Scenario Testing/Demonstration -Turn on system -Screen should display layout of the plant -Physically observe locations of wireless sensor devices -Run treatment -Treatment processes to be shown on mimic screens -Turn on monitoring system and sensors -Sensors should be responding and appearing data on the monitoring system as swiftly as possible -Change state of system -Change of states to be logged in database
-Layout of plant not too detailed -Screen size not to expectations -Not within range -Not at expected location -Treatment process reading not detailed -Lag/Delays between sensors and monitoring system -Unresponsive sensors
Wireless Communication with sensors and monitoring system
Records of the states and history Displays trends and trending analysis Button based control for mimic screens At fail, systems shall recover with its last known state
-Database corruption -Storage for database exceeded
-Force fail system -System should recover with last known state
-Last known state un-stable
System has numerous states hot, cold, standby, soft fail. Fail, success
Treatment areas shall be modular so when one treatment fails others will continue