Technical Detail for Mv Switchgear

Published on December 2016 | Categories: Documents | Downloads: 54 | Comments: 0 | Views: 316
of 10
Download PDF   Embed   Report

STANDARD SPECIFICATION ABOUT MV SWITCHGEAR & CONTROL GEAR

Comments

Content

AN HOI DIESEL POWER PLANT

DATA SHEET

TITLE: DATA SHEET FOR MV SWITCHGEAR & PANEL

PROJECT NAME: AN HOI DIESEL POWER PLANT CLIENT: CON DAO COMMITTEE PROJECT NO.:

REV. NO.

DATE

DESCRIPTION

PREP'N

REVIEW

CHECK

APPROVAL

REV. NO. PREPARATION DEPT.

PREP'N

REVIEW

CHECK

APPROVAL

NGOC N.T A 28-Jul-11

AN HOI DIESEL POWER PLANT

PAGE: 1 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
0

Service Description:

MV SWICHGEAR ENVIRONMENTAL CONDITIONS POWER SYSTEM

Location: Ambient air temp: Humidity:

Indoor Min: 87% 13.8 °C

Outdoor Max: Altitude: 40 °C < 1000m

System Voltage: System Frequency: Neutral Earthing:

22000 50 N/A

V Hz

 

5% 2%

Hazardous area classification:
PARTICULARS OF EQUIPMENT MV SWITCHGEAR GENERAL DATA

Non-Hazardous
UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

Standard of Manufacture Type Location Rated voltage Rated frequency Number of phases Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency w'stand voltage Rated short time withstand current and time Internal arc fault withstand, to IEC 60298 Annex AA Duration of internal arc fault test Rated peak withstand current Earth busbar withstand current and time Busbar system: Rated normal current (main busbar) Phase segregated busbars Busbar arrangement (Single / Duplicate) Busbar identification Busbar material Busbar insulation Future busbar extension at either end Yes/No Yes/No A Yes / No 400 VTA Single Colour coded (R-Y-B) HDHC copper Yes No secs kA (peak) kA (rms) kV (peak) kV (rms) kA (rms) kV Hz Air insulated, metal enclosed Indoor, non-hazardous 24 50 3 95 50 (1 minute) 12.5 kA for 1 secs Criteria 1 through 6 1 125 12.5 kA for 1 secs

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

Document/drawings: Single line diagrams Project specification

0

49 50

AN HOI DIESEL POWER PLANT

PAGE: 2 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
0

Service Description:

MV SWICHGEAR

ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS Voltage V W PURCHASER'S REQUIREMENTS 230 VAC
VTA

PARTICULARS OF EQUIPMENT Anti-condensation heaters:(external source)

VENDOR'S RESPONSE

Power consumption Panel exterior paint colour Panel interior paint colour

Light grey 10 A 03 White
0

Paint specification Overall dimensions of the switchboard: Total weight Largest shipping section dimensions Shipping sections (number and weights) Expected assembly heat dissipation Ingress protection rating Earthing: Method of busbar earthing Rated short circuit current and time Asymmetrical peak making current capability Key interlock kA kA pk Yes/No (L X W x H) LxWxH mm kg mm kg kW

VTA
VTA (Note 7) VTA VTA VTA VTA

IP42

Earth switch (ES) 25 kA for 3 secs 125 Yes, with VCBs

TEST REQUIREMENTS
0

Type Test Routine Tests Special Tests

Yes/No Yes/No Yes/No

Certificate only required Yes, see Note 4 No

41 42 43 44 45 46 47 48 49
0

50 51 52 53

AN HOI DIESEL POWER PLANT

PAGE: 3 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
0

Service Description:

MV SWICHGEAR

ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

PARTICULARS OF EQUIPMENT CIRCUIT BREAKER PANEL DATA (* Current Rating Amps) Number of circuit breakers Panel type Rated normal current Rated voltage Rated short time withstand current and time Rated peak withstand current Rated short circuit breaking current Rated dc component of short circuit breaking current Insulation levels: Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency withstand voltage Trip coil: Voltage Power Close coil: Voltage Power Circuit breaker closing time Circuit breaker opening time Mechanical endurance Electrical endurance Anti pumping device Mechanical operations counter Manual mechanical trip facility Closed/open position indication Charged/discharged spring indication Emergency shutdown (ESD) trip Load shedding trip Power cable entry Control cable entry Gland plate

No.

one (1) Vacuum or SF6, withdrawable

A
0

400 24 25 kA for 3 secs 125 50 ≥ 35

kV kA (rms) kA (peak) kA (rms) %

kV (peak) kV (rms) V VA V VA msecs msecs #
0

110 kV across contacts 60 kV across contacts for 1 min 230 VAC (from UPS source) VTA N/A N/A VTA VTA VTA VTA Yes Yes Yes Yes
0

# Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No

Yes No No Bottom Bottom Brass
0

Overall dimensions of the panel: Panel Control and Indication

(D x W x H)

mm
0

VTA

"Closed" indication (Red) "Open" indication (Green) Tripped circuit or blown fuse indication (Amber) Anti-condensation heater 'ON' indication Indication Earth switchgear Free contacts for remote Indications HV switchgear Closed HV switchgear opened Earth switch connected / disconnected

Yes/No
0

Yes Yes Yes Yes Yes
0

Yes/No Yes/No Yes/No Yes/No

Yes/No Yes/No Yes/No

Yes Yes Yes

56

AN HOI DIESEL POWER PLANT

PAGE: 4 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
0

Service Description:

MV SWICHGEAR

ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

PARTICULARS OF EQUIPMENT

Control mode
0

LOCAL Yes/No Yes/No
0

Ammeter & selector switch Voltmeter & selector switch Trip & control circuit supervision Digital multimeter functions Relay Types Differential Feeder Protection Lockout Trip Circuit Supervision Under voltage/Overvoltage Other

Yes Yes Yes Yes (as per Single line Diagrams) Make Model

Yes/No Yes/No

Yes/No

No As per drawings As per drawings As per drawings As per drawings As required

Communications Communications with DCS: Protocol DCS control inputs DCS status outputs Hardware Redundant Yes/No Yes/No Yes/No
0

Modbus RS485/RS232 Yes Yes Yes

MV CABLES Outgoing Feeders:
0

Type of cable Voltage grade No. of cables and conductor size Cable entry Incomers: Type of cable Voltage grade No. of cables and conductor size Cable entry kV mm²
0

kV
0

mm² Top/bottom

Top/bottom
0

52 53
0

54

AN HOI DIESEL POWER PLANT

PAGE: 5 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 Location: Ambient air temp: Humidity:
Service Description: MV PANEL ENVIRONMENTAL CONDITIONS POWER SYSTEM

Indoor Min: 87% 13.8 °C

Outdoor Max: Altitude: 40 °C < 1000m

System Voltage: System Frequency: Neutral Earthing:

22000 50

V Hz

 

5% 2%

Isolated neutral

Hazardous area classification:
PARTICULARS OF EQUIPMENT MV PANEL GENERAL DATA

Non-Hazardous
UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

Standard of Manufacture Type Location Rated voltage Rated frequency Number of phases Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency w'stand voltage Rated short time withstand current and time Internal arc fault withstand, to (IEC 60298 Annex AA.6) Duration of internal arc fault test Rated peak withstand current Earth busbar withstand current and time Busbar system: Rated normal current (main busbar) Phase segregated busbars Busbar arrangement (Single / Duplicate) Busbar identification Busbar material Busbar insulation Future busbar extension at either end Panel exterior paint colour Panel interior paint colour
0

Air insulated, metal enclosed Indoor, non-hazardous kV Hz 24 50 3 kV (peak) kV (rms) kA (rms) 95 50 (1 minute) 12.5 kA for 1 secs Criteria 1 through 6 sec kA (peak) kA (rms) 1 125 12.5 kA for 1 secs

A Yes / No

400 VTA Single Colour coded (R-Y-B) HDHC copper

Yes/No Yes/No

Yes No Light grey 10 A 03 White VTA

Paint specification Overall dimensions of the switchboard: Total weight Largest shipping section dimensions Shipping sections (number and weights) Expected assembly heat dissipation Ingress protection rating Document/drawings: Single line diagrams Project specification
0

LxWxH

mm kg

VTA (Note 7) VTA VTA VTA VTA

(L X W x H)

mm kg kW

IP42

AN HOI DIESEL POWER PLANT

PAGE: 6 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
0

Service Description:

MV PANEL

ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS Yes/No
0

PARTICULARS OF EQUIPMENT Anti condensation heater Anti condensation heater rating & voltage Power cable entry Control cable entry Gland plate Overall dimensions of the panel: (D x W x H)

PURCHASER'S REQUIREMENTS No N/A
0

VENDOR'S RESPONSE

W/V

Bottom Bottom Brass mm
0

VTA

18 19 20 21 22
0

23
0

24 25 26 27 28

TEST REQUIREMENTS
0

Type Test Routine Tests Special Tests

Yes/No Yes/No Yes/No
0

Certificate only required Yes, see Note 4 No

29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
0

52 53 54 55

AN HOI DIESEL POWER PLANT

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 Location: Ambient air temp: Humidity:
Service Description: MV PANEL

091135-PVG-EK-003 PAGE: 7 of 9

ENVIRONMENTAL CONDITIONS Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

PARTICULARS OF EQUIPMENT CIRCUIT BREAKER DATA (* Current Rating Amps) Number of circuit breakers Panel type Rated normal current Rated voltage Rated short time withstand current and time Rated peak withstand current Rated short circuit breaking current Rated dc component of short circuit breaking current Insulation levels: Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency withstand voltage INDICATION & METERING Anti condensation heater Anti condensation heater rating & voltage Power cable entry Control cable entry Gland plate

No.

one (1) Load Break Switch with HRC Fuses

A
0

400 24 12.5 kA for 1 secs 125 50 ≥ 35

kV kA (rms) kA (peak) kA (rms) %

kV (peak) kV (rms)

110 kV across contacts 60 kV across contacts for 1 min

Yes/No W/V

No N/A Bottom Bottom Brass
0

Overall dimensions of the panel: Indications

(D x W x H)

mm
0 0

VTA

"Closed" indication (Red) "Open" indication (Green) Blown fuse indication (Amber) Anti-condensation heater 'ON' indication Control mode selector switch

Yes/No Yes/No Yes/No
0

Yes Yes Yes No LOCAL
0

Yes/No

Metering Kilowatt Hours meter Number of phases Current transformer Potential Transformer LIGHTNING SURGE ARRESTORS Rated voltage Rated frequency Continuous operating voltage Nominal discharge current Power frequency reference voltage Lightning impulse residual voltage Steep current impulse residual voltage Switching impulse residual voltage kV Hz
0

Yes/No
0

Yes 3 phase

Make

Model

Yes/No Yes/No

Yes Yes

24 48 - 62 19.2
0

kV kA kV kV kV
0

10 24 VTA VTA VTA

kV

AN HOI DIESEL POWER PLANT

PAGE: 8 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
0

Service Description:

MV PANEL

ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

PARTICULARS OF EQUIPMENT LIGHTNING SURGE ARRESTORS (Continuing) Rectangular current withstand 2000 μs High current withstand 4/10 μs Line discharge Class

kA
0

VTA VTA 1
0

kA

Partial discharge Creepage distance Lightning impulse withstand Power frequency withstand (wet 1 min) HV CABLES Cable in
0

VTA mm kV kV VTA VTA VTA

Type of cable Voltage grade No. of cables and conductor size Cable entry Cable out Type of cable Voltage grade No. of cables and conductor size Cable entry kV mm²
0

kV
0

mm² Top/bottom

Top/bottom
0

31 32 33 34 35 36 37 38 39 40 41 42
0

43 44 45 46 47 48
0

49
0

50
0

51 52
0

AN HOI DIESEL POWER PLANT

PAGE: 9 of 9

DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
0

Service Description:

MV SWICHGEAR / PANEL

ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 °C Outdoor Max: Altitude: 40 °C < 1000m System Voltage: System Frequency: Neutral Earthing:

POWER SYSTEM 22000 50 V Hz   5% 2%

Isolated neutral

Hazardous area classification:

Non-Hazardous UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE

PARTICULARS OF EQUIPMENT NOTES:

1. Withdrawable circuit breakers shall be interchangeable with others of the same voltage and current rating. 2. Circuit breaker operating mechanisms shall be of the motor/manual spring charge, stored energy, manual/electrical release type. 3. Rated short time withstand & breaking currents for circuit breakers shall be not less than ratings for main busbar.
0

4. Refer to High Voltage Switchgear Specification for additional information. 5. Refer to Metering & Protection SLD 6. Refer to Electrical Equipment Layout for additional information. 7. VTA = Vendor to advise. 8. N/A = Not Application

27 28 29 30 31 32 33 34 35
0

36 37 38 39 40 41 42 43 44 45 46 47 48 49