smoke control fans

Comments

Content

smokecontrolfans

smoke control fans facilities I nuaire

testingfacilities
• Nuaire has one of the foremost testing facilities in the world. • Nuaire utilise ‘state of the art’ technology, with separate testing facilities (ducted – type C, & D and open inlet – type A) • Nuaire’s laboratories have the capability to carry out acoustic tests to BS848 part 2 and AMCA 300. • Nuaire have a long standing relationship with BISRA (Building Services Research & Information Association), who choose to utilise Nuaire’s facilities for their own independent testing. • Nuaire test all of their electrical products inhouse for EMC (Electro magnetic compatibility). • Nuaire’s team of technicians and test engineers have a wealth of knowledge gleaned from years of extensive acoustic and aerodynamic development and testing. • Nuaire can advise you on the best solution possible for your requirement. • Nuaire offer a ‘factory witness testing facility’ for your and your client.
Type ‘A’ laboratory for testing acoustic and aerodynamic performance of free inlet and discharge eg. Roof mounted fans.

Type ‘C’ and ‘D’ laboratory for testing acoustic and aerodynamic performance of duct mounted fans.

Semi Reverberant Plenum Chamber Transformation Section Airflow 90 Deg
With Turning Vanes

Conical Inlet

Delta P Differential Pressure ▲4

Static Pressure PS 3

Fan Under Test

Static Pressure PS 4

1m - 2m Diameter 315 - 800mm Diameter Test Ducts

Silencer Control Fan
Variable Pitch

Silencer

Inlet Cone

Control Office

Door into Plenum Chamber

Ducted Fan Test Rig (Plan View)

Part of Nuaire’s multi-million pound manufacturing plant

smoke control fans applications

smokecontrol
Shopping Centres & Public Buildings: Safe Escape
The main benefits of installing NuAire Smoke Control Systems are: • Safe escape for occupants • Safe entry for fire fighters • Reduced smoke damage • Reduced water damage NuAire fans provide a smoke ‘clear layer’ to allow building occupants to safely escape from a building during a fire situation.
Reservoir Screen Clear Layer Fresh Airflow Fresh Airflow Safe Means of Escape

Commercial & Industrial Buildings: Safe Escape & Protecting Goods
In addition these systems allow fire fighting services to safely enter the building, to locate the fire and maintaining a clear layer helps prevent ‘fire damage’ to stored goods or machinery.

High Temperature Fan/Cowl Combination

Pressurisation of Escape Routes
BS5588 Part 4: specifies the use of pressurisation for the means of escape. The systems ensure that stairs and corridors in mulit-storey buildings remain clear of smoke. BS5588 Part 5: specifies the use of pressurisation for fire fighting systems. In addition to providing safe means of escape, these are designed to offer safe access to fire fighters. Nuaire pressurisation run & stand by fans are specially designed to meet the requirements of these standards.
PRODUCTS PRODUCTS PRODUCTS PRODUCTS

Clear Layer

Pressurisation Run & Standby Axial

Fresh air fed in by Mechanical Fan

Vent representing Leakage Path to Atmosphere

Pressurised Lobby

Fire behind door

Shopping Centres & Car Parks: Safe Escape
Thrust Vent offers efficient daily ventilation for CO removal, smoke clearance and smoke control. The system provides active cooling of the smoke, creation of virtual smoke barriers, easy visual location of the fire for emergency services and quick, efficient extinguishing of the fire. Thrust Vent smoke control system For further details contact Nuaire on 029 2085 8200

smoke control fans I fan selection I 7.02

smoke control fans benefits

Axus High Temperature Long Cased Axial

Axus High Temperature Roof Mounted Cowl/Fan Combination

Purpose designed smoke extract unit.
Sizes - 16 Case diameters, from 315mm to 1600mm Airflow - Up to 85m3/s (306,000m3/hr) Static Pressure - Up to 1275 Pa Operating temperature - 300oC for 2 hours (4000c fan 2 hours option) Matching attenuators Installation ancillaries • Wide range The widest range of high temperature axials available. • Superb build quality Welded, heavy gauge galvanised steel construction for strength and durability. • High performance Developed to provide optimum performance for each case size. • Tested to the highest standards Air performance to BS848 (part1) 1997 and ISO5801 (Part 1) 1997. Acoustic performance to AMCA300. High temperature operation to EN12101-3 2002 • Easy selection The performance curves illustrated in this catalogue are the standard 300oC range. Performance figures for 400oC. For detailed selection and technical data contact you local representative or Nuaire’s technical department.

Purpose designed roof mounted smoke extract unit.
Cowls - Low profile, high velocity, vertical discharge Operating temperature - 300oC for 2 hour (optional 400oC for 2 hour) • Low profile, weatherproof cowl Tested in winds of 70mph and rainfall of 75mm/hr the low profile cowl provides a weatherproof, aesthetic installation. • Temperature/Time options 300oC for 2 hours as standard (optional 400oC for 2 hours, contact Nuaire for details). • Superb build quality Robust heavy gauge aluminium alloy (sizes 560 & 710) or painted galvanised steel (sizes 1000 & 1250) construction for strength and durability. Tested to the highest standards • Easy selection The cowl pressure drop is indicated on each fan performance graph to provide quick, accurate information.

fan selection
step 1
Where is the fan to be located?

fan selection axus contra-rotating axus run & standby

I 7.03 I 7.05 I 7.07

essure (Pa

12

50 0 40 0 30 0 20 0

11A

step 2
11B

3

4

5

10 0

Which fan matches the required duty? Volume & flow rate? Pressure drop?

Fan Static Pr

high temperature axial with vertical cowl option high temperature squif

I 7.09

step 3
What ancillaries do you need? Do I need attenuators, cowls, etc?

I 7.29

step 4
Write your project specification?

smoke control fans I fan selection I 7.04

smoke control fans axus contra-rotating I technical information

axuscontra-rotating
Axus High Temperature Contra-Rotating Axial Flow Fans:
• 13 Case diameters, 315 - 1250mm. • Airflow - Up to 42m3/s. • Static pressure - Up to 2500 Pa • Operating temperature - 300oC for 2 hours/4OOoC for 2 hours. • High performance - Developed to provide optimum performance for each case size.

• Tested to the highest standardsAir performance to BS848 (part 1) 1997 and IS05801 (Part 1) 1997. Acoustic performance AMCA300. High temperature operation EN 12101-3 2002

• General Features
• 13 Case diameters, 315 - 1250mm • Superb build quality - Welded, heavy gauge galvanised steel construction for strength and durability. • High temperature performance Units are suitable for smoke reservoir and non smoke reservoir applcations. Units are dual purpose for day to day plus ‘one off’ emergency use. • Flexible solution - Units can be installed at any angle. • Matching Attenuators & ancillaries • Advanced construction Avoids the distortion associated with traditional methods of manufacturing and ensures consistency of performance.

• High performance - Developed to provide optimum performance for each case size. • Available options: AXUS units suitable for two speed operation (full and half speed). AXUS units available with access doors suitable for cleaning and observation. • Ancillaries available - AV mounts, flexible connectors, mounting Brackets Matching Flanges, Inlet Cones, Guard, backdraught damper. • Warranty Axus Contra-Rotating have a 3 year warranty. Note: An ambient option (550C) utilising standard motors are also available.

Code Descriptions
AXC 100 A - 4 1 3 A 7 T | | | | | | | | | 1 2 3 45 6 7 8 9
Axus Contra-rotating axial Case diameter in cm Impeller specification reference Motor speed in poles Impeller blade angle reference Electrical supply in phase 3=400v, 50Hz three phase 7. Impeller material A = Aluminium 8 Operating Temperature 7 = 3000C for 2 hours 8 = 4000C for 2 hours 9 Other options (combinations possible) T = Two speed (full and half) Z = Access Door 1. 2. 3. 4. 5. 6.

Attenuators Standard and Long options available

Anti Vibration Mounts

Mounting Brackets

Flexible Connectors

Matching Flanges

Inlet Cones

Damper

Arc Cowl

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Performance
m3/hr 0 4000 35000 72000 108000 144000 180000

3500

C

3000

3000C for 2 hours Fan Static Pressure (Pa)
2500
B Flange

Ambient (550C)
D

AIRFLOW

2000

4000C for 2 hours
1500

E ctrs

E ctrs

F= No. of G dia holes equi-spaced on H p.c.d.

1000

500

Unit shown supported on optional mounting brackets and A.V. mounts J ctrs

0 0 10 20 Air Volume Flow Rate 30 m3/s 40 50

K foot

Dimensions and Weights
Code Frame A B C D E F AXC31 63-71 315 400 700 210 620 8 AXC35 63-90 350 430 700 240 620 8 AXC40 63-100 400 490 880 270 810 8 AXC45 63-112 450 540 880 300 800 8 AXC50 63-112 500 608 880 340 800 12 AXC50 132 500 608 1200 340 1120 12 AXC56 71-100 560 670 880 370 800 12 AXC56 132 560 670 1200 370 1120 12 AXC63 63-112 630 740 880 430 800 12 AXC63 132-180 630 740 1200 430 1120 12 AXC71 80-112 710 814 880 470 800 16 AXC71 132 710 814 1400 470 1320 16 AXC80 80-112 800 910 880 540 800 16 AXC80 132-160 800 910 1400 540 1320 16 AXC90 90-180 900 1016 1480 600 1400 16 AXC100 90-180 1000 1128 1480 670 1370 16 AXC100 200 1000 1128 1700 670 1590 16 AXC112 100-160 1120 1240 1460 750 1350 20 AXC112 180-200 1120 1240 1730 750 1620 20 AXC112 225-250 1120 1240 2020 750 1910 20 AXC125 100-200 1250 1365 1730 830 1620 20 AXC125 225-280 1250 1365 2020 830 1910 20 For unit weights and pressure drops above 2500 pascals, please call our technical team on 029 2085 8200 G 12 12 12 12 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15 H 355 395 450 500 560 560 620 620 690 690 770 770 860 860 970 1070 1070 1190 1190 1190 1320 1320 J 220 250 290 330 380 380 420 420 500 500 540 540 590 590 670 770 770 870 870 870 920 920 K 270 300 340 380 430 430 470 470 550 550 600 600 650 650 750 850 850 950 950 950 1000 1000

Download specification from www.nuairegroup.com/specifications smoke control fans I axus contra-rotating I 7.06

smoke control fans I axus contra-rotating technical information

A

smoke control fans axus run & standby I technical information

axusrun&standby
Axus High Temperature Run & Standby Axial Fan
• Airflow - Up to 73m3/s. • Static pressure - Up to 1200 Pa. • Operating temperature - 300oC for 2 hours/400oC for 2 hours. • High performance - Developed to provide optimum performance for each case size. • Tested to the highest standards, Air performance to BS848 (partl) 1997 and IS05801 (Part 1) 1997. • Acoustic performance AMCA300 • High temperature operation EN12101-3 2002

• General Features
• 16 Case diameters, 315 - 1600mm • High performance - Developed to provide optimum performance for each case size. Available optionsAXUS units suitable for two speed operation (full and half speed). AXUS units available with access doors suitable for cleaning and observation. • Matching Attenuators and ancillaries • Superb build quality - Welded, heavy gauge galvanised steel construction for strength and durability. • High temperature performance Units are suitable for smoke reservoir and non smoke reservoir applcations. Units are dual purpose for day to day plus ‘one off’ emergency use. • Advanced construction Avoids the distortion associated with traditional methods of manufacturing and ensures consistency of performance. • Ancillaries available - AV mounts, Flexible connectors, Mounting Brackets, Matching Flanges, Inlet Cones, Guard, Backdraft Damper and attenuators. • Warranty Axus Run & Standby have a 3 year warranty. Note: An ambient option (550C) utilising standard motors are also available.

Code Descriptions
AXT | 1
1. 2. 3. 4. 5. 6.

100 A - 4 1 3 A 7 T | | | | | | | | 2 3 45 6 7 8 9

Axus Run & Standby axial Case diameter in cm Impeller specification reference Motor speed in poles Impeller blade angle reference Electrical supply in phase 3=400v, 50Hz three phase 7. Impeller material A = Aluminium 8 Operating Temperature 7 = 3000C for 2 hours 8 = 4000C for 2 hours 9 Other options (combinations possible) T = Two speed (full and half) Z = Access Door

Attenuators Standard and Long options available

Anti Vibration Mounts

Mounting Brackets

Flexible Connectors

Matching Flanges

Inlet Cones

Damper

Arc Cowl

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Performance
m3/hr 0 1300 36000 72000 108000 144000 180000 216000 252000 288000

1200

1100

1000
C

900

Ambient (55oC)
B Flange

800

700

D

AIRFLOW

600
E ctrs E ctrs

500
F= No. of G dia holes equi-spaced on H p.c.d.

400

400oC for 2 hours

300

300oC for 2 hours
200
Unit shown supported on optional mounting brackets and A.V. mounts J ctrs

100

0

10

20

30

40

50

60

70

80

K foot

Air Volume Flow Rate (m3/s)

Dimensions and Weights
Code Frame A B C D E F AXT31 63-71 315 400 700 210 620 8 AXT35 63-90 350 430 700 240 620 8 AXT40 63-100 400 490 880 270 810 8 AXT45 63-112 450 540 880 300 800 8 AXT50 63-112 500 608 880 340 800 12 AXT50 132 500 608 1200 340 1120 12 AXT56 71-100 560 670 880 370 800 12 AXT56 132 560 670 1200 370 1120 12 AXT63 63-112 630 740 880 430 800 12 AXT63 132-180 630 740 1200 430 1120 12 AXT71 80-112 710 814 880 470 800 16 AXT71 132 710 814 1400 470 1320 16 AXT80 80-112 800 910 880 540 800 16 AXT80 132-160 800 910 1400 540 1320 16 AXT90 90-180 900 1016 1480 600 1400 16 AXT100 90-180 1000 1128 1480 670 1370 16 AXT100 200 1000 1128 1700 670 1590 16 AXT112 100-160 1120 1240 1460 750 1350 20 AXT112 180-200 1120 1240 1730 750 1620 20 AXT112 225-250 1120 1240 2020 750 1910 20 AXT125 100-200 1250 1365 1730 830 1620 20 AXT125 225-2880 1250 1365 2020 830 1910 20 For unit weights and pressure drops above 2500 pascals, please call our technical team on 029 2085 8200 1800 & 2000 are available with standard motors (ambient 550c) Unit sizes 1400 - 1600mm call Nuaire for details. G 12 12 12 12 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15 H 355 395 450 500 560 560 620 620 690 690 770 770 860 860 970 1070 1070 1190 1190 1190 1320 1320 J 220 250 290 330 380 380 420 420 500 500 540 540 590 590 670 770 770 870 870 870 920 920 K 270 300 340 380 430 430 470 470 550 550 600 600 650 650 750 850 850 950 950 950 1000 1000

Download specification from www.nuairegroup.com/specifications smoke control fans I axus run & standby I 7.08

smoke control fans I axus run & standby technical information

Fan Static Pressure (Pa)

A

smoke control fans axial I technical information

high temperature

axialfans
• Tried & tested
Nuaire’s high temperature fans have been tested in accordance with the latest legislation and testing procedures. High temperature fans have been tested to EN12101-3 (2002) 3000C for 2 hours or 4000C for 2 hours.

• High temperature performance
Units are suitable for smoke reservoir and non smoke reservoir applcations. Units are dual purpose for day to day plus ‘one off’ emergency use.

• Wide range
The widest range of hgh temperature axials available. A fan to match every application ensures maximum efficiency and saving costly energy.

• Heavy gauge galvanised steel construction
Ensuring strength, durability, protection from damage during installation and corrosion resistant for a long life.

• Manufactured by using advanced production methods
ensures high quality, free from defect fans, to give superior performance consistently at lower costs.

• Comprehensive ancillaries
including a range of attenuators, and mounting ancillaries all pre-selected for the individual fan to ensure a perfect match and eliminate any on-site fitting problems. • Warranty High Temperature Axial fans have a 3 year warranty.

• Tested to the highest standards
Air performance to BS848 (part 1)1997 and ISO5801(part1)1997 with acoustic performance to AMCA300. All carried out at our own test facilities to ensure the most accurate performance figures and noise data is provided, constantly monitored to give you up to date information you can rely on.

Code Descriptions
AX 100 A - 4 1 3 A 7 T | | | | | | | | | 1 2 3 45 6 7 8 9
Axus long cased axial Case diameter in cm Impeller specification reference Motor speed in poles Impeller blade angle reference Electrical supply in phase 3=400/415v, 50Hz three phase 7. Impeller material A = Aluminium 8 Operating Temperature 7 = 3000C for 2 hours 8 = 4000C for 2 hours 9 Other options (combinations possible) T = Two speed (full and half) T6 = Two speed (full & two thirds) (4/6 pole only) 1. 2. 3. 4. 5. 6.

• Fan options
As well contra-rotating & run /standby series, other options available are 4000c for 2 hours & two speed.

AXUS Circular Axial

AXUS Run & Standby

AXUS Contra-Rotating

Arc Cowl

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial
Below is an indication of the overall duty range, a selection of which is covered in this brochure. Please contact Nuaire Technical on (029) 2085 8200 for any duty outside the range indicated.

AXUS - Axial flow fans for smoke control (3000C for 2 Hour)
1500
ISO 5801 1997 AMCA 300

1400 1300 1200 1100 1000

V
Type D Air Density 1.2 kg/m3

Fan Static Pressure (Pa)

2 POLE

900 800 700 4 POLE 600 500 400 300 8 POLE 200 100 6 POLE

0

10

20

30

40

50

60

70

80

90

Air Volume Flow Rate (m3/s)

AXUS - Axial flow fans for smoke control (4000C for 2 Hour)
1100
ISO 5801 1997 AMCA 300

1000

V
Type D Air Density 1.2 kg/m3

900

800

Fan Static Pressure (Pa)

700

600

500 2 POLE 400 4 POLE

300 6 POLE 200 8 POLE 100

0

10

20

30

40

50

60

Air Volume Flow Rate (m3/s)

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.10

smoke control fans I axial fans technical information

smoke control fans axial I technical information

Axus Long Cased Axial - 315mm ø (3000c for 2 hours)
315mm Ø - 4 Pole/1440 RPM
120 400
ISO 5801 1997 AMCA 300

315mm Ø - 2 Pole/2800 RPM

ISO 5801 1997 AMCA 300

V
100
Type D Air Density 1.2 kg/m3

350

V
Type D Air Density 1.2 kg/m3

300

80 250

12

60

200

1

2

3 4 5 6
100 150

11 10 9 14 15 13 16

40

psF - Static Pressure (Pa)

20

8

psF - Static Pressure (Pa)

7

50

0

0.2

0.4

0.6

0.8

0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 315 Ø - 4pole/1440 rpm 1 AX31M-413A7 20 1415 21 NAV38 80 2 AX31X-413A7 25 1415 21 NAV38 80 3 AX31X-423A7 30 1415 21 NAV38 80 4 AX31X-443A7 35 1415 21 NAV38 80 5 AX31X-463A7 40 1415 21 NAV38 80 6 AX31F-443A7 40 1415 21 NAV38 80 7 AX31F-453A7 45 1415 21 NAV38 80 8 AX31B-453A7 45 1415 21 NAV38 80 315 Ø - 2pole/2800rpm 9 AX31M-213A7 20 2875 23 NAV38 80 10 AX31B-213A7 25 2875 23 NAV38 80 11 AX31X-223A7 30 2875 23 NAV38 80 12 AX31F-223A7 30 2875 23 NAV38 80 13 AX31X-243A7 35 2875 23 NAV38 80 14 AX31F-233A7 35 2875 23 NAV38 80 15 AX31F-243A7 40 2875 23 NAV38 80 16 AX31B-243A7 40 2875 23 NAV38 80 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 85 77 79 77 82 70 71 71 81 72 85 79 82 79 82 76 72 72 72 70 71 75 72 71 97 78 86 78 89 77 79 80 65 63 64 63 64 63 64 63 80 75 80 80 79 78 79 78 61 61 61 62 63 65 65 61 78 75 77 76 79 77 79 78 58 58 58 58 59 61 61 59 74 72 73 73 75 74 74 73 50 48 49 48 50 53 55 55 70 69 68 70 71 71 69 68 Breakout dBA 8k @ 3m 42 42 43 41 44 46 48 50 63 63 64 65 64 65 65 64 42 40 40 39 41 41 40 39 57 5 54 52 54 52 53 50

Mounting Brackets (pair) Code: CMB31 Matching Flange (single) Code: CMF31 Flexible Connector (single) Code: CFC31 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA31S, CA31L, CA31SP, CA31LP Guard Code: CGD31 Inlet Cone Code: CIC31 Backdraught Damper Code: CBD31

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. .

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial - 350mm ø (3000c for 2 hours)
350mm Ø - 4 Pole/1440 RPM
140
ISO 5801 1997 AMCA 300

350mm Ø - 2 Pole/2800 RPM
500
ISO 5801 1997 AMCA 300

V
125
Type D Air Density 1.2 kg/m3

450

V
Type D Air Density 1.2 kg/m3

400

100

350

300 80

250

60 200

1
40

2

3 5 4 6 7
150

8

9

10

11

12 13 14

100

20

50

0

0.20

0.40

0.60

0.80

1.00

1.20

0

0.50

1.00

1.50

2.00

2.5

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 350 Ø - 4pole/1440 rpm 1 AX35M-413A7 20 1415 22 NAV38 80 2 AX35F-413A7 25 1415 22 NAV38 80 3 AX35D-413A7 25 1415 22 NAV38 80 4 AX35X-423A7 30 1415 22 NAV38 80 5 AX35F-433A7 35 1415 22 NAV38 80 6 AX35F-443A7 40 1415 22 NAV38 80 7 AX35F-453A7 45 1415 22 NAV38 80 350 Ø - 2pole/2800rpm 8 AX35M-213A7 20 2875 23 NAV38 80 9 AX35X-213A7 25 2875 26 NAV38 80 10 AX35X-223A7 30 2875 26 NAV38 80 11 AX35X-243A7 35 2875 26 NAV38 80 12 AX35M-273A7 40 2875 23 NAV38 80 13 AX35F-243A7 40 2875 22 NAV38 90 14 AX35F-253A7 45 2875 22 NAV38 90 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 0.55 0.55 0.55 0.55 0.55 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.3 2.3 2.3 2.3 2.3 3.1 3.1 7.2 7.2 7.2 7.2 7.2 7.2 7.2 17.9 17.9 17.9 17.9 17.9 25.7 25.7

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 81 75 69 89 69 73 74 81 84 85 87 86 90 90 69 72 67 77 78 75 78 88 89 96 88 101 85 85 66 66 66 66 64 64 65 79 81 81 83 82 86 86 64 65 62 63 64 63 65 81 80 81 84 82 84 84 61 63 62 59 62 59 61 76 76 77 79 79 81 81 56 57 55 50 56 55 57 72 74 74 75 74 76 76 Breakout dBA 8k @ 3m 50 49 48 43 49 50 53 67 66 66 68 69 71 71 44 41 42 48 44 42 45 55 57 60 58 65 60 60

Mounting Brackets (pair) Code: CMB35 Matching Flange (single) Code: CMF35 Flexible Connector (single) Code: CFC35 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA35S, CA35L, CA35SP, CA35LP Guard Code: CGD35 Inlet Cone Code: CIC35 Backdraught Damper Code: CBD35

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field.

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.12

smoke control fans I axial fans technical information

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

smoke control fans axial I technical information

Axus Long Cased Axial - 400mm ø (3000c for 2 hours)
400mm Ø - 4 Pole/1440 RPM
200
ISO 5801 1997 AMCA 300

400mm Ø - 2 Pole/2800 RPM
700
ISO 5801 1997 AMCA 300

180

V
Type D Air Density 1.2 kg/m3

V
600
Type D Air Density 1.2 kg/m3

160

140

500

120 400

100

1 2

80

3 4

300

7

8 9
Roof cowl resistance

60

5 6

200

10 11

13 12

psF - Static Pressure (Pa)

40

20

0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

psF - Static Pressure (Pa)

100

0

0.5

1.0

1.5

2.0

2.5

3.0

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 400 Ø - 4pole/1440 rpm 1 AX40D-413A7 25 1415 26 NAV38 80 2 AX40I-413A7 25 1415 30 NAV38 80 3 AX40I-423A7 30 1415 30 NAV38 80 4 AX40I-433A7 35 1415 30 NAV38 80 5 AX40I-443A7 40 1415 30 NAV38 80 6 AX40I-453A7 45 1415 30 NAV38 80 400 Ø - 2pole/2800rpm 7 AX40C-213A7 25 2875 31 NAV38 80 8 AX40M-213A7 20 2875 31 NAV38 80 9 AX40F-213A7 25 2875 38 NAV39 90 10 AX40I-223A7 30 2875 39 NAV39 90 11 AX40I-233A7 35 2875 39 NAV39 90 12 AX40I-243A7 40 2875 41 NAV39 100 13 AX40I-253A7 45 2875 44 NAV39 100 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 0.55 0.55 0.55 0.55 0.75 0.75 1.5 1.8 2.2 3 3 1.5 1.5 1.5 1.5 1.5 1.5 1.65 1.65 3.1 3.6 4.4 5.8 5.8 7.2 7.2 7.2 7.2 7.2 7.2 11.2 11.2 25.7 31.3 39.6 53 53

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 71 72 69 72 76 76 81 81 78 82 85 88 92 81 77 76 79 77 77 90 89 82 81 83 86 87 69 73 70 70 70 71 83 83 86 89 90 92 90 66 69 66 67 68 69 80 84 83 84 84 85 90 65 67 64 63 64 64 75 79 81 80 80 81 85 59 63 60 58 60 60 71 75 78 78 75 76 80 Breakout dBA 8k @ 3m 51 54 53 53 55 55 69 72 74 75 70 72 76 49 45 44 45 45 46 59 57 58 61 62 63 63

Mounting Brackets (pair) Code: CMB40 Matching Flange (single) Code: CMF40 Flexible Connector (single) Code: CFC40 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA40S, CA40L, CA40SP, CA40LP Guard Code: CGD40 Inlet Cone Code: CIC40 Backdraught Damper Code: CBD40

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field.

Roof Cowl Code: ARC56

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial - 450mm ø (3000c for 2 hours)
450mm Ø - 4 Pole/1440 RPM
250
ISO 5801 1997 AMCA 300

450mm Ø - 2 Pole/2800 RPM
1000
ISO 5801 1997 AMCA 300

V
Type D Air Density 1.2 kg/m3

900

V
Type D Air Density 1.2 kg/m3

200

800

700

150

600

500

100

400

3 2 1

4

5 6 7 8 9

10
300

11 12 13 14 15 16 17
Roof cowl resistance

50

200

100

0

0.25

0.5

0.75

1.0

1.25

1.5

1.75

2.0

2.25

2.5

0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 450 Ø - 4pole/1400 rpm 1 AX45S-413A7 20 1415 34 NAV38 80 2 AX45P-413A7 20 1415 32 NAV38 80 3 AX45S-433A7 30 1415 34 NAV38 80 4 AX45S-453A7 35 1415 34 NAV38 80 5 AX45S-473A7 40 1415 34 NAV38 80 6 AX45S-483A7 45 1415 37 NAV39 80 7 AX45AA-453A7 37.5 1415 36 NAV39 80 8 AX45P-473A7 40 1415 36 NAV39 80 9 AX45P-483A7 45 1415 36 NAV39 80 450 Ø - 2pole/2800rpm 10 AX45P-213A7 20 2875 42 NAV39 90 11 AX45AA-213A7 32.5 2875 54 NAV41 100 12 AX45S-253A7 35 2910 55 NAV41 112 13 AX45P-243A7 32.5 2910 53 NAV41 112 14 AX45P-253A7 35 2910 53 NAV41 112 15 AX45AA-253A7 37.5 2910 56 NAV41 112 16 AX45F-243A7 45 2910 51 NAV41 112 17 AX45F-253A7 45 2910 51 NAV41 112 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 0.55 0.55 0.55 0.75 0.55 0.75 0.75 1.8 3 4 4 4 4 4 4 1.5 1.5 1.5 1.5 1.5 2 1.5 2 2 3.6 5.8 7.8 7.8 7.8 7.8 7.8 7.8 7.2 7.2 7.2 7.2 7.2 9.8 7.2 9.8 9.8 31 53 66 66 66 66 66 66

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 82 79 83 83 85 83 82 79 80 85 90 91 88 89 92 85 87 81 79 82 81 86 84 79 82 81 86 87 91 86 87 89 82 84 80 78 78 80 80 80 75 73 73 91 91 95 91 91 92 93 92 75 74 75 78 78 77 73 72 71 91 89 94 90 91 90 89 90 71 71 70 72 71 69 68 67 66 87 85 90 87 85 85 85 86 66 66 64 68 65 65 61 62 60 83 81 86 82 81 80 81 82 Breakout dBA 8k @ 3m 58 58 57 61 59 59 55 57 55 81 79 82 79 78 74 78 79 52 50 51 53 54 55 49 49 49 64 64 68 65 65 66 65 66

Mounting Brackets (pair) Code: CMB45 Matching Flange (single) Code: CMF45 Flexible Connector (single) Code: CFC45 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA45S, CA45L, CA45SP, CA45LP Guard Code: CGD45 Inlet Cone Code: CIC45 Backdraught Damper Code: CBD45

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC56

smoke control fans I axial fans I 7.14

smoke control fans I axial fans technical information

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

smoke control fans axial I technical information

Axus Long Cased Axial - 500mm ø (3000c for 2 hours)
500mm Ø - 4 Pole/1440 RPM
250
ISO 5801 1997 AMCA 300

500mm Ø - 2 Pole/2800 RPM
1200
ISO 5801 1997 AMCA 300

V
Type D Air Density 1.2 kg/m3

V
1000
Type D Air Density 1.2 kg/m3

200

800 150

600

100 400

8 1

9

10

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

50

3 2 4 5 6

11 12 13 14 Roof cowl
resistance

7

200

0

0.5

1.0

1.5

2.0

2.5

3.0

0

1.0

2.0

3.0

4.0

5.0

6.0

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 500 Ø - 4pole/1440 rpm 1 AX50P-413A7 20 1415 33 NAV38 80 2 AX50S-433A7 30 1415 35 NAV38 80 3 AX50S-443A7 32.5 1415 40 NAV39 80 4 AX50S-453A7 35 1415 40 NAV39 80 5 AX50S-473A7 40 1430 44 NAV39 90 6 AX50P-473A7 40 1430 42 NAV39 90 7 AX50P-483A7 45 1430 42 NAV39 90 500 Ø - 2pole/2800rpm 8 AX50P-213A7 20 2875 53 NAV41 100 9 AX50P-223A7 25 2910 58 NAV41 112 10 AX50S-243A7 32.5 2930 77 NAV43 132 11 AX50S-253A7 35 2930 77 NAV43 132 12 AX50S-273A7 40 2935 88 NAV43 132 13 AX50P-263A7 40 2930 75 NAV43 132 14 AX50P-283A7 45 2935 85 NAV43 132 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 0.75 0.75 1.1 1.1 1.1 3 4 7.5 7.5 9 7.5 9 1.5 1.5 2 2 2.5 2.5 2.5 5.8 7.8 14 14 16.6 14 16.6 7.2 7.2 9.8 9.8 14.3 14.3 14.3 53 66 118 118 146 118 146

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 79 80 81 81 85 79 79 87 86 93 93 95 91 93 80 82 87 84 84 80 80 87 90 94 91 93 90 91 81 79 79 80 78 77 77 93 96 96 99 97 98 99 77 77 78 78 77 74 74 95 95 94 95 97 94 95 73 73 73 73 70 70 69 92 92 89 91 92 92 91 68 68 68 68 65 64 63 87 86 85 87 88 85 86 Breakout dBA 8k @ 3m 60 62 61 61 60 60 59 85 81 81 85 86 82 85 53 52 53 53 53 52 52 67 68 69 71 71 70 71

Mounting Brackets (pair) Code: CMB50 Matching Flange (single) Code: CMF50 Flexible Connector (single) Code: CFC50 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA50S, CA50L, CA50SP, CA50LP Guard Code: CGD50 Inlet Cone Code: CIC50 Backdraught Damper Code: CBD50

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC71

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial - 560mm ø (3000c for 2 hours)
560mm Ø - 4 Pole/1440 RPM
300
ISO 5801 1997 AMCA 300

560mm Ø - 2 Pole/2800 RPM
1000
ISO 5801 1997 AMCA 300

V
Type D Air Density 1.2 kg/m3

900

V
Type D Air Density 1.2 kg/m3

250 800

700 200 600

150

600

400 100 300

9

10 11

12

5

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

2
50

3

4

6

7

8

200 Roof cowl resistance

1

200

0

1.0

2.0

3.0

4.0

5.0

0

1

2

3

4

5

6

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 560 Ø - 4pole/1440 rpm 1 AX56S-413A7 20 1415 41 NAV39 80 2 AX56S-423A7 25 1415 41 NAV39 80 3 AX56S-433A7 30 1430 43 NAV39 90 4 AX56S-453A7 35 1435 47 NAV40 90 5 AX56S-473A7 40 1435 47 NAV40 90 6 AX56S-483A7 45 1435 49 NAV40 90 7 AX56AA-473A7 45 1435 49 NAV40 90 8 AX56X-483A7 50 1435 44 NAV40 90 560 Ø - 2pole/2800rpm 9 AX56D-213A7 25 2875 42 NAV39 90 10 AX56F-213A7 25 2875 49 NAV40 100 11 AX56S-223A7 25 2930 94 NAV44 132 12 AX56S-233A7 30 2935 102 NAV44 132 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.75 0.75 1.1 1.5 1.5 1.8 1.8 1.5 1.8 3 7.5 9 2 2 2.5 3.4 3.4 4 4 3.4 3.6 5.8 14 16.6 9.8 9.8 14.3 19.7 19.7 24.4 24.4 19.7 31.3 53 118 146

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 74 75 78 80 85 83 83 87 83 86 90 97 72 73 76 79 84 87 82 79 79 82 89 93 80 81 82 83 84 83 82 80 88 89 97 99 79 80 81 80 80 81 79 77 91 89 96 97 77 78 78 76 76 77 74 71 89 90 94 92 74 75 75 72 72 74 70 66 87 88 91 89 Breakout dBA 8k @ 3m 73 74 73 68 67 68 66 63 86 87 89 84 55 55 56 56 55 55 53 52 66 65 70 70

Mounting Brackets (pair) Code: CMB56 Matching Flange (single) Code: CMF56 Flexible Connector (single) Code: CFC56 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA56S, CA56L, CA56SP, CA56LP Guard Code: CGD56 Inlet Cone Code: CIC56 Backdraught Damper Code: CBD56

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC71

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.16

smoke control fans I axial fans technical information

smoke control fans axial I technical information

Axus Long Cased Axial - 630mm ø (3000c for 2 hours)
630mm Ø - 4 Pole/1440 RPM
450
ISO 5801 1997 AMCA 300

630mm Ø - 2 Pole/2800 RPM
1800
ISO 5801 1997 AMCA 300

400

V
Type D Air Density 1.2 kg/m3

1600

V
Type D Air Density 1.2 kg/m3

350

1400

300

1200

250

1000

200

Roof cowl resistance

800

10 9
600

150

11 12

psF - Static Pressure (Pa)

100

2 1

3

4

5

6 7

8

50

psF - Static Pressure (Pa)

400

Roof cowl resistance

200

0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

0

1

2

3

4

5

6

7

8

9

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 630 Ø - 4pole/1440 rpm 1 AX63S-413A7 20 1430 50 NAV40 90 2 AX63S-423A7 25 1430 50 NAV40 90 3 AX63AD-423A7 30 1435 56 NAV41 100 4 AX63AD-443A7 35 1435 59 NAV41 100 5 AX63AD-473A7 45 1435 61 NAV41 100 6 AX63AD-483A7 50 1455 65 NAV41 112 7 AX63AA-483A7 50 1455 63 NAV41 112 630 Ø - 2pole/2800rpm 8 AX63P-213A7 20 2915 81 NAV43 132 9 AX63P-223A7 25 2935 88 NAV43 132 10 AX63AD-213A7 25 2935 123 NAV46 160 11 AX63AD-223A7 30 2940 141 NAV46 160 12 AX63AD-243A7 35 2938 156 NAV47 180 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 1.1 1.1 1.8 2.2 3 4 4 5.5 9 11 15 22 2.5 2.5 4 4.7 6.4 8.2 8.2 10.3 16.6 19.9 27 39.9 14.3 14.3 24.4 30.1 41 *57 *57 100 146 183 265 319

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 85 82 85 85 87 86 83 86 94 92 95 97 85 82 87 90 87 87 87 89 93 92 94 97 83 83 86 85 84 86 85 97 102 100 105 107 81 80 80 81 81 82 82 99 101 99 98 100 78 77 76 78 77 78 77 98 98 96 95 95 76 75 72 76 73 74 71 92 93 92 91 92 Breakout dBA 8k @ 3m 68 67 64 68 67 68 67 90 90 93 91 91 56 55 57 58 58 59 58 72 74 73 75 77

Mounting Brackets (pair) Code: CMB63 Matching Flange (single) Code: CMF63 Flexible Connector (single) Code: CFC63 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA63S, CA63L, CA63SP, CA63LP Guard Code: CGD63 Inlet Cone Code: CIC63 Backdraught Damper Code: CBD63

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC71

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial - 710mm ø (3000c for 2 hours)
710mm Ø - 6 Pole/960 RPM
200
ISO 5801 1997 AMCA 300

710mm Ø - 4 Pole/1400 RPM
450
ISO 5801 1997 AMCA 300

180

V
Type D Air Density 1.2 kg/m3

400

V
Type D Air Density 1.2 kg/m3

160 350

140 300 120 250 100 200 80

15
150

14 10 11 12 13

Roof cowl resistance

60

1

2

3

4

5

6 7

9

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

40

100

8
50

20

0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

0

1

2

3

4

5

6

7

8

9

10

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 710 Ø - 6pole/960 rpm 1 AX71O-613A7 20 920 43 NAV39 90 2 AX71P-623A7 25 920 45 NAV39 90 3 AX71AA-623A7 30 920 47 NAV40 90 4 AX71AD-643A7 35 920 57 NAV41 90 5 AX71AD-663A7 40 920 61 NAV41 100 6 AX71AD-673A7 45 920 61 NAV41 100 7 AX71AD-683A7 30 960 66 NAV42 112 710 Ø - 4pole/1400 rpm 8 AX71O-413A7 20 1415 44 NAV39 80 9 AX71O-423A7 25 1430 45 NAV39 90 10 AX71P-423A7 25 1435 48 NAV40 100 11 AX71AD-423A7 30 1435 63 NAV41 100 12 AX71AA-463A7 40 1455 64 NAV41 112 13 AX71AD-463A7 40 1455 97 NAV44 132 14 AX71AD-473A7 45 1455 97 NAV44 132 15 AX71AD-483A7 50 1455 124 NAV46 132 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 0.55 1.1 1.5 1.5 2.2 0.75 1.1 1.8 3 4 5.5 5.5 7.5 1.75 1.75 1.75 3.0 4 4 5.2 2 2.5 4 6.4 8.2 10.8 10.8 14.5 8.1 8.1 8.1 13.3 19.2 19.2 31.7 9.8 14.3 24.4 41 57 81 81 107

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 78 82 83 79 81 79 79 83 81 100 83 83 86 85 86 79 76 78 79 79 78 81 82 81 95 92 95 91 96 94 76 74 74 77 77 78 79 84 80 90 88 89 86 87 90 76 74 74 73 73 73 75 85 80 86 86 86 83 85 87 72 72 73 70 70 70 72 81 79 81 83 83 80 80 84 66 67 65 64 65 65 67 78 77 79 81 81 75 75 80 Breakout dBA 8k @ 3m 57 58 56 58 60 61 61 72 70 72 72 73 69 70 76 49 49 49 50 50 51 52 57 56 61 60 63 60 62 64

Mounting Brackets (pair) Code: CMB71 Matching Flange (single) Code: CMF71 Flexible Connector (single) Code: CFC71 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA71S, CA71L, CA71SP, CA71LP Guard Code: CGD71 Inlet Cone Code: CIC71 Backdraught Damper Code: CBD71

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC100

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.18

smoke control fans I axial fans technical information

smoke control fans axial I technical information

Axus Long Cased Axial - 800mm ø (3000c for 2 hours)
800mm Ø - 6 Pole/960 RPM
250
ISO 5801 1997 AMCA 300

800mm Ø - 4 Pole/1440 RPM
500
ISO 5801 1997 AMCA 300

V
Type D Air Density 1.2 kg/m3

450

V
Type D Air Density 1.2 kg/m3

200

400

350

150

300

250

100

200

Roof cowl resistance

10 1 2 3 4 5 6 7
150

11

12

9 8

13 14 15

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

50

100

50

0

1

2

3

4

5

6

7

8

0

2

4

6

8

10

12

14

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 800 Ø - 6pole/960 rpm 1 AX80O-623A7 25 920 57 NAV41 90 2 AX80P-623A7 25 920 59 NAV41 90 3 AX80AG-623A7 30 920 87 NAV43 100 4 AX80AG-643A7 35 960 100 NAV44 112 5 AX80AG-663A7 40 960 100 NAV44 112 6 AX80AG-673A7 45 945 125 NAV46 132 7 AX80AG-683A7 50 945 135 NAV46 132 800 Ø - 4pole/1440 rpm 8 AX80O-413A7 20 1430 57 NAV41 90 9 AX80P-423A7 25 1435 63 NAV41 100 10 AX80AA-423A7 30 1435 69 NAV42 100 11 AX80AG-443A7 35 1455 134 NAV46 132 12 AX80AG-463A7 40 1455 149 NAV46 160 13 AX80AG-473A7 45 1455 149 NAV46 160 14 AX80AG-483A7 50 1456 159 NAV47 160 15 AX80AD-483A7 50 1455 145 NAV46 160 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 0.55 0.55 1.5 2.2 2.2 3 4 1.1 2.2 3 7.5 11 11 15 11 1.75 1.75 4 5.2 5.2 7 9.3 2.5 4.7 6.4 14.5 21.2 21.2 28.8 21.2 8.1 8.1 19.2 31.7 31.7 39.2 52 14.3 30.1 41 107 163 163 202 163

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 80 82 82 80 81 84 83 83 80 82 87 89 91 93 88 76 75 85 86 84 86 88 84 86 88 89 94 93 93 96 76 77 83 81 81 83 84 86 87 88 92 94 93 96 92 77 76 79 79 78 79 81 91 87 86 90 89 89 91 89 75 75 78 78 76 76 78 88 85 83 87 86 85 89 87 71 71 72 74 72 71 74 82 84 82 85 84 82 85 84 Breakout dBA 8k @ 3m 60 60 63 66 64 66 68 76 78 74 79 78 77 82 81 50 50 56 55 55 58 57 62 61 61 64 64 66 68 65

Mounting Brackets (pair) Code: CMB80 Matching Flange (single) Code: CMF80 Flexible Connector (single) Code: CFC80 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA80S, CA80L, CA80SP, CA80LP Guard Code: CGD80 Inlet Cone Code: CIC80 Backdraught Damper Code: CBD80

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC100

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial - 900mm ø (300 0c for 2 hours)
900mm Ø - 6 Pole/960 RPM
300
ISO 5801 1997 AMCA 300

900mm Ø - 4 Pole/1440 RPM
600

V
Type D Air Density 1.2 kg/m3

ISO 5801 1997 AMCA 300

V
500
Type D Air Density 1.2 kg/m3

250

200

400

150

300

1 2 3
100 Roof cowl resistance

6 7
200

8

9

10

4

5

11 resistance

Roof cowl

50

100

0

1

2

3

4

5

6

7

8

9

10

11

12

0

2

4

6

8

10

12

14

16

18

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 900 Ø - 6pole/960 rpm 1 AX90AA-623A7 30 920 102 NAV44 100 2 AX90AG-643A7 35 945 144 NAV46 132 3 AX90AG-663A7 40 945 144 NAV46 132 4 AX90AG-673A7 45 950 149 NAV46 132 5 AX90AG-683A7 50 970 174 NAV47 160 900 Ø - 4pole/1440 rpm 6 AX90AA-423A7 30 1455 120 NAV45 132 7 AX90AG-423A7 30 1455 163 NAV47 160 8 AX90AG-443A7 35 1456 173 NAV47 160 9 AX90AG-463A7 40 1456 187 NAV47 180 10 AX90AG-473A7 45 1456 203 NAV47 180 11 AX90AG-483A7 50 1450 256 NAV48 200 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 1.5 4 4 5.5 7.5 5.5 11 15 18.5 22 30 4 9.3 9.3 12.7 16.1 10.8 21.2 28.8 35.2 41.7 56.3 19.2 52 52 72 76 81 163 202 268 329 372

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 85 83 84 88 87 85 90 90 92 94 97 82 90 88 90 92 92 94 93 97 96 97 80 85 84 87 88 92 96 96 97 97 99 79 83 81 83 85 90 92 93 93 93 95 79 82 80 79 82 86 89 90 90 89 92 74 78 75 75 78 85 89 89 88 85 88 Breakout dBA 8k @ 3m 61 69 68 69 72 78 81 82 82 81 85 54 60 58 62 61 71 69 69 69 70 71

Mounting Brackets (pair) Code: CMB90 Matching Flange (single) Code: CMF90 Flexible Connector (single) Code: CFC90 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA90S, CA90L, CA90SP, CA90LP Guard Code: CGD90 Inlet Cone Code: CIC90 Backdraught Damper Code: CBD90

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC125

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.20

smoke control fans I axial fans technical information

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

smoke control fans axial I technical information

Axus Long Cased Axial - 1000mm ø (300 0c for 2 hours)
1000mm Ø - 6 Pole/960 RPM
350
ISO 5801 1997 AMCA 300

1000mm Ø - 4 Pole/1440 RPM
900
ISO 5801 1997 AMCA 300

V
300
Type D Air Density 1.2 kg/m3

800

V
Type D Air Density 1.2 kg/m3

700 250 600

200 500

150

Roof cowl resistance

400

9 8
300 100

10

11 12 13

Roof cowl resistance

7

1

2

3 5 6

psF - Static Pressure (Pa)

50

psF - Static Pressure (Pa)

4

200

100

0

2

4

6

8

10

12

14

16

0

5

10

15

20

25

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 1000 Ø - 6pole/960 rpm 1 AX100AD-613A7 25 960 115 NAV45 112 2 AX100AD-623A7 30 945 127 NAV46 132 3 AX100CX-623A7 30 950 161 NAV47 132 4 AX100CX-643A7 35 970 190 NAV47 160 5 AX100CX-663A7 40 970 214 NAV47 160 6 AX100CX-673A7 45 970 214 NAV47 160 1000 Ø - 4pole/1440 rpm 7 AX100AD-413A7 25 1455 103 NAV44 132 8 AX100AD-423A7 25 1455 129 NAV46 160 9 AX100CX-413A7 30 1455 179 NAV47 160 10 AX100CX-423A7 35 1456 187 NAV47 160 11 AX100CX-443A7 35 1456 221 NAV47 180 12 AX100CX-463A7 40 1460 319 NAV49 200 13 AX100CX-473A7 45 1468 359 NAV49 225 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 2.2 3 5.5 7.5 11 11 5.5 11 11 15 22 30 37 5.2 7 12.7 16.1 23.3 23.3 10.8 21.2 21.2 28.8 41.7 56 69 31.7 39.2 72 76 107 107 81 163 163 202 329 372 433

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 83 93 100 94 95 100 84 96 97 102 100 101 103 89 88 94 89 90 91 97 98 96 98 100 101 101 94 95 89 85 87 86 94 103 97 97 98 100 100 93 95 82 80 82 83 100 103 93 94 95 97 98 85 89 77 76 78 79 96 98 89 90 91 93 95 81 83 74 77 79 78 91 92 88 88 90 92 95 Breakout dBA 8k @ 3m 67 73 67 71 74 75 86 87 81 83 87 89 93 64 66 63 60 61 62 71 74 69 70 71 73 73

Mounting Brackets (pair) Code: CMB100 Matching Flange (single) Code: CMF100 Flexible Connector (single) Code: CFC100 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA100S, CA100L, CA100SP, CA100LP Guard Code: CGD100 Inlet Cone Code: CIC100 Backdraught Damper Code: CBD100

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC125

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axus Long Cased Axial - 1120mm ø (300 0c for 2 hours)
1120mm Ø - 6 Pole/960 RPM
500
ISO 5801 1997 AMCA 300

1120mm Ø - 4 Pole/1440 RPM
1200
ISO 5801 1997 AMCA 300

450

V
Type D Air Density 1.2 kg/m3

V
Type D Air Density 1.2 kg/m3

1000 400

350 800 300

250 Roof cowl resistance 200

600

Roof cowl resistance

400 150

4 1 2 3

5

6

7

8

9

10

11

12

100

200

50

0

5

10

15

20

25

0

5

10

15

20

25

30

35

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 1120 Ø - 6pole/960 rpm 1 AX112CW-613A7 25 945 196 NAV47 132 2 AX112CX-613A7 25 950 212 NAV47 132 3 AX112CX-623A7 30 970 228 NAV47 160 4 AX112CX-643A7 35 970 252 NAV48 160 5 AX112CX-663A7 40 970 252 NAV48 160 6 AX112CX-673A7 45 970 293 NAV48 180 1120 Ø - 4pole/1440 rpm 7 AX112CW-413A7 25 1455 222 NAV47 160 8 AX112CX-413A7 25 1455 233 NAV47 160 9 AX112CX-423A7 30 1455 270 NAV48 180 10 AX112CX-443A7 35 1460 323 NAV49 200 11 AX112CX-463A7 40 1470 369 NAV49 225 12 AX112CX-473A7 45 1480 531 NAV51 250 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 3 5.5 7.5 11 11 15 11 15 22 30 37 55 7 12.7 16.1 23.3 23.3 30.1 21.2 28.8 41.7 56.3 69 101 43 72 76 107 107 205 163 202 329 372 433 707

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 91 94 98 99 101 104 95 98 102 103 105 108 95 93 94 96 98 100 101 99 100 102 104 106 94 88 89 91 94 95 105 99 100 102 105 106 95 85 86 87 89 91 104 94 95 96 98 100 88 81 83 85 87 89 98 92 94 95 98 100 83 80 80 83 86 88 92 88 89 92 95 97 Breakout dBA 8k @ 3m 74 82 79 79 83 86 85 93 90 90 94 97 69 67 68 69 72 73 77 75 76 77 80 81

Mounting Brackets (pair) Code: CMB112 Matching Flange (single) Code: CMF112 Flexible Connector (single) Code: CFC112 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA112S, CA112L, CA112SP , CA112LP Guard Code: CGD112 Inlet Cone Code: CIC112 Backdraught Damper Code: CBD112

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC125

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.22

smoke control fans I axial fans technical information

psF - Static Pressure (Pa)

psF - Static Pressure (Pa)

smoke control fans axial I technical information

Axus Long Cased Axial - 1250mm ø (300 0c for 2 hours)
1250mm Ø - 6 Pole/960 RPM
600
ISO 5801 1997 AMCA 300

1250mm Ø - 4 Pole/1440 RPM
1400

V
Type D Air Density 1.2 kg/m3

ISO 5801 1997 AMCA 300

V
1200
Type D Air Density 1.2 kg/m3

500

1000 400 Roof cowl resistance

800 300 Roof cowl resistance 600

200

1

2

3

4 5 6

8
400

9

10 11 12

7

psF - Static Pressure (Pa)

100

psF - Static Pressure (Pa)

200

0

5

10

15

20

25

30

35

0

5

10

15

20

25

30

35

40

45

50

qv - Air volume flow (m3/s)

qv - Air volume flow (m3/s)

Note: Curves above are indicative of the range, a more comprehensive selection is available, contact Nuaire Technical (029) 2085 8200

General
Motor Curve Unit Blade Speed Unit A.V. frame No Code Angle RPM kg Set size 1250 Ø - 6pole/960 rpm 1 AX125CW-613A7 25 945 245 NAV48 132 2 AX125CX-613A7 25 970 257 NAV48 160 3 AX125CX-623A7 30 970 281 NAV48 160 4 AX125CX-643A7 35 970 311 NAV48 180 5 AX125CX-663A7 40 970 347 NAV49 200 6 AX125CX-673A7 45 970 377 NAV49 200 1250 Ø - 4pole/1440 rpm 7 AX125CW-413A7 25 1460 245 NAV48 160 8 AX125CX-413A7 25 1460 289 NAV48 180 9 AX125CX-423A7 30 1460 353 NAV49 200 10 AX125CX-443A7 35 1470 423 NAV50 225 11 AX125CX-463A7 40 1480 619 NAV53 250 12 AX125CX-473A7 45 1480 724 NAV54 280 All start currents are for DOL starting unless otherwise indicated
0

Electrical/Motor
3 Phase (400v) Motor flc sc kW amps amps 4 7.5 11 15 18.5 22 15 22 30 45 55 75 9.3 16.1 23.3 30.1 37 43.6 28.8 41.7 56 83 101 137 52 76 107 205 237 262 202 329 372 525 707 986

Noise/Sound
In-duct sound power levels dB re 1pW Inlet Octave band mid frequency Hz 125 250 500 1k 2k 4k 95 95 99 100 102 105 99 99 103 104 106 109 99 96 97 99 101 103 105 102 103 105 107 109 100 91 92 94 97 98 109 100 101 103 106 107 99 88 89 90 92 94 108 97 98 99 101 103 94 84 86 88 90 92 102 93 95 96 99 101 87 83 83 86 89 91 96 91 92 95 98 100 Breakout dBA 8k @ 3m 80 85 82 82 86 89 89 94 91 91 95 98 73 70 71 72 75 76 81 78 79 80 83 84

Mounting Brackets (pair) Code: CMB125 Matching Flange (single) Code: CMF125 Flexible Connector (single) Code: CFC125 Anti-Vibration Mounts (for fan only) Codes: See table

Attenuator (standard, long & podded options) Code: CA125S, CA125L, CA125SP, CA125LP Guard Code: CGD125 Inlet Cone Code: CIC125 Backdraught Damper Code: CBD125

Notes relating to the table The electrical and sound information in the table is nominal. Breakout dBA @ 3m is spherical, free field. Start currents (sc.) are DOL for all motor sizes.

Roof Cowl Code: ARC125

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Dimensions and Weights
C F= No. of G dia holes equi-spaced on H p.c.d.

D

AIRFLOW Unit shown supported on optional mounting brackets and A.V. mounts E ctrs Optional AV mounts J ctrs K foot

Code AX31 AX35 AX40 AX45 AX50 AX56 AX63 AX71 AX80 AX90 AX100 AX112

AX125 Please

Frame A 80 315 90 350 90-100 400 90-112 450 132 450 90-112 500 132 500 90-100 560 132 560 90-112 630 132-180 630 90-112 710 132 710 90-112 800 132-160 800 112-180 900 112-180 1000 200 1000 132-160 1120 180-200 1120 225-250 1120 132-200 1250 225-280 1250 call Nuaire on (029) 2085 8200 if

B C 400 350 430 350 490 440 540 440 540 600 608 440 608 600 670 440 670 600 740 440 740 600 814 440 814 700 910 440 910 700 1016 740 1128 740 1128 850 1240 730 1240 865 1240 1010 1365 865 1365 1010 you require further details

D 210 240 270 300 300 340 340 370 370 430 430 470 470 540 540 600 670 750 750 750 830 830

E 270 270 370 360 520 360 520 360 520 360 520 360 620 360 620 660 630 740 620 755 900 755 900

F 8 8 8 8 8 12 12 12 12 12 12 16 16 16 16 16 16 16 20 20 20 20 20

G 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 15 15 15 15 15 15 15 15

H 355 395 450 500 500 560 560 620 620 690 690 770 770 860 860 970 1070 1070 1190 1190 1190 1320 1320

J 220 250 290 330 330 380 380 420 420 500 500 540 540 590 590 670 770 770 870 870 870 920 920

K 270 300 340 380 380 430 430 470 470 550 550 600 600 650 650 750 850 850 950 950 950 1000 1000

Max. Weight kg 23 26 44 65 88 104 209 124 142 203 324 551

729

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.24

smoke control fans I axial fans technical information

B Flange

A

smoke control fans axial I ancillaries

ancillaries
Attenuators
Attenuators shall be rigidly constructed from galvanised steel, internally lined with sound absorbing material not less than 100mm thick retained by galvanised steel perforated sheet. Attenuator e ‘ nd faces’ shall be drilled and tapped to match the flange details of the associated fan. Attenuator s ‘ ound absorbing material’ shall be chemically inert, non combustible, non-hygroscopic and vermin resistant. Attenuator shall be tested in accordance with BS4718 : 1971 ASTME 477. All attenuators shall be suitable for internal and external use at any installed angle. Standard - Typical code: CA100S. Long - Typical code: CA100L
Dimensions (mm) Weight (kg) Unit Code A B C Code Standard CA31 315 515 315 CA35 355 555 355 CA40 400 600 400 CA45 450 650 450 CA50 500 700 500 CA56 560 760 560 CA63 630 830 630 CA71 710 910 710 CA80 800 1000 800 CA90 900 1100 900 CA100 1000 1200 1000 CA112 1120 1320 1120 CA125 1250 1450 1250 For Further attenuation please refer to Axial Section
A B dia dia

C Length

'E' No. of holes tapped 'F' equi-spaced on 'G' P .C.D.

Airflow

C Long 630 710 800 900 1000 1120 1260 1420 1600 1800 2000 2240 2500

D 8 8 8 8 12 12 12 16 16 16 16 20 20

E M8 M8 M10 M10 M10 M10 M10 M10 M10 M12 M12 M12 M12

F 355 395 450 500 560 620 690 770 860 970 1070 1190 1320

Standard No Pod 8 11 16 20 23 25 30 34 73 92 111 143 188

Long No Pod 15 21 30 38 42 47 56 63 133 166 203 261 343

C/L fan

Mounting Brackets
Manufactured from heavy gauge galvanised steel mounting brackets are supplied in pairs. See table 1 for dimensions and weights. Typical code: CMB100 (100 = fan diameter in cm)
E F base fixing centres

C

Inlet Cone (single)
Manufactured in heavy gauge galvanised steel with a single bolted flange. See table 1 for dimensions and weights. Low loss inlet cone 0.38 Typical code: CIC100 (100 = fan diameter in cm)
D

Flexible Connector
Circular without flanges. Flexible connectors are suitable for operation at 400oC for 2 hours and are resistant to chemicals, ozone, oil and grease. The connector is airtight, waterproof and tested to BS476 Part 7. Flexible connector is suitable for 400oC and 2 hours Temperature/Time. Clamping bands included. Typical code: CFCH100 (100 = fan diameter in cm)
To match fan diameter

B

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Vertical Discharge Cowl
Dimensions (mm) Code A B C ARC56 845 570 535 ARC71 1100 770 760 ARC100 1295 1000 880 ARC125 1795 1300 1160 For further assistance, please contact Nuaire Technical on (029) 2085 Fans and Cowls are supplied seperately D 786 1045 1234 1738 8200 Max Weight 93.0kg 146.0kg 364.0kg 615.0kg

A sq

B

FLOW

C A sq

D sq Inside Skirt

Curb Dimensions (3000/4000 units)
Code ARC56 ARC71 ARC100 ARC125 Dimensions (mm) A B 600 75 800 100 1000 100 1500 100 C 675 875 1100 1600 D 746 1016 1198 1700
CONCRETE ROOF

Wood capping (optional 15mm overhang)

D x D maximum B Flashing can be extended over curb or to underside of timber

150 min

A x A minimum dim. Inside roof opening

Note: Wooden capping to be hardwood or treated softwood.

Builders Upstand DECKING ROOF 150 min

D x D maximum

Prefabricated Curb

Purlin Trimmer

AxA C&C inside trimmer angles

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.26

smoke control fans I axial fans technical information

smoke control fans axial I technical information

Wiring
2 Speed 3 phase Dual Wound Motors (D.O.L. starting both speeds)
L1 L2 L3
1U 1V 1W 2U 2V 2W

2 Speed 3 phase PAP/PAM Wound Motors (D.O.L. starting both speeds)
Fan unit

Single Speed 3 Phase (Below 4kW)

400V 3 phase 50Hz supply

1U 1V

L1 L2

L3

L1
1W

1U 1V 1W 2U

L2 L3

L1 L2 L3

2U 2V

Link (if no control is used ) L1 L2 400V 3 phase L3 50Hz supply

1U 1V 1W 2U 2V 2W

2W 2V 2W

400V 3 phase 50Hz supply

Low speed

High speed

NOTE: If a two speed starter is used it must have TWO contactors Individual wiring diagrams are included with each unit.

Low speed

High speed

NOTE: If a two speed starter is used it must have THREE contactors Individual wiring diagrams are included with each unit.

3 phase for Star/Delta Starting (4kW and above)

3 Phase input Matched NuAire Inverter Speed Control
Matched NuAire Inverter Speed Control 3 Phase input Connections
to motor L1 L/L2 N/L3 PE/ W V U

Note: For D.O.L. (Direct On Line) operation or Inverter type Speed Control wire in DELTA
U1 V1 W1 W2
DELTA L1 - U1 - W2 L2 - V1 - U2 L3 - W1 - V2

STAR L1 - U1 L2 - V1 L3 - W1 Link W2, U2, V2

L1 L2
400V 3 phase 50Hz supply

L3
Motor 3 phase

400V 3 phase 50Hz supply

U2 V2

3 Phase only INVERTER SPEED CONTRO

L

Note: individual wiring instructions are included with all units

Notes: Motors should be fitted with PTC Termistors. Refer to Inverter installation sheet fot instructions on connection and programming . Total length of motor leads should not exceed 50 metres. If a screened motor cable is used, maximum length should be 25 metres. Consult out Technical Department if you wish to use longer leads. Inverters are configured to suit specific fans and control applications as described on the Customer Order free of charge.

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Axial Fans
Consultants Specification
System specification - Smoke extract
The ventilation fan Unit shall be configured and arranged as detailed on the drawings and in accordance with the schedule of equipment and shall be of the High Temperature AXUS axial flow fan as manufactured by Nuaire. The units shall be manufactured heavy gauge Aluzinc corrosion resistant steel to BS EN10142 1991. The case shall be fitted with an external terminal box to IP55 The fan impeller and motor shall be direct drive with EFF2 high efficiency motors to BS5000 as standard and shall be foot mounted TENV type with IP55 enclosures and class H insulation in accordance with BS4999 part 20 (EFF1 motors are optional). They shall have sealed for life ball bearings. Motors shall be pre-wired to an external electrical terminal box through weatherproof flexible conduit to IP55. The units shall be suitable for operation in ambient temperatures up to 60°C and a one off operation of 300°C for 2 hours to class F300/120 minutes or 400°C for 2 hours to class F400/120 minutes. The unit shall be certified to EN12101-3. The unit has been independently tested for high temperature operation by BSRIA and certified by BSI. The unit is suitable for operating in smoke reservoir and non smoke reservoir applications. A two speed version of the unit to be provided where specified and controlled in accordance with the specification and manufacturers recommendations. The unit shall be supplied with all necessary ancillaries as recommended by the manufacturer and in accordance with the equipment schedule. The contractor shall allow for all necessary ductwork transformations to and from the fan unit and any associated components in accordance with the manufacturers recommendations, DW 144 and general good practice. The impeller blades shall be of special aero-foil section giving excellent performance and low noise characteristic manufactured from cast aluminium alloy. All units shall be suitable for internal and external operation and can be installed any angle. The units will be provided complete with matching flanges, flexible connections, anti vibration mounts and all other necessary components to complete the installation and shall be in accordance with the manufacturer’s specification. The unit and ancillaries shall be supplied with a 3 years manufacturer’s warranty The unit shall be of the High Temperature AXUS type as manufactured by Nuaire Ltd.

Download specification from www.nuairegroup.com/specifications smoke control fans I axial fans I 7.28

smoke control fans I axial fans technical information

smoke control fans squif I features

high temperature

squif
• Quiet operation
One of the quietest solutions for motor unit out of airstream’ applications. ‘

• High temperature operation
400 degrees for 2 hours on standard motors, reducing cost and lead times.

• Easy maintenance
‘ ut of air stream’ allows for quick and easy O access ensures lower maintenance costs.

• Ideal for high resistances
High pressure development suitable for ducted systems.

• Flexible solution
Can be mounted internally, externally, vertically or horizontally.

• Fan to suit all applications
2-speed motors available for day to day use and smoke extract.

• Safety tested
Fans are tested to comply with EN12101-3 2002.

• High temperature application
Capable of running continuously at 900C, ideal for kitchen canopy applications with a one off 4000C for 2 hours.

• Warranty
High temperature Squif has a 3 year warranty. Note: Suitable for Non-Smoke Reservoir applications.

Splitter Attenuator

AV Mounts

Flexible Connectors

Feet (As Standard)

Fan Guard

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Performance
1600
ISO 5801 1997 AMCA 300

Casing

V

Type D Air Density 1.2 kg/m3

1200

6

800
5 4

400
2 1

3

0 0 1 2 3 4 5 6 7

Air Volume Flow Rate (m3/s)

800
ISO 5801 1997 AMCA 300

V

Fan Static Pressure (Pa)

Type D Air Density 1.2 kg/m3

600
10

400
8 7

9

200

0 0 1 2 3
3

4

5

6

Air Volume Flow Rate (m /s)

Code Descriptions
SQF | 1
1. 2. 3. 4.

4 | 2

1 - 3 | | 3 4

Squif range Pole (4 or 6) Curve No. Phase (1 or 3)

Download specification from www.nuairegroup.com/specifications smoke control fans I squif I 7.30

smoke control fans I squif technical information

Fan Static Pressure (Pa)

smoke control fans squif I technical information

Performance
Electrical and Sound - Extract units
Motor Power (kW) 0.37 0.37 0.75 0.75 1.1 1.1 2.2 4 7.5 0.75 1.1 2.2 4 flc (amps) 1.1 2.8 2 5.4 2.5 7 4.8 8.3 15.2 2.1 3 5.9 9.4 sc (amps) 5.2 11.2 9.0 21 12 35 12 45 108 8.82 13.2 28.9 63 sc ★/▲ 15 36 20.4 O I O I O Data Type I O I O I O I O I O I O I O Sound Power Levels (dB re 10 -12 W) Octave band mid frequency (Hz) 125 250 500 1k 2k 4k 90 79 70 70 70 91 74 68 74 75 70 92 82 77 74 76 93 78 74 78 80 77 95 83 79 77 78 96 79 77 82 83 79 93 89 82 77 80 87 86 87 81 82 82 99 87 85 85 84 100 83 82 89 89 84 103 92 86 86 85 92 90 91 89 87 87 89 84 75 70 73 83 81 80 74 75 75 96 83 78 76 75 97 78 76 80 79 75 100 87 79 76 76 101 82 77 80 80 78 103 91 82 79 77 104 86 80 83 82 78 dBA 8k 69 64 75 69 78 73 80 68 83 83 86 81 73 61 74 74 77 75 77 76 @ 3m 62 67 71 71 81 83 64 72 73 74 50 53 56 58 62 63 47 56 59 62 Curve Code Phase 1 SQF 41-3 3 SQF 41-1 1 2 SQF 42-3 3 SQF 42-1 1 3 SQF 43-3 3 SQF 43-1 1 4 SQF 44 3 5 6 7 8 9 10 SQF 45 SQF 46 SQF 61 SQF 62 SQF 63 SQF 64 3 3 3 3 3 3 RPM 1450 1410 1450 1370 1450 1420 1450 1450 1450 960 960 960 960

The electrical and sound information in the table is nominal. Breakout dBA@3m is spherical, free field. Start currents (sc) are DOL. * Motor electrical supply, 1=1 phase (230V, 50Hz) 3=3phase (400V, 50Hz) I = induct inlet O = induct outlet
H

Quick Selection Guide
Fan unit SQF41-3 SQF41-1 SQF42-3 SQF42-1 SQF43-3 SQF43-1 SQF44 SQF45 SQF46 SQF61 SQF62 SQF63 SQF64 Standard silencers SQFS1S SQFS1S SQFS2S SQFS2S SQFS3S SQFS3S SQFS4S SQFS4S SQFS5S SQFS5S SQFS6S SQFS7S SQFS8S Long Flexible silencers Connectors SQFS1L SQFF1 SQFS1L SQFF1 SQFS2L SQFF2 SQFS2L SQFF2 SQFS3L SQFF3 SQFS3L SQFF3 SQFS4L SQFF4 SQFS4L SQFF5 SQFS5L SQFF6 SQFS5L SQFF4 SQFS6L SQFF5 SQFS7L SQFF6 SQFS8L SQFF7 Fan Guards SQFGD1 SQFGD1 SQFGD2 SQFGD2 SQFGD3 SQFGD3 SQFGD4 SQFGD5 SQFGD6 SQFGD4 SQFGD5 SQFGD6 SQFGD7 AV Mounts NAV2 NAV2 NAV2 NAV2 NAV2 NAV2 NAV5 NAV5 NAV3 NAV3 NAV4 NAV4 NAV6
C inside
FLOW

G

D ctrs

E ctrs
FLOW

View A

B inside

A

View B
G H

M
FLOW

C inside

E ctrs
FLOW

16 flange holes 11mm dia (2 planes equi-spaced) F

Dimensions and Weights
UNIT SIZE SQF 41-3 SQF 41-1 SQF 42-3 SQF 42-1 SQF 43-3 SQF 43-1 SQF 44 SQF 61 SQF 61 SQF 45 SQF 62 SQF 62 SQF 46 SQF 63 SQF 64 A 634 634 692 692 750 750 820 820 820 901 901 901 994 994 1114 B 500 500 700 700 750 750 800 800 800 900 900 900 1000 1000 1100 C 500 500 600 600 650 650 700 700 700 800 800 800 900 900 1000 D 532 532 730 730 780 780 830 830 830 930 930 930 1030 1030 1130 E 532 532 630 630 680 680 730 730 730 830 830 830 930 930 1030 F 26.5 26.5 32 32 32 32 32 32 32 32 32 32 32 32 32

B inside D ctrs

A

View B

View A
Weight (kg) 52 52 60 60 70 70 100 100 100 150 150 150 255 255 315

G 273 273 382 382 412 412 440 440 440 490 490 490 546 546 600

H 227 227 318 318 338 338 360 360 360 410 410 410 454 454 500

M 193 193 215 215 231 231 290 290 290 290 290 290 387 387 387

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Silencers
Squif Long Silencers MatchingAttenuatorAirflow Dynamic Attenuation Dimensions & Weights Unit Code m3/s 125 250 500 1k 2k 4k 8k A B C E F G Weight Kg Z SQF 41-3 SQFS1L 0-1.1 -8 -12 -32 -42 -33 -32 -18 1200 560 560 532 532 11 38 36.8 SQF 41-1 SQFS1L 0-1.1 -8 -12 -32 -42 -33 -32 -18 1200 560 560 532 532 11 38 36.8 SQF 42-3 SQFS2L 0-1.6 -8 -12 -32 -42 -33 -32 -18 1200 760 660 630 730 11 43 30.5 SQF 42-1 SQFS2L 0-1.6 -8 -12 -32 -42 -33 -32 -18 1200 760 660 630 730 11 43 30.5 SQF 43-3 SQFS3L 0-2.2 -8 -12 -32 -42 -33 -32 -18 1200 810 710 680 780 11 46 30.5 SQF 43-1 SQFS3L 0-2.2 -8 -12 -32 -42 -33 -32 -18 1200 810 710 680 780 11 46 30.5 SQF 44 SQFS4L 0-3.1 -8 -12 -32 -42 -33 -32 -18 1200 860 760 730 830 11 60 10.9 SQF 61 SQFS4L 0-1.9 -8 -12 -32 -42 -33 -32 -18 1200 860 760 730 830 11 60 10.9 SQF 45 SQFS5L 0-4.3 -8 -12 -32 -42 -33 -32 -18 1200 980 880 830 930 12.5 91 5.47 SQF 62 SQFS5L 0-2.7 -8 -12 -32 -42 -33 -32 -18 1200 980 880 830 930 12.5 91 5.47 SQF 46 SQFS6L 0-6.5 -8 -12 -32 -42 -33 -32 -18 1200 1080 980 930 1030 12.5 98 5.47 SQF 63 SQFS7L 0-4.2 -8 -12 -32 -42 -33 -32 -18 1200 1080 980 930 1030 12.5 116 1.54 SQF 64 SQFS8L 0-6 -8 -12 -32 -42 -33 -32 -18 1200 1180 1080 1030 1130 12.5 122 1.54 Squif Short Silencers SQF 41-3 SQFS1S 0-1.1 -4 -8 -18 -24 -19 -16 -11 900 560 560 532 532 11 15 36.8 SQF 41-1 SQFS1S 0-1.1 -4 -8 -18 -24 -19 -16 -11 900 560 560 532 532 11 15 36.8 SQF 42-3 SQFS2S 0-1.6 -4 -8 -18 -24 -19 -16 -11 900 760 660 630 730 11 29 30.5 SQF 42-1 SQFS2S 0-1.6 -4 -8 -18 -24 -19 -16 -11 900 760 660 630 730 11 29 30.5 SQF 43-3 SQFS3S 0-2.2 -4 -8 -18 -24 -19 -16 -11 900 810 710 680 780 11 32 30.5 SQF 43-1 SQFS3S 0-2.2 -4 -8 -18 -24 -19 -16 -11 900 810 710 680 780 11 32 30.5 SQF 44 SQFS4S 0-3.1 -4 -8 -18 -24 -19 -16 -11 900 860 760 730 830 11 42 10.9 SQF 61 SQFS4S 0-1.9 -4 -8 -18 -24 -19 -16 -11 900 860 760 730 830 11 42 10.9 SQF 45 SQFS5S 0-4.3 -4 -8 -18 -24 -19 -16 -11 900 980 880 830 930 12.5 61 5.47 SQF 62 SQFS5S 0-2.7 -4 -8 -18 -24 -19 -16 -11 900 980 880 830 930 12.5 61 5.47 SQF 46 SQFS6S 0-6.5 -4 -8 -18 -24 -19 -16 -11 900 1080 980 930 1030 12.5 68 5.47 SQF 63 SQFS7S 0-4.2 -4 -8 -18 -24 -19 -16 -11 900 1080 980 930 1030 12.5 81 1.54 SQF 64 SQFS8S 0-6 -4 -8 -18 -24 -19 -16 -11 900 1180 1080 1030 1130 12.5 86 1.54 Note: Air Pressure Drop of Attenuator (Pa) = Z x Q2 where Z = Factor listed in table above Q = Air Volume Flow Rate (m3/s)
B

C

E ctrs

16 flange holes 11mm dia (2 planes equi-spaced)

F ctrs

A

Guard for Square Fans
Manufactured from galvanised steel wire or polyester coated mild steel. Resistance to airflow is negligible.
Code Squif Fan A B SQFGD 1 SQF41-3 532 532 SQF41-1 SQFGD 2 SQF42-3 730 630 SQF42-1 SQFGD 3 SQF43-3 780 680 SQF43-3 SQFGD 4 SQF44 830 730 SQF61 SQFGD 5 SQF45 930 830 SQF62 SQFGD 6 SQF46 1030 930 SQF63 SQFGD 7 SQF64 1130 1030 C 11 13 13 13 13 13 13
4 holes B dia A sq

Double Flanged Flexible Connectors
Flexible duct material is flame proof. Heat resistance is 400°C with excellent resistance to chemicals, ozone, oil and grease. The connector is air-tight, waterproof and tested to BS476 Part 7.
Code
SQFF 1 SQFF 2 SQFF 3 SQFF 4 SQFF 5 SQFF 6 SQFF 7
F ctrs C E ctrs

Squif Fan A
SQF41-3 SQF41-1 SQF42-3 SQF42-1 SQF43-3 SQF43-1 SQF44 SQF61 SQF45 SQF62 SQF46 SQF63 SQF64 150 150 150 150 150

B

C

F

E
532 630 680 730 830

A

B
16 flange holes 11mm dia (2 planes equi-spaced)

560 560 532 760 660 730 810 710 780 860 760 830 980 880 930

150 1080 980 1030 930 150 1180 1080 1130 1030

Download specification from www.nuairegroup.com/specifications smoke control fans I squif I 7.32

smoke control fans I squif technical information

smoke control fans technical information

Wiring
Single phase single speed. Two speed motors DOL starting on both speeds
observe the motor plate and connection details. 3 phase two speed tap/pam wound motors require a three contactor control. 3 phase Dual wound motors require a two contactor control.
Motor Terminal Box
Note: HIGH SPEED Supply 2U 2V 2W Link 1U 1V 1W LOW SPEED Supply 1U 1V 1W 2U 2V 2W E

Fan Unit X L N

L N
230V 1 phase 50 Hz supply

1U

1V

1W

Three phase motors are connected directly to the Motor Terminal Box.

400V 3 phase 50Hz supply

3 phase units up to 3KW 3 phase units with matched frequency inverter
Notes: Total length of motor leads should not exceed 50 mtrs. If a screened motor cable is used,maximum length should be 25 mtrs. Consult our Technical Department if you wish to use longer leads. Inverters are configured to suit specific fans and control applications as described on the Customer Order.

W2

U2

V2

U1

V1

W1

3 Phase input 400V 3 phase 50Hz supply
L1 L/L2 N/L3 PE/

Connections to motor
W V U

L1

L2

L3

E
L1 L2 L3
Ecosmart 3 phase

3 phase units 4KW and above

3 Phase only INVERTER SPEED CONTROL Connect as figure 7 or 8.

W2

U2

V2

U1

V1

W1

L1

L2

L3

E

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

Squif
Consultants Specification
System specification
The SMOKE EXTRACT fan Unit shall be configured and arranged as detailed on the drawings and in accordance with the schedule of equipment and shall be of the SQUIF type as manufactured by Nuaire. The units shall be manufactured heavy gauge Aluzinc corrosion resistant steel. The general construction is to class A leakage. The fan impeller and motor shall be selected to provide the most energy efficient solution conforming to part L regulations and shall be direct drive with EFF2 high efficiency motors to BS5000 as standard. The fan impeller shall be a high efficiency backward curved centrifugal design, manufactured in galvanised steel and the motor shall be positioned outside the ventilation airflow path. It shall provide excellent in duct and breakout noise levels. The unit shall be capable of continuous operation at 90°C and a one off operation at up to 400°C for a period of 2 hrs certified to EN12101-3. The unit has been independently tested for high temperature operation by BSRIA and certified by BSI. This shall be achieved using a standard non temperature rated motor. The unit is suitable for non smoke reservoir applications. A two speed version of the unit to be provided where specified and controlled in accordance with the specification and manufacturers recommendations. The unit shall be supplied with all necessary ancillaries as recommended by the manufacturer and in accordance with the equipment schedule. The contractor shall allow for all necessary ductwork transformations to and from the fan unit and any associated components in accordance with the manufacturers recommendations, DW 144 and general good practice. The unit and ancillaries shall be supplied with a 3 years manufacturer’s warranty The unit shall be of the SQUIF type as manufactured by Nuaire Ltd.

Download specification from www.nuairegroup.com/specifications smoke control fans I squif I 7.34

smoke control fans I squif technical information

smokecontrol car park ventilation

smoke control car park ventilation

As from April 2005 it is mandatory for all emergency smoke ventilation equipment for use in the EU to be independently tested in an accredited test facility and certified by the appropriate notified body (BSI)** to ensure its suitability for the purpose.

axusimpulse fans car park ventilation

All such equipment must be independently tested to BS EN12101-3:2002 Smoke and heat control systems. Specification for powered smoke and heat exhaust ventilators. Nuaire’s Axus range of high temperature fans and ancillaries have been tested at BSRIA* in accordance with the above standard, ensuring your system meets these stringent requirements. Nuaire, through their partners Airvent Systems, can offer a complete smoke ventilation solution for car parks & buildings in general from initial conceptual discussions right through the design, installation, commissioning and handover stages. Nuaire’s comprehensive high temperature range includes • Up to 1600mm diameter • 3000C for 2 hours • 4000C for 2 hours The Impulse system • Energy efficient – By monitoring the air quality and operating the system at optimum level the overall motor power and running costs can be reduced by up to 40% Space saving by up to 40% – Low depth unit eliminates the need for ducting, maximising car park space availability Full design & installation service – An experienced technical team offer design, supply, installation & commissioning to suit your project requirements Quiet systems – Unit has inlet and outlet silencers ensuring low noise levels are maintained Cost savings – Less ductwork can typically reduce costs by up to 30% Safety tested – All equipment is tested to EN12101-3, 3000C for 2 hours Fully reversible option – Flexible directional flow responds to any fire location Quick and easy installation - Unique mounting bracket allows for 2 stage, ‘quick’ installation Warranty – AXUS Impulse range has a 3 year warranty

C



B



• • • • • •

A

*BSRIA – the Building Services Research and Information Association operate the only UKAS Accredited facility in the UK to test to EN 12101-3. (www.bsria.co.uk ) **BSI – the British Standards Institution, is the UK notified body under the Construction Products directive, under which compliance with this standard requires type testing and approval and monitoring of the factory production control systems. (www.bsi.co.uk)

Directional outlet diffuser

Inlet/Outlet silencer with integrated bell mouth

Unique mounting bracket

Safety inlet guard

How the system works
The car park impulse system is used to control and remove contaminants on a day to day basis, whilst ensuring that smoke is removed quickly and efficiently in the event of a fire. The systems utilises a number of strategically positioned impulse fans, mounted on the ceiling, that push the fumes and smoke towards a designated point of exhaust. This in effect compartmentalises the smoke stream ensuring quick and effective clearance whilst keeping the rest of the car park smoke free. This removes the need for complicated ductwork systems and optimises space.

1

3

The system runs at low speed ensuring that Carbon Monoxide levels and other contaminants are kept within acceptable limits. Strategically placed detectors monitor the air and control the units which can directly effect the condition.

Smoke detectors throughout the car park identify the units which can most effectively contain the smoke layer and increases the fan speed to maximum, the main exhaust unit is also switched to maximum.

2

4

A fire starts in one of the vehicles and smoke starts to spread throughout the car park, the smoke detection system identifies the situation and the fire alarm system will be activated.

Car Park Impulse Fan Key:
Low speed/day to day High speed/smoke mode Main exhaust/extract unit, low speed/day to day

The smoke layer is contained and directed towards the main extract unit, where the smoke can be safely exhausted to atmosphere. This maximises the space within the car park, keeping large areas clear of smoke, enabling the area to be quickly and safely evacuated.

Main exhaust/extract unit, high speed/smoke mode

Technical details and performance data
Fan Reference: Airflow m3/s: Half/Full Speed Thrust Newtons: Half/Full Speed* Motor Power kw: Half/Full Speed* Protection Class: Insulation: Electrical Supply Motor FLC amps: Half/Full Speed Motor SC amps: DOL Half/Full Speed Temperature Classification: EN12101-3 Speed RPM: Half/Full Speed Sound dBA @ 1m: Half/Full Speed Material Finish: Dimensions AxBxC (mm) See opposite * These are based on an airflow deflector angle of 50 SVT-1 (A-E) 0.5/1.1 5/24N 0.23/1.1 IP55 H 400/3/50 0.83/2.7A 2.9/14.5 3000deg. C for 2 hours 1370/2775 50/65 Galvanised 2610x320x600 SVT- 2 (A-E) 0.9/1.8 12/50N 0.23/1.1 IP55 H 400/3/50 0.83/2.7A 2.9/14.5 3000deg. C for 2 hours 1370/2775 52/67 Galvanised 2610X400X600

Fan Code Descriptions
SVT | 1
1 2 3

-

1 (A-E) | | 2 3

AXUS Impulse range Case size Impeller blade angle

t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com

technical specificationI car park impulse ventialtion system

Car park impulse system specification

Complete solution for car park ventilation
Airvent Systems have over twenty years experience in the smoke ventilation industry and their project managers were instrumental in establishing the first Car Park impulse system in the UK, designing, installing and commissioning the system Airvent systems utilise the latest computer aided design, computational fluid dynamic technology and extensive testing, to master the physics and behaviour of fires within buildings. By understanding the movement of the fire and smoke and combining that with the knowledge and expertise of fire engineering, ventilation and containment principles, Airvent are capable of designing bespoke smoke ventilation systems to protect any building and its occupants whilst providing safe, healthy, clean and welcoming car parks. Airvent offer; • • • • • • • • • Conceptual design UK’s largest sales engineer network Dedicated technical in-house support team Regulatory compliance/co-ordination Onsite liaison Installation Commissioning Maintenance Whole life support facility

The car park ventilation system shall control and remove pollutants, such as Carbon Monoxide, on a day to day basis, whilst ensuring that smoke is removed quickly and efficiently in the case of fire. The car park Impulse Ventilation System shall consist of a number of strategically positioned acoustically treated Impulse fans distributed throughout the car park, the positions shall be in accordance with the specialists design & layout drawings. Carbon Monoxide & smoke detectors shall be strategically placed in accordance with the specialists design and shall control the operation of the impulse fans in individual areas appropriately. By controlling the fans in this way the impulse fans will contain pollutants and smoke within a defined & predetermined corridor and channel its flow to the extract point where it can be evacuated safely to atmosphere by the main exhaust fan unit. The control system ensures that only the fans that can directly effect the ventilation requirement are in operation. The Nuaire SVT impulse unit comprises a high temperature axial fan with specially designed inlet and outlet attenuators which, along with the fan unit, are encased in a Galvanised steel acoustic enclosure. The Nuaire SVT unit comprising fan/motor assembly, and inlet & outlet silencers shall be certified for high temperature operation at 3000C for 2 hours, the range shall have been type tested to EN12101-3.The Axus Main exhaust unit and ancillaries shall have been type tested and certified for high temperature operation at 3000C for 2 hours to EN12101-3. The units shall be either 2 speed or inverter driven providing, low speed for day to day environmental extract and one off operation for emergency extract. They shall also be suitable for reversible operation. Fully reversible options (i.e similar duty in both airflow directions) are available, please contact Nuaire for details. The unit shall have a unique mounting bracket, which shall enable the bracket to be positioned as a “first fix” component with the unit being fitted as a “second fix” component, avoiding possible mechanical damage. The Nuaire SVT unit shall have inlet guards for safety purposes and also to prevent debris being sucked through the fan. It also has a specially designed airflow deflector to direct the jet stream from the fan at the required angle sufficient to overcome the natural buoyancy effect of the smoke. The car park impulse units shall be the SVT type and the main Exhaust unit shall be the high temperature AXUS type all as manufactured by Nuaire.

Contact us to discuss your requirements or for a focused and highly relevant CPD seminar at a location to suit your team tel:029 (20) 858 200.

Systems Designed for Life
t: +44 (0)29 2085 8200 f: +44 (0)29 2085 8300 e: [email protected] www.nuairegroup.com/specifications

August 2006 Issue 1