Form 6 Microprocessor-Based Recloser Control
Communications
R280-90-18
Communications Point Data Base
Data 3026
For
Communications Protocol DNP3
For Use With Cooper Power Systems
Form 6 Recloser Controls
August 2012 • Supersedes 1/2003
Form 6 DNP3 Device Profile Data Dictionary
Form 6 DNP3 Map Points
August 24, 2012
v2.0
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
Date
5/30/2001
5/30/2001
1.02
1.03
1.04
1.05
5/8/2002
10/30/2002
11/20/2002
8/29/03
1.06
1.07
2.00
3/10/2004
10/28/2005
8/24/2012
Description
Initial release.
Changed wording on SGF "enable" to "block"
Made hot line tag CROBs self-resetting.
Added Binary Input 59 as "CCI:Control Circuit Interrupted"
Added CROBs 18 (Combined Trip / Close) and 19 (Sync-Check Enable)
Changed nomenclature of binary inputs and outputs.
Added TS crob definitions, updated counter & binary
input definitions match the 'DNP Tables at last compilation' file
Added TS binary input and counter definitions
Minor edits in the Class 0 - 3, Binarys tab.
Updates and re-release for ProView 5.0
Page 1
Cover Page
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
Recloser Closed
Recloser Open
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Default Event Variation
Obj 02 Var 2 Binary input with time
Class 0 - 3, Binarys
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
Ground Overcurrent Alarm
Phase Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Recloser Closed (Phase A)
Recloser Open (Phase A)
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non-Reclosing
Ground Trip Blocked
SEF Blocked
CLPU Blocked
Fast Trips Blocked
Profile Selected (Normal)
Profile Selected (Alt1)
Profile Selected (Alt2)
Profile Selected (Alt3)
Hot Line Tag
Bus Voltage Present (Phase A)
Bus Voltage Present (Phase B)
Bus Voltage Present (Phase C)
Reverse Power Flow
Battery Test in Progress
No AC Power
Battery Alarm
ci8:Alt1 (TB3:9-10)
ci9:Alt2 (TB3:11-12)
ci10:Alt3 (TB3:13-14)
ci11:Nrml (TB3:15-16)
co1:aux (TB1:11-12,13)
co2:ok (TB1:14-15)
co3:hlt (TB1:16-17)
co4:gtb (TB1:18-19)
ss1:lo (TB1:9-10)
co5:nr (TB3:17-18)
co6:alm (TB3:19-20,21)
co7:nrm (TB4:1-2)
co8:alt1 (TB4:3-4)
co9:alt2 (TB4:5-6)
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Default Event Variation
Obj 02 Var 2 Binary input with time
Class 0 - 3, Binarys (TS)
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs (Triple-Single)
Description
co10:alt3 (TB4:7-8)
co11:frq (TB4:9-10)
co12:vlt (TB4:11-12,13)
Reclose Retry Enabled
A Phase Fault Trip
B Phase Fault Trip
C Phase Fault Trip
Ground Fault Trip
SEF Trip
ci1:RTrip (TB1:3-4)
ci2:SClose (TB1:5-6)
ci3:STrip (TB1:7-8)
ci4:GTB (TB3:1-2)
ci5:NRecl (TB3:3-4)
ci6:TargR (TB3:5-6)
ci7 (TB3:7-8)
Ground Overcurrent Alarm
Phase A Overcurrent Alarm
Negative Sequence Overcurrent Alarm
Hot Line Tag On from Workbench
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted (Phase A)
Recloser Closed (Phase B)
Recloser Open (Phase B)
Control is Locked Out (Phase B)
Control Circuit Interrupted (Phase B)
Recloser Closed (Phase C)
Recloser Open (Phase C)
Control is Locked Out (Phase C)
Control Circuit Interrupted (Phase C)
Phase B Overcurrent Alarm
Phase C Overcurrent Alarm
Ganged Mode
1-3 Mode
1-1 Mode
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
Hex Index
00
01
02
03
04
04
00
01
02
03
04
04
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
Default
Event Deadband
Class
1
1
1
1
1
1
10000
10000
10000
10000
10000
10000
Page 6
Class 0 - 3, Counters
Form 6 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters (Triple-Single)
Description
Trip Counter (Phase A)
Trip Counter (Phase B)
Trip Counter (Phase C)
Trip Counter (Ground)
Trip Counter (SEF)
Total Trip Counter
Operations Counter (Phase A)
Operations Counter (Phase B)
Operations Counter (Phase C)
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
Hex Index
00
01
02
03
04
05
06
07
08
00
01
02
03
04
05
06
07
08
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
* Close Mechanism
* Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
indicates point is supervised regardless of setting
Crosshatch
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Conditioned by
Supervisory State Description
(Factory Default)
* Close Mechanism
* Trip Mechanism
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Page 10
CROB
Form 6 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status (Triple-Single)
Default Static Variation
Description
* Close Mechanism (Phase A)
* Trip Mechanism (Phase A)
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
* Trip Mechanism (Phase B)
* Trip Mechanism (Phase C)
* Close Mechanism (Phase B)
* Close Mechanism (Phase C)
* Activate Ganged Mode
* Activate 1-3 Mode
* Activate 1-1 Mode
* Trip All Phases
* Close All Phases
Not Used
Not Used
Not Used
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Crosshatch
indicates point is supervised regardless of setting
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Conditioned by
Supervisory State Description
(Factory Default)
* Close Mechanism (Phase A)
* Trip Mechanism (Phase A)
Block Reclosing
Block Ground Trip
Block SEF
Block CLPU
Block Fast Trips
* Profile - Normal
* Profile - Alt1
* Profile - Alt2
* Profile - Alt3
* Reset Targets
* Reset Demand Meters
* Reset Alarms
* Test Battery
*, *** Hot Line Tag Set
*, *** Hot Line Tag Reset
Enable Reclose Retry
Combined Trip and Close
Enable Sync Check
* Trip Mechanism (Phase B)
* Trip Mechanism (Phase C)
* Close Mechanism (Phase B)
* Close Mechanism (Phase C)
* Activate Ganged Mode
* Activate 1-3 Mode
* Activate 1-1 Mode
* Trip All Phases
* Close All Phases
Not Used
Not Used
Not Used
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Page 12
CROB (TS)
Form 6 Microprocessor-Based Recloser Control Communications DNP3 Protocol