY PWB(PCB) ASSEMBLY,MAIN(AC) PWB(PCB) ASSEMBLY,MAIN(DC) CUT OFF DRAIN PAN ASSEMBLY BEARING MOTOR ASSEMBLY,INDOOR TUBE ASSEMBLY,TUBING TUBE ASSEMBLY, EVAPORATOR IN TUBE ASSEMBLY EVAPORATOR OUT HOSE ASSEMBLY,DRAIN EVAPORATOR ASSEMBLY,FIRST FAN ASSEMBLY,CROSS FLOW PLATE ASSEMBLY,INSTALL CAPACITOR,DRAWING BRACKET CHASSIS ASSEMBLY COVER GRILL ASSEMBLY, DIFFUSER(INDOOR) GRILL ASSEMBLY, INLET

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request. (GCSC WEBSITE http://biz.LGservice.com)

Service Manual 219

135310

352111

146811

159911

346810 166000

Convertible Type (VB chassis)

220 Multi type Air Conditioner
130911 235450 237900 268711 249951 352115 354210 35211A 263230-1 263230-2 268712 W0CZZ 330870 359010 152302 342800

159912

Exploded View & Replacement Parts List

352150

267110

137211

135314

135303

Exploded View & Replacement Parts List Parts List(Convertible Type-VB chassis)
Location No. 130911 135303 135310 135314 137211 146811 152302 159911 159912 166000 235450 237900 249951 263230-1 263230-2 267110 268711 268712 330870 342800 346810 35211A 352111* 352115 352150 354210 359010 W0CZZ Part No. Description CABINET ASSEMBLY GRILLE, INLET GRILLE ASSEMBLY, DIFFUSER (INDOOR) GRILLE ASSEMBLY, INLET SUB PANEL ASSEMBLY, FRONT (INDOOR) MOTOR ASSEMBLY, STEP FILTER(MECH), A/C VANE ASSEMBLY, HORIZONTAL(UPPER) VANE ASSEMBLY, HORIZONTAL(LOWER) SWITCH, PUSH DISPLAY ASSEMBLY (MECH) WINDOW, DISPLAY CONTROL BOX ASSEMBLY, INDOOR THERMISTOR ASSEMBLY (ROOM, IN) THERMISTOR ASSEMBLY (OUT) REMOTE CONTROLLER ASSEMBLY PWB(PCB) ASSEMBLY, MAIN PWB(PCB) ASSEMBLY, DISPLAY DRAIN PAN ASSEMBLY BEARING MOTOR ASSEMBLY, INDOOR TUBE ASSEMBLY, SUCTION INDOOR TUBE ASSEMBLY, CONNECTOR TUBE ASSEMBLY, EVAPORATOR - IN HOSE ASSEMBLY, DRAIN EVAPORATOR ASSEMBLY, FIRST FAN ASSEMBLY, CROSS FLOW CAPACITOR, DRAWING AMNH186VBA0 AMNH246VBA0 AMNC246VBA0 3091AP2533A 5230AP1236A 3531A10272C 5237AP2817B 3720AP2767P 4681A20055A 5230AP7093A 5991AP2867B 5991AP7334C 6600AP2059B 3545AP7224B 3790AP7080A 4995A10107B 6323A20004Y 6323AQ3226Y 6711A20096A 3871A10159B 6871AQ3263A 3087AP7233A 3H02821B 4681AP2306M 5211AP2813G 5211A20514G 5211AP2810Q 5251AP2460B 5421AP2812B 5901AR2351E 3H00671A 3091AP2533A 5230AP1236A 3531A10272C 5237AP2817B 3720AP2767P 4681A20055A 5230AP7093A 5991AP2867B 5991AP7334C 6600AP2059B 3545AP7224B 3790AP7080A 4995A10107C 6323A20004Y 6323AQ3226Y 6711A20096A 3871A10159A 6871AQ3263A 3087AP7233A 3H02821B 4681AP2306N 5211AP2813H 5211A20514G 5211AP2810R 5251AP2460B 5421AP2812A 5901AR2351E 3H00671A 3091AP2533A 5230AP1236A 3531A10272C 5237AP2817B 3720AP2767P 4681A20055A 5230AP7093A 5991AP2867B 5991AP7334C 6600AP2059B 3545AP7224B 3790AP7080A 4995A10107C 6323A20004Y 6323AQ3226Y 6711A20096C 3871A10159A 6871AQ3263A 3087AP7233A 3H02821B 4681AP2306N 5211AP2813H 5211A20514G 5211AP2810R 5251AP2460B 5421AP2812A 5901AR2351E 3H00671A SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 221

437212 554031 558511 552113-1 435511

A2UQ166FA0

Outdoor Unit

552112

222 Multi type Air Conditioner
546810 559010 W0CCZ 658740 668711 649950 552116 552204-1 554160-1 447910 561411 552113-2 437210 430410 552203-1 552203-2 552203-1 552203-2 552204-2 263230-1 263230-2 561410

Exploded View & Replacement Parts List

435301

A2UW146FA0

554031

437212

435512 552112

552113-1

558511

559010 W0CCZ 566000

546810

435511 668711

447910 658740 649950

435301 552116 552204-1 552204-2 554160-1

263230-1 263230-2 561410

561411 552113-2 437211 552203-1 552203-2 552203-1 552203-2 430411

Exploded View & Replacement Parts List

Service Manual 223

554031 137213-1 437212 137213-2

435512 552112

552113-1

A2UW186FA0/A3UW186FA0

224 Multi type Air Conditioner
558511 559010 W0CCZ 566000 668711 447910 658740 649950 435511 546810 263230-1 552116 552204-1 552204-2 554160-1 561411 552113-2 437211 552203-1 552203-2 552203-1 552203-2 430411 561410 263230-2

Exploded View & Replacement Parts List

435301

Exploded View & Replacement Parts List Parts List(Single compressor inverter)
Location No. 263230-1 263230-2 430410 435301 435511 437210 437212 447910 546810 552112 552113-1 552113-2 552116 552203-1 552203-2 552204-1 552204-2 554031 554160 558511 559010 561410 561411 649950 658740 668711 668713 W0CZZ Part No. Description THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY BASE ASSEMBLY,OUTDOOR GRILLE,DISCHARGE COVER ASSEMBLY,CONTROL(OUTDOOR) PANEL ASSEMBLY,FRONT(OUTDOOR) PANEL ASSEMBLY,REAR(OUTDOOR) BARRIER ASSEMBLY,OUTDOOR MOTOR ASSEMBLY,OUTDOOR TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,REVERSING VALVE,SERVICE VALVE,SERVICE HARNESS HARNESS CONDENSER ASSEMBLY,BENT COMPRESSOR SET DRIER ASSEMBLY FAN ASSEMBLY,PROPELLER COIL ASSEMBLY,REVERSING VALVE COIL ASSEMBLY,EXPANSION CONTROL BOX ASSEMBLY,OUTDOOR REACTOR PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL) CAPACITOR,DRAWING A2UW146FA2 6323A20037A 6323A20037B 3041A20066A 3530A20006G 3551A30115G 3721A20027Q 3721A20026Y 4791A30002G 4681A20170A 5211A23331A 5211A23336A 5211A23337A 5211A23335A 5220A20001K 2H02479J 6877A20050N 6877A20050P 5403A20221A 5416A90029A 5851A20003J 5901A10033A 6141AR3509L 6140A90001K 4995A21016B 5874A90003A 6871A10334A 6871A20484A 3A02157A A2UW166FA0 6323A20037A 6323A20037B 3041A20066A 3530A20006G 3551A30115G 3721A20027Q 3721A20026Y 4791A30002G 4681A20170A 5211A23331A 5211A23332A 5211A20927D 5211A23330A 5220A20001K 2H02479J 6877A20050N 6877A20050P 5403A20221A 2520UGHN2AC 5901A10033A 6141AR3509L 6140A90001K 4995A21016A 5874A90003A 6871A10225A 6871A20484A 3A02157A A2UW166FA1 6323A20037A 6323A20037B 3041A20066A 3530A20006G 3551A30115G 3721A20027Q 3721A20026Y 4791A30002G 4681A20170A 5211A23331A 5211A23336A 5211A23337A 5211A23335B 5220A20001K 2H02479J 6877A20050N 6877A20050P 5403A20221A 5416A90015A 5851A20003J 5901A10033A 6141AR3509L 6140A90001K 4995A21016C 5874A90003A 6871A10334B 6871A20484A 3A02157A SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R OPTION R

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 225

Exploded View & Replacement Parts List Outdoor Unit Parts List (Single compressor inverter)
LOCATION No. DESCRIPTION PART No. A2UW146FA0 A2UW186FA0 1A00201D 3A02284M 6323A20020F 6323A20020G 3041A20022Q 3530A20007J 3A01919B 3H03266K 3721A20005P 3H03307L 4681A20028S 5211A24019A 5211A24018A 5220A20001K 2A02479R 6141A20018K 6141A20018L 5211A20493Q 5403A10013J 5416A90008A 5851A30004A 5901A10032A 6141AR3509L 6140A90001F 4995A10101H 5874A90003A 6871A10117K 6871A20484A 2A00986D 3720AP0003F 498110019B 5220A90010A 6323A20020F 6323A20020G 3041A20022Q 3530A20007J 3A01919B 3H03266L 3721A20004L 1A00207B 3H03307L 4681A20028S 5211A30298A 5211A30297Z 5211A20927A 5220A20001K 2A00468J 6877A20050A 6877A20050B 5211A20493H 5403A20072N 5416A90015A 5851A30004A 5901A10032A 6141AR3509L 6140A90001K 3A02524F 4995A10101A 5874A90003A 6871A10117B 6871A20484A 2A00986D A3UW186FA0 1A00201D 3A02284M 6323A20020F 6323A20020G 3041A20022Q 3530A20007J 3A01919B 3H03266L 3721A20004L 1A00207B 3H03307L 4681A20028S 5211A30298A 5211A30297Z 5211A21155C 5220A20001K 2A00468J 6877A20050A 6877A20050B 6877A20050K 5211A20493R 5403A20072N 5416A90015A 5851A30004A 5901A10032A 6141AR3509L 6140A90001K 3A02524F 4995A10101J 5874A90003A 6871A10117L 6871A20484A 2A00986D SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R OPTION R R R R

137213-1 PANEL ASSEMBLY, SIDE 137213-2 PANEL ASSEMBLY, SIDE 263230-1 THERMISTOR ASSEMBLY (ROOM, OUT) 263230-3 THERMISTOR ASSEMBLY (DISCHARGE, SUCTION) 430411 BASE ASSEMBLY, WELD[OUTDOOR] 435301 GRILLE, DISCHARGE 435511 COVER ASSEMBLY, CONTROL(OUTDOOR) 435512 COVER ASSEMBLY, TOP(OUTDOOR) 437210 PANEL ASSY, FRONT SUB 435300 GRILLE, REAR 447910 BARRIER ASSEMBLY, OUTDOOR 546810 MOTOR ASSEMBLY, OUTDOOR 552112 TUBE ASSEMBLY, CONDENSER IN 552113-1 TUBE ASSEMBLY, CONDENSER OUT 552113-2 TUBE ASSEMBLY, COND OUT (SUPPORTER) 552203-1 VALVE, SERVICE (Ø9.52) 552203-2 VALVE, SERVICE (Ø6.35) 552204-1 COIL ASSEMBLY, SOLENOID (A) 552204-2 COIL ASSEMBLY, SOLENOID (B) 552204-3 COIL ASSEMBLY, SOLENOID (C) 552116 TUBE ASSEMBLY, REVERSING 554031 CONDENSER ASSEMBLY, BENT 554160 COMPRESSOR 558511 DRIER ASSEMBLY 559010 FAN ASSEMBLY, PROPELLER 561410 COIL ASSEMBLY, REVERSING VALVE 561411 COIL ASSEMBLY, EXPANSION 566000 SWITCH, PRESSURE (LOW PRESSURE) 649950 CONTROL BOX ASSEMBLY, OUTDOOR 658740 REACTOR 668711 PWB(PCB) ASSEMBLY, MAIN(OUTDOOR) 668713 PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL) W0CZZ CAPACITOR, DRAWING 437212 PANEL ASSEMBY, REAR W49810 SUPPORT ASSEMBLY 552200 VALVE, EXPANSION BODY

226 Multi type Air Conditioner

554031 137213-1 435300 137213-2 552204 552115 552113 558511

435512

A3UW246FA0/A4UW246FA0

566000

559010 649950 658740 548490

546810

263230-1

263230-2 668711 447910 561411-1 561411-2 561411 561411-3 561411-4 561410 554160-1 554160-2 552113-2 552113-1 435511

263230-3

435301

437210

552113

Exploded View & Replacement Parts List

Service Manual 227

430411

Exploded View & Replacement Parts List Parts List (A3UW246FA0, A4UW246FA0 - MPS Inverter)
Location No. 137213-1 137213-2 263230-1 263230-2 263230-3 352113 430410 435300 435301 435511 435512 437210 447910 546810 548490 552111 552113 552115 552116 552203-1 552203-2 552204 554031 554160 554161 558511 559010 561410-1 561410-2 561410-3 561410 561411-1 561411-2 561411-3 561411-4 566000 649950 658740 668711 668713 552201 W0CZZ-1 W0CZZ-2 Part No. Description PANEL ASSEMBLY, SIDE PANEL ASSEMBLY, SIDE THERMISTOR ASSEMBY (INV DISCHARGE, SUCTION) THERMISTOR ASSEMBLY (CONST DISCHARGE) THERMISTOR, ASSEMBLY (ROOM, COND OUT) TUBE, ASSEMBLY, DISCHARGE BASE ASSEMBLY, WELD GRILLE, REAR GRILLE, DISCHARGE COVER ASSEMBLY, CONTROL (OUTDOOR) COVER ASSEMBLY, TOP PANEL ASSEMBLY, FRONT SUB BARRIER ASSEMBLY, OUTDOOR MOTOR ASSEMBLY, OUTDOOR ACCUMULATOR ASSEMBLY TUBE ASSEMBLY, CAPILLARY TUBE ASSEMBLY, CONDENSER OUT TUBE ASSEMBLY, MANIFOLD TUBE ASSEMBLY, REVERSING VALVE, SERVICE (Ø9.52) VALVE, SERVICE (Ø6.35) VALVE, SOLENOID (BODY) CONDENSER ASSEMBLY, BENT COMPRESSOR (INVERTER) COMPRESSOR (CONSTANT) DRIER, ASSEMBLY FAN ASSEMBLY, PROPELLER COIL ASSEMBLY, REVERSING VALVE COIL ASSEMBLY, SOLENOID COIL ASSEMBLY, SOLENOID VALVE, EXPANSION BODY COIL ASSEMBLY EXPANSION (A) COIL ASSEMBLY EXPANSION (B) COIL ASSEMBLY EXPANSION (C) COIL ASSEMBLY EXPANSION (D) SWITCH, PRESSURE CONTROL BOX ASSEMBLY, OUTDOOR REACTOR PWB(PCB) ASSEMBLY, MAIN(OUTDOOR) PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL) VALVE, CHECK CAPACITOR, DRAWING (FAN) CAPACITOR, DRAWING (COMP) A3UW246FA0 1A00202F 3A02284R 6323A20030G 6323A20001J 6323A20020F 5211A23013A 3041AP2741H 1A00208H 3530A20007J 3A01919B 3551A30113C 1A00197C 4791A30004M 4681A20028Y 4849A22003A 5211A22009A 5211A21155B 5211A20895A 5211A20896A 5220A20001K 2A02479J 5220A90002C 5403A20070B 5416A90015A 5416A90016A 5851A30004A 5901A10032A 6871A20052D 6877A20052E 6877A20052F 6140A90001K 6877A20050C 6877A20050D 6877A20050E 3A02524F 4995A10101B 5874A90003A 6871A10117C 6871A20484A 5220A30004A 2A00986D 2H00841F A4UW246FA0 1A00202F 3A02284T 6323A20030G 6323A20001J 6323A20020F 5211A23013A 3041AP2741H 1A00208H 3530A20007J 3A01919B 3551A30113C 1A00197C 4791A30004M 4681A20028Y 4849A22003A 5211A22009A 5211A21155A 5211A20895A 5211A20896A 5220A20001K 2A02479J 5220A90002C 5403A20070B 5416A90015A 5416A90016A 5851A30004A 5901A10032A 6871A20052D 6877A20052E 6877A20052F 6140A90001K 6877A20050C 6877A20050D 6877A20050E 6877A20050L 3A02524F 4995A10101K 5874A90003A 6871A10117M 6871A20484A 5220A30004A 2A00986D 2H00841F SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

228 Multi type Air Conditioner

554031-1 137213-1 135314 137213-2 552111 552204 552115 352113

566000

A4UW306FA0

552116

435512 548490 546810-1 559010 649950 554031-2

558511

546810-2 668711 561411-1 561411-2 W0CZZ-1 W0CZZ-2 552113 552203-1 447910 561410 554160 554161 552203-2 561411-3 561411-4 435511

435301

Exploded View & Replacement Parts List

Service Manual 229
437210

658740 430410

Exploded View & Replacement Parts List Parts List (A4UW306FA0 - MPS Inverter)
Part No. Location No. 135301 137213-1 137213-2 263230-1 263230-2 263230-3 352113 430410 435300 435511 435512 437211 447910 546810-1 546810-2 548490 552111 552113 552115 552116 552201 552203-1 552203-2 552204 554031 554160 554161 558511 559010 561410 561410-1 561410-2 561410-3 561411-1 561411-2 561411-3 561411-4 566000 649950 658740 668711 668713 W0CZZ-1 W0CZZ-2 Description GRILLE,DISCHARGE PANEL ASSEMBLY,SIDE PANEL ASSEMBLY,SIDE THERMISTOR ASSEMBLY (ROOM, COND, OUT) THERMISTOR ASSEMBLY (DISCHARGE, SUCTION) THERMISTOR ASSEMBLY (DISCHARGE, CONST) TUBE ASSEMBLY, DISCHARGE SINGLE BASE ASSEMBLY, OUTDOOR GRILLE,REAR COVER ASSEMBLY,CONTROL(OUTDOOR) COVER ASSEMBLY,TOP(OUTDOOR) PANEL ASSEMBLY,FRONT(OUTDOOR) BARRIER ASSEMBLY,OUTDOOR MOTOR ASSEMBLY,OUTDOOR MOTOR ASSEMBLY, OUTDOOR ACCUMULATOR ASSEMBLY(MECH) TUBE ASSEMBLY, CAPILLARY TUBE ASSEMBLY, CONDENSER OUT TUBE ASSEMBLY, MANIFOLD TUBE ASSEMBLY,REVERSING VALVE, CHECK VALVE,SERVICE(Ø9, 52) VALVE,SERVICE (Ø6, 35) VALVE, SOLENOID (BODY) CONDENSER ASSEMBLY,BENT COMPRESSOR (INVERTER) COMPRESSOR (CONSTANT) DRIER ASSEMBLY FAN ASSEMBLY,PROPELLER VALVE, EXPANSION (BODY) COIL ASSEMBLY,REVERSING VALVE COIL ASSEMBLY SOLENOID (P/ICE) COIL ASSEMBLY SOLENOID (OIL/S) COIL ASSEMBLY,EXPANSION (A) COIL ASSEMBLY,EXPANSION (B) COIL ASSEMBLY,EXPANSION (C) COIL ASSEMBLY,EXPANSION (D) SWITCH, PRESSURE (LOW) CONTROL BOX ASSEMBLY,OUTDOOR REACTOR PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL) CAPACITOR,DRAWING (COMP) CAPACITOR,DRAWING (FAN) A4UW306FA0 3530A20006B 3721A10110A 3721A10111A 6323A20020H 6323A20020J 6323A20001K 35211A23013A 3041AP2741H 3530A10176B 3A01919B 3551A30113C 3721A10109A 4791A10019A 4681AR1392Y 4681AR1392Z 4849A22003A 5211A22010A 5211A21155A 5211A20895B 5211A20896A 5220A30004A 5220A20001K 2H02479J 5220A90002C 5403A20168B 5416A90015A 5416A90021A 5851A30004A 5901A10033A 6140A90001K 6877A20052A 6877A20052B 6877A20052C 6877A20050F 6877A20050G 6877A20050H 6877A20050J 3A02524F 4995A10101C 5874A90003A 6871A10117D 6871A20484A 2A00986X 2H00660P SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Option R R

230 Multi type Air Conditioner

435512 658740

558511

546810-1 W0CCZ-1 W0CCZ-2 669200 437212

668713

263230-1

A6UW406FA0/A6UQ406FA0
263230-2 263230-3

559010 447910 546810-1 546810-2 35211A 552116 554031-1

437210

435301

552113-1 554160 554161

352112 566000 552203-1

435511

552113 552203-2 430410

554031-2 552115-2

552113-2

237204

Exploded View & Replacement Parts List

Service Manual 231

552115-1

Exploded View & Replacement Parts List Parts List (A6UW406FA0 - MPS Inverter)
Part No. Location No. 137213 263230-1 263230-2 263230-3 35211A 352112 430410 435301 435511 435512 437210 437212 447910 546810-1 546810-2 548490 552102 552112 552113 552115-1 552115-2 552116 55211A 55211G 552201 552203-1 552203-2 552204 554031-1 554031-2 554160-1 554160-2 558511 559010 561410 561410-1 561410-2 561411 566000 649950 658740 668711 668713 669200 W0CZZ-1 W0CZZ-2 Description PANEL, SIDE THERMISTOR ASSEMBLY (ROOM, COND OUT) THERMISTOR ASSEMBLY (DISCHARGE SUCTION) THERMISTOR ASSEMBLY (DISCHARGE CONSTANT) TUBE ASSEMBLY, SUCTION (INDOOR) TUBE ASSEMBLY, COUPLING BASE ASSEMBLY, WELD GRILLE, DISCHARGE COVER ASSEMBLY, CONTROL COVER ASSEMBLY, TOP PANEL ASSEMBLY, FRONT SUB PANEL ASSEMBLY, REAR BARRIER ASSEMBLY, OUTDOOR MOTOR ASSEMBLY, OUTDOOR MOTOR ASSEMBLY, OUTDOOR ACCUMULATOR ASSEMBLY TUBE ASSEMBLY, EXPANSION TUBE ASSEMBLY, CAPILLARY TUBE ASSEMBLY, CONDENSER OUT TUBE ASSEMBL, MANIFOLD(OUTDOOR) Ø19.05 TUBE ASSEMBL, MANIFOLD(OUTDOOR) Ø9.52 TUBE ASSEMBLY, REVERSING TUBE ASSEMBLY, SUCTION INDOOR TUBE ASSEMBLY, EXPANSION VALVE, CHECK VALVE, SERVICE (Ø19, 05) VALVE, SERVICE (Ø9, 52) VALVE, SOLENOID (BODY) CONDENSER ASSEMBLY, BENT CONDENSER ASSEMBLY, BENT COMPRESSOR SET (INVERTER) COMPRESSOR SET (CONSTANT) DRIER ASSEMBLY FAN ASSEMBLY, PROPELLER VALVE, EXPANSION (BODY) COIL ASSEMBLY, REVERSING VALVE COIL ASSEMBLY, SOLENOID (BY-PASS) COIL ASSEMBLY, EXPANSION SWITCH, PRESSURE CONTROL BOX ASSEMBLY, OUTDOOR REACTOR PWB(PCB) ASSEMBLY, MAIN(OUTDOOR) PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL) RELAY CAPACITOR, DRAWING (FAN) CAPACITOR, DRAWING (COMP) A6UW406FA0 3720AP1215B 6323A20020H 6323A20020J 6323A20020K 5211A21187A 5211A10433A 3041A20047K 3530AP1225D 3A01293X 3550AP1213B 3720AP1212B 3720AP1202C 4791A20012E 4681A20028J 4681A20028Q 4849A10009A 5211A22013A 5211A10430A 5211A23015A 5211A22018A 5211A22018B 5211A21188A 5211A21187A 5211A10434A 5220A30004A 2A00499L 5220A20001E 5220A90002C 5403A20166J 5403A20166K 5416A90015A 5416A90017A 5851A20002A 5901A10032A 6140A90001H 6141AR3509A 6141A2013G 6141A30003M 3A02524F 4995A10118A 5874A90003A 6871A10117E 6871A20484A 6920AP3400A 2A00986D 2A00986A A6UQ406FA0 3720AP1215B 6323A20020H 6323A20020J 6323A20020K 5211A21187A 5211A10433A 3041A20047K 3530AP1225D 3A01293X 3550AP1213B 3720AP1212B 3720AP1202C 4791A20012E 4681A20028J 4681A20028Q 4849A10009A 5211A22013A 5211A10430A 5211A23015A 5211A22018A 5211A22018B 5211A21188A 5211A21187A 5211A10434A 5220A30004A 2A00499L 5220A20001E 5220A90002C 5403A20166J 5403A20166K 5416A90015A 5416A90017A 5851A20002A 5901A10032A 6140A90001H 6141AR3509A 6141A2013G 6141A30003M 3A02524F 4995A10118A 5874A90003A 6871A10117E 6871A20484A 6920AP3400A 2A00986D 2A00986A SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R OPTION R R R

232 Multi type Air Conditioner

Exploded View & Replacement Parts List A7UW486FA0/A8UW566FA0/A8WQ566FA0

435311 349490

137213 330870 559010

549610 546810

447910-1

552113-1 552113-2

552112-2 352112 558511 548490-1 552112-4

552112-1

447910-2 554030-2 435312 554030-4

552112-3 5211AB1 554030-1 658740 561410-2 55211G 561411 552116

554030-3

649950 435310 352114 668711 346811 554160-2 552203-1 561410-1 552203-2

548490-2

437211

430410

554160-1 552115-2 554160-2

137213

W0CCZ-1 W0CCZ-2

263230-1 263230-2 263230-3

552115-1

Service Manual 233

Exploded View & Replacement Parts List Parts List (A7UW486FA0)
Part No. Location No. 137213 263230-1 263230-2 263230-3 263230-4 330870 346811 349490 352112 352114 430410 435310 435311 435312 437211 437212 447910-1 447910-2 5211AB1 546810 548490-1 548490-2 549610 552112-1 552112-2 552112-3 552112-4 552113-1 552113-2 552115-1 552115-2 552116 55211G 552203-1 552203-2 554030-1 554030-2 554030-3 554030-4 554160-1 554160-2 558511 559010 561410-1 561410-2 561411 649950 658740 668711 W0CZZ-1 W0CZZ-2 Description PANEL ASSEMBLY,SIDE THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY DRAIN PAN ASSEMBLY MOTOR ASSEMBLY,SINGLE ORIFICE ASSEMBLY TUBE ASSEMBLY,COUPLING TUBE ASSEMBLY,DISTRIBUTOR BASE ASSEMBLY,OUTDOOR GRILLE ASSEMBLY,FRONT(OUTDOOR) GRILLE ASSEMBLY,DISCHARGE(OUTDOOR) GRILLE ASSEMBLY,REAR(OUTDOOR) PANEL ASSEMBLY,FRONT(OUTDOOR) PANEL ASSEMBLY,REAR(OUTDOOR) BARRIER ASSEMBLY,OUTDOOR BARRIER ASSEMBLY,OUTDOOR TUBE ASSEMBLY,CHECK VALVE MOTOR ASSEMBLY,OUTDOOR ACCUMULATOR ASSEMBLY(MECH) ACCUMULATOR ASSEMBLY(MECH) MOUNT ASSEMBLY,MOTOR(OUTDOOR) TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,MENIFOLD(OUTDOOR) TUBE ASSEMBLY,MENIFOLD(OUTDOOR) TUBE ASSEMBLY,REVERSING TUBE ASSEMBLY,EXPANSION VALVE,SERVICE VALVE,SERVICE CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,FIRST COMPRESSOR COMPRESSOR DRIER ASSEMBLY FAN ASSEMBLY,PROPELLER COIL ASSEMBLY,SOLENOID COIL ASSEMBLY,REVERSING VALVE COIL ASSEMBLY,EXPANSION CONTROL BOX ASSEMBLY,OUTDOOR REACTOR PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) CAPACITOR,DRAWING CAPACITOR,DRAWING A7UW486FA0 3721A10120A 6323A20020K 6323A20020L 6323A20001L 6323A20001M 3087A10023C 4681A20155A 4949A10010A 5211A10284C 5211A21190B 3041A10058B 3531A10266D 3531A20211B 3531A11004D 3721A10107B 3721A10108B 4791A10022A 4791A20035A 5211A23023A 4681A10014H 4849A10003F 4849A10041B 4961A20028A 5211A10480A 5211A10480B 5211A10480C 5211A10480D 5211A10481A 5211A10481B 5211A22018A 5211A22018B 5211A21324A 5211A21323A 5220A20001J 2A00499N 5403A21003E 5403A21003F 5403A21003G 5403A21003H 5416A90015A 5416A90021A 5851A20002A 5901A10029A 6141A20013W 6141A20024A 6141A30003P 4995A10145B 5874A90003A 6871A10117F 2A00986Y 2A00986C SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

234 Multi type Air Conditioner

Exploded View & Replacement Parts List Parts List (A8UW566FA0)
Part No. Location No. 137213 263230-1 263230-2 263230-3 263230-4 330870 346811 349490 352112 352114 430410 435310 435311 435312 437211 437212 447910-1 447910-2 5211AB1 546810 548490-1 548490-2 549610 552112-1 552112-2 552112-3 552112-4 552113-1 552113-2 552115-1 552115-2 552116 55211G 552203-1 552203-2 554030-1 554030-2 554030-3 554030-4 554160-1 554160-2 554160-3 558511 559010 561410-1 561410-2 561411 649950 658740 668711 W0CZZ-1 W0CZZ-2 W0CZZ-3 Description PANEL ASSEMBLY,SIDE THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY THERMISTOR ASSEMBLY DRAIN PAN ASSEMBLY MOTOR ASSEMBLY,SINGLE ORIFICE ASSEMBLY TUBE ASSEMBLY,COUPLING TUBE ASSEMBLY,DISTRIBUTOR BASE ASSEMBLY,OUTDOOR GRILLE ASSEMBLY,FRONT(OUTDOOR) GRILLE ASSEMBLY,DISCHARGE(OUTDOOR) GRILLE ASSEMBLY,REAR(OUTDOOR) PANEL ASSEMBLY,FRONT(OUTDOOR) PANEL ASSEMBLY,REAR(OUTDOOR) BARRIER ASSEMBLY,OUTDOOR BARRIER ASSEMBLY,OUTDOOR TUBE ASSEMBLY,CHECK VALVE MOTOR ASSEMBLY,OUTDOOR ACCUMULATOR ASSEMBLY(MECH) ACCUMULATOR ASSEMBLY(MECH) MOUNT ASSEMBLY,MOTOR(OUTDOOR) TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER IN TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,CONDENSER OUT TUBE ASSEMBLY,MENIFOLD(OUTDOOR) TUBE ASSEMBLY,MENIFOLD(OUTDOOR) TUBE ASSEMBLY,REVERSING TUBE ASSEMBLY,EXPANSION VALVE,SERVICE VALVE,SERVICE CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,FIRST COMPRESSOR COMPRESSOR COMPRESSOR DRIER ASSEMBLY FAN ASSEMBLY,PROPELLER COIL ASSEMBLY,SOLENOID COIL ASSEMBLY,REVERSING VALVE COIL ASSEMBLY,EXPANSION CONTROL BOX ASSEMBLY,OUTDOOR REACTOR PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) CAPACITOR,DRAWING CAPACITOR,DRAWING CAPACITOR,DRAWING A8UW566FA0 3721A10120A 6323A20020K 6323A20020L 6323A20001L 6323A20001M 3087A10023C 4681A20155A 4949A10010A 5211A10284C 5211A21190B 3041A10058C 3531A10266D 3531A20211B 3531A11004D 3721A10107B 3721A10108B 4791A10022A 4791A20035A 5211A23023B 4681A10014H 4849A10003F 4849A10041A 4961A20028A 5211A10480A 5211A10480B 5211A10480C 5211A10480D 5211A10481A 5211A10481B 5211A22018A 5211A22018B 5211A21324A 5211A21323A 5220A20001J 2A00499N 5403A21003E 5403A21003F 5403A21003G 5403A21003H 5416A90015A 5416A90021A 5416A90017A 5851A20002A 5901A10029A 6141A20013W 6141A20024A 6141A30003P 4995A10145A 5874A90003A 6871A10117G 2A00986Y 2A00986A 2A00986C A8UQ566FA0 3721A10120A 6323A20020K 6323A20020L 6323A20001L 6323A20001M 3087A10023C 4681A20155A 4949A10010A 5211A10284C 5211A21190B 3041A10058C 3531A10266D 3531A20211B 3531A11004D 3721A10107B 3721A10108B 4791A10022A 4791A20035A 5211A23023B 4681A10014H 4849A10003F 4849A10041A 4961A20028A 5211A10480A 5211A10480B 5211A10480C 5211A10480D 5211A10481A 5211A10481B 5211A22018A 5211A22018B 5211A21324A 5211A21323A 5220A20001J 2A00499N 5403A21003E 5403A21003F 5403A21003G 5403A21003H 5416A90015A 5416A90021A 5416A90017A 5851A20002A 5901A10029A 6141A20013W 6141A20024A 6141A30003P 4995A10145A 5874A90003A 6871A10117G 2A00986Y 2A00986A 2A00986C SVC CODE R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

Service Manual 235

June, 2005 Printed in Korea P/No.: 3828A22009C